This document is applicable to ceramic insulated outdoor bushings for highest voltages for equipment of 24 kV and 36 kV, with rated currents of 5 kA and 8 kA for insulating liquid filled transformers and frequencies from 15 Hz up to 60 Hz.
This document establishes dimensions to ensure interchangeability and adequate mounting of bushings.
Two types of construction are specified, type A and type B, both types for highest voltages for equipment 24 kV and 36 kV and rated currents of 5 kA and 8 kA. The mechanical stresses of the conductor tube define the difference between type A and type B. The conductor tube of type A is axially and radially fixed in the top of the bushing. The inner line terminal of the transformer can be flexible and without any special support for the lower end of the conductor tube.
For new installations bushings of Type A are expected to be used. Type B bushings can be supplied at the request of a customer.
In case of type B, the conductor tube is only radially fixed in the top of the bushing. In that case, a rigid support is mounted to fix the lower end of the conductor tube (for example, in combination with a drip proofed sealing end). The drip proofed sealing end is often required in the service requirements. In this case, it is not possible to use type A because of the existing double fixation. Therefore, both bushing types A and B are be specified.
The condition for the usage of type B is that the drip-proof sealing end is able to withstand the mechanical stress in axial direction.

  • Standard
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document is applicable to ceramic insulated outdoor bushings for highest voltages for equipment of 24 kV and 36 kV, with rated currents of 5 kA and 8 kA for insulating liquid filled transformers and frequencies from 15 Hz up to 60 Hz. This document establishes dimensions to ensure interchangeability and adequate mounting of bushings. Two types of construction are specified, type A and type B, both types for highest voltages for equipment 24 kV and 36 kV and rated currents of 5 kA and 8 kA. The mechanical stresses of the conductor tube define the difference between type A and type B. The conductor tube of type A is axially and radially fixed in the top of the bushing. The inner line terminal of the transformer can be flexible and without any special support for the lower end of the conductor tube. For new installations bushings of Type A are expected to be used. Type B bushings can be supplied at the request of a customer. In case of type B, the conductor tube is only radially fixed in the top of the bushing. In that case, a rigid support is mounted to fix the lower end of the conductor tube (for example, in combination with a drip proofed sealing end). The drip proofed sealing end is often required in the service requirements. In this case, it is not possible to use type A because of the existing double fixation. Therefore, both bushing types A and B are specified. The condition for the usage of type B is that the drip-proof sealing end is able to withstand the mechanical stress in axial direction.

  • Standard
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document is applicable to insulated bushings, excluding those plug-in bushings specified by EN 50180 series, for use in air insulated, shroud insulated and fully insulated cable boxes for liquid filled transformers and reactors for rated voltages up to 36 kV, and rated currents up to 4 000 A at frequencies from 15 Hz to 60 Hz.

  • Standard
    17 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    17 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Extend the scope of the EN50180-1/2/3 and EN50181 for plug-in type bushings up to 72.5 kV

  • Standard
    14 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document is applicable to insulated bushings, excluding those plug-in bushings specified by EN 50180 series, for use in air insulated, shroud insulated and fully insulated cable boxes for liquid filled transformers and reactors for rated voltages up to 36 kV, and rated currents up to 4 000 A at frequencies from 15 Hz to 60 Hz.

  • Standard
    17 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    17 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This International Standard applies to outdoor and indoor bushings of any voltage used on DC systems, of capacitance graded or gas insulated types for use as components of oil-filled converter transformers and smoothing reactors, as well as air-to-air DC bushings. This standard does not apply to the following: • cable terminations (potheads); • bushings for instrument transformers; • bushings for test power supplies; • bushings applied with gaseous insulation (other than air at atmospheric pressure) external to the bushing; • bushings for industrial application; • bushings for traction application; • bushings for distribution class transformers. This standard makes reference to IEC 60137 for general terms and conditions and defines the special terms used, operating conditions, ratings, test procedures as well as general mechanical and electrical requirements for bushings for DC application.

