IEC 62271-202:2022 specifies the service conditions, rated characteristics, general structural requirements and test methods of enclosed high-voltage prefabricated substations. These prefabricated substations are cable-connected to AC high-voltage networks with an operating voltage up to and including 52 kV and power frequencies up to and including 60 Hz. They can be manually operated from inside (walk-in type) or from outside (non-walk-in type). They are designed for outdoor installation at locations with public accessibility and where protection of personnel is provided.
This third edition cancels and replaces the second edition published in 2014. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
the whole document contents and structure are reviewed with due consideration of IEC 62271-1:2017;
modification of the title and scope to include high-voltage switchgear prefabricated substations;
inclusion of CEADS as a possible component of MV/LV prefabricated substation;
in 7.2.101, the possible influence of surrounding elements on the dielectric performance of high-voltage components as high-voltage switchgear and controlgear and high-voltage interconnections non-metal-enclosed or without earthed screen are now considered;
new informative Annex G with testing procedure to evaluate the impact of solar radiation in temperatures inside the enclosure and how to apply it;
new informative Annex H for appropriate consideration of installation conditions of electronic equipment;
the rated power of a prefabricated substation is now defined as a three-parameter rated value. See 5.101.1;
minimum dimensions for access doors to the prefabricated substation in 6.104.4 and for free height of operation aisle in 6.105.3 have been introduced;
continuous current (temperature rise) test methods have been revised/clarified where necessary;
Figure D.1, which shows the mineral-oil-immersed power transformer load factor inside the enclosure, has been corrected.

  • Standard
    2 pages
    English and French language
    sale 15% off

This part of IEC 62271 is applicable to AC switching devices designed for indoor or outdoor
installation, for operation at frequencies of 50 Hz and 60 Hz on systems having voltages above
1 000 V and applied for inductive current switching. It is applicable to switching devices
(including circuit-breakers in accordance with IEC 62271-100) that are used to switch
high-voltage motor currents and shunt reactor currents and also to high-voltage contactors used
to switch high-voltage motor currents as covered by IEC 62271-106.
Switching unloaded transformers, i.e. breaking transformer magnetizing current, is not
considered in this document. The reasons for this are as follows:
a) Owing to the non-linearity of the transformer core, it is not possible to correctly model the
switching of transformer magnetizing current using linear components in a test laboratory.
Tests conducted using an available transformer, such as a test transformer, will only be
valid for the transformer tested and cannot be representative for other transformers.
b) As detailed in IEC TR 62271-306, the characteristics of this duty are usually less severe
than any other inductive current switching duty. Such a duty can produce severe
overvoltages within the transformer winding(s) depending on the re-ignition behaviour of the
switching device and transformer winding resonance frequencies.
NOTE 1 The switching of tertiary reactors from the high-voltage side of the transformer is not covered by this
document.
NOTE 2 The switching of shunt reactors earthed through neutral reactors is not covered by this document. However,
the application of test results according to this document, on the switching of neutral reactor earthed reactors (4-leg
reactor scheme), is discussed in IEC TR 62271-306.

  • Standard
    32 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    29 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 62271-110:2023 is available as IEC 62271-110:2023 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 62271-110:2023 is applicable to AC switching devices designed for indoor or outdoor installation, for operation at frequencies of 50 Hz and 60 Hz on systems having voltages above 1 000 V and applied for inductive current switching. It is applicable to switching devices (including circuit-breakers in accordance with IEC 62271-100) that are used to switch high‑voltage motor currents and shunt reactor currents and also to high-voltage contactors used to switch high-voltage motor currents as covered by IEC 62271-106. This fifth edition cancels and replaces the fourth edition published in 2017. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: references to IEC 62271-100 and IEC 62271-106 have been updated to the latest editions.

  • Standard
    32 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    29 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 62271-110:2023 is available as IEC 62271-110:2023 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 62271-110:2023 is applicable to