  • Standard
    56 pages
    English language
    sale 10% off
    e-Library read for
    1 day

NEW!IEC 60137:2017 is available as IEC 60137:2017 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 60137:2017 specifies the characteristics and tests for insulated bushings. This standard is applicable to bushings, as defined in Clause 3, intended for use in electrical apparatus, machinery, transformers, switchgear and installations for three-phase alternating current systems, having highest voltage for equipment above 1 000 V and power frequencies of 15 Hz up to and including 60 Hz. Subject to special agreement between purchaser and supplier, this standard may be applied, in part or as a whole, to the following: - bushings used in other than three-phase systems; - bushings for high-voltage direct current systems; - bushings for testing transformers; - bushings for capacitors. Special requirements and tests for transformer bushings in this standard apply also to reactor bushings. This standard is applicable to bushings made and sold separately. Bushings which are a part of an apparatus and which cannot be tested according to this standard should be tested with the apparatus of which they form part. This edition includes the following significant technical changes with respect to the previous edition: - Resin-impregnated synthetic (RIS) bushings has been introduced. - Bushings with Um ≤ 1,1 kV, Um = 1100 kV and Um = 1200 kV have been introduced. - Temperature rise testing has been included for liquid-insulated bushings according to clause to 3.4. - Introducing dry lightning impulse testing as a routine test for all transformer bushings with Um > 72,5 kV. - The altitude correction procedure has been revised ( > 1 000 m). - An explanation about Very Fast Transient (VFT) phenomenon and its impact on bushings has been included.

  • Standard
    64 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Integrate the not accepted changes of the work of WG1 proposed in the meeting on 23th October 2014 in EN50180-3

  • Amendment
    5 pages
    English language
    sale 10% off
    e-Library read for
    1 day

CCMC - wrong standard reference to be corrected

  • Corrigendum
    1 page
    English language
    sale 10% off
    e-Library read for
    1 day

This document is applicable to plug-in type bushings, according to EN 60137, 72,5 kV, rated currents
from 630 A up to 1 250 A and frequencies from 15 Hz up to 60 Hz for single or three-phase arrangements in electrical equipment like liquid filled transformers or gas insulated switchgear and controlgear. It complements and amends, if necessary, the relevant EN standards.
The application of such plug-in type bushings is derived from EN 50180 and EN 50181 but applied for higher voltages with described deviations to EN 50299-2 and EN 62271-209.
This standard does not cover the connection assembly as described in EN 50299-2 and EN 62271-209.
EN 60137 and HD 632 series outline the qualification, type test, routine and sample test of plug-in type bushings according to this standard.
This document establishes essential dimensions and testing procedures, to ensure adequate mounting and interchangeability of mating plug-in separable connectors of equivalent ratings.

  • Standard
    14 pages
    English language
    sale 10% off
    e-Library read for
    1 day

CCMC - wrong standard reference to be corrected

  • Corrigendum
    1 page
    English language
    sale 10% off
    e-Library read for
    1 day

IEC - Corrected version

  • Corrigendum
    3 pages
    English and French language
    sale 10% off
    e-Library read for
    1 day

This International Standard applies to outdoor and indoor bushings of any voltage used on DC
systems, of capacitance graded or gas insulated types for use as components of oil-filled
converter transformers and smoothing reactors, as well as air-to-air DC bushings. This
standard does not apply to the following:
• cable terminations (potheads);
• bushings for instrument transformers;
• bushings for test power supplies;
• bushings applied with gaseous insulation (other than air at atmospheric pressure) external
to the bushing;
• bushings for industrial application;
• bushings for traction application;
• bushings for distribution class transformers.
This standard makes reference to IEC 60137 for general terms and conditions and defines the
special terms used, operating conditions, ratings, test procedures as well as general
mechanical and electrical requirements for bushings for DC application.

  • Standard
    56 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC - Corrected version

  • Corrigendum
    3 pages
    English and French language
    sale 10% off
    e-Library read for
    1 day

This European Standard should be considered in factual context with EN 50180 only. Constructional details for fastenings and their details are supplementing EN 50180. This information is of importance for utilities concerning compatibility. For a better understanding of additional information some dimension from EN 50180 are repeated in this European Standard. This European Standard was extended for fastenings of bushings for a highest voltage of 52 kV.

  • Standard
    11 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard should be considered in factual context with EN 50180 only. The dimensional supplements are related to figures and tables of EN 50180. To enable a better understanding of additional information some tables from EN 50180 are used and extended. This European Standard may now be used also for bushings with a highest voltage of 52 kV. Figures for the details of the components and the related tables are added according to the extended range of voltage.

  • Standard
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard is applicable to ceramic and resin insulated bushings having highest voltages above 1 kV up to 52 kV, rated currents from 250 A up to 3 150 A and frequencies from 15 Hz up to 60 Hz for insulating liquid filled transformers. This European Standard establishes essential dimensions, to ensure interchangeability of bushings and to ensure adequate mounting and interchangeability of mating plug-in separable connectors of equivalent ratings.

  • Standard
    39 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This International Standard specifies the characteristics and tests for insulated bushings.
This standard is applicable to bushings, as defined in Clause 3, intended for use in electrical
apparatus, machinery, transformers, switchgear and installations for three-phase alternating
current systems, having highest voltage for equipment above 1 000 V and power frequencies
of 15 Hz up to and including 60 Hz.
Subject to special agreement between purchaser and supplier, this standard may be applied,
in part or as a whole, to the following:
• bushings used in other than three-phase systems;
• bushings for high-voltage direct current systems;
• bushings for testing transformers;
• bushings for capacitors.
Special requirements and tests for transformer bushings in this standard apply also to reactor
bushings.
This standard is applicable to bushings made and sold separately. Bushings which are a part
of an apparatus and which cannot be tested according to this standard should be tested with
the apparatus of which they form part.

  • Standard
    64 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Integrate the not accepted changes of the work of WG1 proposed in the meeting on 23th October 2014 in EN50180-3

  • Amendment
    5 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC TS 60079-46:2017 specifies requirements for the design, construction, assembly, testing, inspection, marking, documenting and assessment of equipment assemblies for use in explosive atmospheres under the responsibility of the manufacturer of the equipment assembly. The requirements of this document apply to individual items according to the IEC 60079 series or ISO 80079 series that comprise the assembly and that have individual certificates. These individual items are then integrated as part of the equipment assembly. Also included are requirements to address aspects for the assembly which may be beyond the certificates of the individual items forming the assembly. The scope of this document includes assessment of the additional requirements for assemblies for hazardous areas and does not include requirements for non-hazardous areas. It is assumed that compliance with other electrical or mechanical requirements that are applicable for non-hazardous areas will be verified by either the same or different party in addition to the requirements of this document. This document does not apply to:
- equipment which is covered, in its entirety, by one or more IEC 60079 and ISO 80079 equipment types of protection;
- pressurized rooms, “p”, in accordance with IEC 60079-13, artificial ventilation for the protection of analyzer(s) houses in accordance with IEC TR 60079-16, and other standards addressing specific Ex assemblies;
- installation at the end-user site under the scope of IEC 60079-14;
- classification of the hazardous area;
- equipment assemblies for mines susceptible to firedamp (Group I applications);
- inherently explosive situations and dust from explosives or pyrophoric substances (for example explosives manufacturing and processing);
- rooms used for medical purposes;
- electrical installations in areas where the hazard is due to flammable mist.
The specification is only intended to provide validation for the initial supply of an assembly.
Keywords: equipment assemblies for use in explosive atmospheres

  • Technical specification
    33 pages
    English and French language
    sale 15% off

IEC 62041: 2017 is applicable to transformers, reactors and power supply units covered by the IEC 61558 series of standards. This document deals with the electromagnetic compatibility requirements for emission and immunity within the frequency range 0 Hz to 400 GHz. No tests need to be performed at frequencies where no requirements are specified.
This third edition cancels and replaces the second edition published in 2010. It constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
the inclusion of a clause on tests in series production;
the inclusion of a new clause on measurement uncertainly, and
the status of a harmonized standard for this third edition.
It has the status of a product family EMC standard in accordance with IEC Guide 107:2009,
Electromagnetic compatibility – Guide to the drafting of electromagnetic compatibility publications.

  • Standard
    62 pages
    English and French language
    sale 15% off

IEC 60137:2017 is now available as IEC 60137:2017 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.
IEC 60137:2017 specifies the characteristics and tests for insulated bushings.
This standard is applicable to bushings, as defined in Clause 3, intended for use in electrical apparatus, machinery, transformers, switchgear and installations for three-phase alternating current systems, having highest voltage for equipment above 1 000 V and power frequencies of 15 Hz up to and including 60 Hz.
Subject to special agreement between purchaser and supplier, this standard may be applied, in part or as a whole, to the following:
- bushings used in other than three-phase systems;
- bushings for high-voltage direct current systems;
- bushings for testing transformers;
- bushings for capacitors.
Special requirements and tests for transformer bushings in this standard apply also to reactor bushings.
This standard is applicable to bushings made and sold separately. Bushings which are a part of an apparatus and which cannot be tested according to this standard should be tested with the apparatus of which they form part. This edition includes the following significant technical changes with respect to the previous edition:
- Resin-impregnated synthetic (RIS) bushings has been introduced.
- Bushings with Um ≤ 1,1 kV, Um = 1100 kV and Um = 1200 kV have been introduced.
- Temperature rise testing has been included for liquid-insulated bushings according to clause to 3.4.
- Introducing dry lightning impulse testing as a routine test for all transformer bushings with Um > 72,5 kV.
- The altitude correction procedure has been revised ( > 1 000 m).
- An explanation about Very Fast Transient (VFT) phenomenon and its impact on bushings has been included.
The contents of the corrigendum of May 2018 have been included in this copy.

  • Standard
    124 pages
    English and French language
    sale 15% off

IEC TS 61463:2016(E), which is a Technical Specification, is applicable to alternating current and direct current bushings for highest voltages above 52 kV (or with resonance frequencies placed inside the seismic response spectrum), mounted on transformers, other apparatus or buildings. For bushings with highest voltages less than or equal to 52 kV (or with resonance frequencies placed outside from the seismic response spectrum), due to their characteristics, seismic qualification is not used as far as construction practice and seismic construction practice comply with the state of the art. This document presents acceptable seismic qualification methods and requirements to demonstrate that a bushing can maintain its mechanical properties, insulate and carry current during and after an earthquake. The seismic qualification of a bushing is only performed upon request.

  • Technical specification
    40 pages
    English language
    sale 15% off

This European Standard is applicable to ceramic and resin insulated bushings having highest voltages above 1 kV up to 52 kV, rated currents from 250 A up to 3 150 A and frequencies from 15 Hz up to 60 Hz for insulating liquid filled transformers.
This European Standard establishes essential dimensions, to ensure interchangeability of bushings and to ensure adequate mounting and interchangeability of mating plug-in separable connectors of equivalent ratings.

  • Standard
    39 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard should be considered in factual context with EN 50180-1 only. The dimensional
supplements are related to figures and tables of EN 50180-1. To enable a better understanding of additional
information some tables from EN 50180-1 are used and extended.
This European Standard may now be used also for bushings with a highest voltage of 52 kV. Figures for the
details of the components and the related tables are added according to the extended range of voltage.

  • Standard
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard should be considered in factual context with EN 50180-1 only. Constructional details
for fastenings and their details are supplementing EN 50180-1. This information is of importance for utilities
concerning compatibility.
For a better understanding of additional information some dimension from EN 50180-1 are repeated in this
European Standard.
This European Standard was extended for fastenings of bushings for a highest voltage of 52 kV.

  • Standard
    11 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC/IEEE 65700-19-03:2014 applies to outdoor and indoor bushings of any voltage used on DC systems, of capacitance graded or gas insulated types for use as components of oil-filled converter transformers and smoothing reactors, as well as air-to-air DC bushings. This standard makes reference to IEC 60137 for general terms and conditions and defines the special terms used, operating conditions, ratings, test procedures as well as general mechanical and electrical requirements for bushings for DC application. This standard replaces IEC 62199:2004, Bushings for DC application.

  • Standard
    109 pages
    English and French language
    sale 15% off

This European Standard is applicable to ceramic insulated bushings for rated voltages up to 1 000 V, rated currents from 250 A up to 5 000 A and frequencies from 15 Hz up to 60 Hz for insulating liquid filled transformers.

  • Amendment
    4 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard is applicable to insulated bushings for maximum voltages above 1 kV up to 52 kV, rated currents from 250 A up to 2 500 A and frequencies from 15 Hz up to 60 Hz for equipment other than liquid filled transformers. This European Standard establishes essential dimensions, to ensure adequate mounting and interchangeability of mating plug-in separable connectors of equivalent ratings.

  • Standard
    11 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard is applicable to ceramic insulated bushings for rated voltages up to 1 000 V, rated currents from 250 A up to 5 000 A and frequencies from 15 Hz up to 60 Hz for insulating liquid filled transformers.

  • Standard
    8 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard is applicable to insulated bushings for maximum voltages above 1 kV up to 52 kV, rated currents from 250 A up to 2 500 A and frequencies from 15 Hz up to 60 Hz for equipment other than liquid filled transformers. This European Standard establishes essential dimensions, to ensure adequate mounting and interchangeability of mating plug-in separable connectors of equivalent ratings.

  • Standard
    11 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This Technical Specification is applicable to capacitance graded outdoor bushings with values of highest voltage for equipment (Um) from 52 kV up to 420 kV and with values of rated current (Ir) up to 3 150 A and frequencies from 15 Hz up to 60 Hz for oil immersed transformers. The major insulation of these bushings consists either of oil-impregnated or resin-impregnated paper or other suitable insulating systems. This Technical Specification establishes essential details and dimensions to ensure interchange ability and adequate mounting of the bushings.

  • Technical specification
    19 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This Technical Specification is applicable to capacitance graded outdoor bushings with values of highest voltage for equipment (Um) from 52 kV up to 420 kV and with values of rated current (Ir) up to 3 150 A and frequencies from 15 Hz up to 60 Hz for oil immersed transformers. The major insulation of these bushings consists either of oil-impregnated or resin-impregnated paper or other suitable insulating systems. This Technical Specification establishes essential details and dimensions to ensure interchange ability and adequate mounting of the bushings.

  • Technical specification
    19 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Applies to outdoor and indoor bushings of any voltage used on d.c. systems, of capacitance graded or gas insulated types for use as components of oil-filled converter transformers and smoothing reactors, as well as air-to-air d.c. bushings.

  • Standard
    28 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This standard is applicable to moulded indoor busbar bushings for rated voltages up to 1 000 V, rated currents from 1 250 A up to 5 000 A and frequencies from 15 Hz up to 60 Hz for insulating liquid filled transformers.
NOTE These bushings are suitable for operation at 1,1 kV in compliance with HD 428.1 S1.

  • Standard
    6 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This standard is applicable to ceramic insulated outdoor bushings for highest voltages for equipment of 24 kV and 36 kV, with rated currents of 5 kA and 8 kA and frequencies from 15 Hz up to 60 Hz for insulating liquid filled transformers.
This standard establishes dimensions to ensure interchangeability and adequate mounting of bushings.
Two types of construction are specified, type A and type B, both types for highest voltages for equipment 24 kV and 36 kV and rated currents of 5 kA and 8 kA. The mechanical stresses of the conductor tube make the difference between type A and type B. The conductor tube of type A is axially and radially fixed in the top of the bushing. The inner line terminal of the transformer can be flexible and without any special support for the lower end of the conductor tube.
In case of type B, the conductor tube is only radially fixed in the top of the bushing. In that case, a rigid support has to be mounted to fix the lower end of the conductor tube (for example, in combination with a drip proofed sealing end). The drip proofed sealing end is often required in the service requirements. In this case, it is not possible to use type A because of the existing double fixation. Therefore, both bushing types A and B have to be specified.
The condition for the usage of type B is that the drip prooved sealing end is able to withstand the mechanical stress in axial direction.

  • Standard
    18 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This standard is applicable to insulated bushings for use in air insulated, shroud insulated and fully insulated cable boxes for liquid filled transformers and reactors for rated voltages up to 36 kV, and rated currents up to 4 000 A at frequencies from 15 Hz to 60 Hz.

  • Standard
    14 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This standard is applicable to ceramic insulated outdoor bushings for highest voltages for equipment of 24 kV and 36 kV, with rated currents of 5 kA and 8 kA and frequencies from 15 Hz up to 60 Hz for insulating liquid filled transformers. This standard establishes dimensions to ensure interchangeability and adequate mounting of bushings. Two types of construction are specified, type A and type B, both types for highest voltages for equipment 24 kV and 36 kV and rated currents of 5 kA and 8 kA. The mechanical stresses of the conductor tube make the difference between type A and type B. The conductor tube of type A is axially and radially fixed in the top of the bushing. The inner line terminal of the transformer can be flexible and without any special support for the lower end of the conductor tube. In case of type B, the conductor tube is only radially fixed in the top of the bushing. In that case, a rigid support has to be mounted to fix the lower end of the conductor tube (for example, in combination with a drip proofed sealing end). The drip proofed sealing end is often required in the service requirements. In this case, it is not possible to use type A because of the existing double fixation. Therefore, both bushing types A and B have to be specified. The condition for the usage of type B is that the drip prooved sealing end is able to withstand the mechanical stress in axial direction.

  • Standard
    18 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This standard is applicable to insulated bushings for use in air insulated, shroud insulated and fully insulated cable boxes for liquid filled transformers and reactors for rated voltages up to 36 kV, and rated currents up to 4 000 A at frequencies from 15 Hz to 60 Hz.

  • Standard
    14 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This standard is applicable to vertical connecting terminal flags for insulated bushings with rated currents from 250 A to 4 000 A and frequencies from 15 Hz to 60 Hz for liquid immersed equipment.

  • Draft
    13 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Gives guidance for the interpretation of dissolved gas analysis (DGA) which has been developed for bushings, in service, where the main insulation (generally paper) is impregnated with mineral insulating oil according to IEC 60296. Is applicable to oil-filled and impregnated paper bushings in service. The contents of the corrigendum of January 2003 have been included in this copy.

  • Technical specification
    31 pages
    English and French language
    sale 15% off

This International Standard specifies the characteristics and tests for insulated bushings. This standard is applicable to bushings, as defined in Clause 3, intended for use in electrical apparatus, machinery, transformers, switchgear and installations for three-phase alternating current systems, having highest voltage for equipment above 1 000 V and power frequencies of 15 Hz up to and including 60 Hz. Subject to special agreement between purchaser and supplier, this standard may be applied, in part or as a whole, to the following: - bushings used in other than three-phase systems; - bushings for high-voltage direct current systems; - bushings for testing transformers; - bushings for capacitors. Special requirements and tests for transformer bushings in this standard apply also to reactor bushings. This standard is applicable to bushings made and sold separately. Bushings which are a part of an apparatus and which cannot be tested according to this standard should be tested with the apparatus of which they form part.

  • Standard
    61 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard is applicable to ceramic and resin insulated bushings having highest voltages above 1 kV up to 52 kV, rated currents from 250 A up to 3 150 A and frequencies from 15 Hz up to 60 Hz for insulating liquid filled transformers. This standard establishes essential dimensions, to ensure interchangeability of bushings and to ensure adequate mounting and interchangeability of mating plug-in separable connectors of equivalent ratings.

  • Standard
    37 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Amendment
    4 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Superseded by EN 62444:2013

  • Amendment
    9 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European standard provides requirements and tests for the construction and performance of metric cable glands. This standard covers complete glands as supplied by the manufacturer or supplier, but not parts of cable glands. Requirements and tests for metric cable glands with multi-orifice seals are under consideration. This standard does not cover cable glands: for fibre optic cables; for mineral insulated cables specified in HD 586: with a gland entry portion other than metric. NOTE: Certain cable glands may also be used in 'Hazardous Areas'. Regard should then be taken of other or additional requirements necessary for equipment to be installed in such conditions, for example as specified in EN 50014

  • Standard
    25 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard is applicable to ceramic and resin insulated bushings having highest voltages above 1 kV up to 52 kV, rated currents from 250 A up to 3 150 A and frequencies from 15 Hz up to 60 Hz for insulating liquid filled transformers. This standard establishes essential dimensions, to ensure interchangeability of bushings and to ensure adequate mounting and interchangeability of mating plug-in separable connectors of equivalent ratings.

  • Standard
    37 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 60137:2008 gives the characteristics and tests for insulated bushings intended for use in electrical apparatus, machinery, transformers, switchgear and installations for three-phase alternating current systems, having highest voltage for equipment above 1 000 V and power frequencies of 15 Hz up to and including 60 Hz. Special requirements and tests for transformer bushings in this standard apply also to reactor bushings. This edition includes the following significant technical changes with respect to the previous edition: - Long duration power-frequency for transformer bushings; - Special requirements for type and acceptance tests applicable to transformer and GIS bushings; - Specific insulation levels for bushings fitted to transformers and GIS; - According to IEC Guide 111, clauses relating to safety and the environment have been added; and - The altitude correctino procedure has been revised (> 1 000 m).

  • Standard
    61 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Supersedes HD 596 S1:1996

  • Standard
    6 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This standard is applicable to ceramic and resin insulated bushings for rated voltages above 1 kV up to 36 kV rated currents from 250A up to 3150 A and frequencies from 15 Hz up to 60 Hz for insulating liquid filled transformers. This standard establishes essential dimensions, to ensure interchangeability of bushings and to ensure adequate mounting and interchangeability of mating plug-in separable connectors of equivalent ratings

  • Standard
    36 pages
    English language
    sale 10% off
    e-Library read for
    1 day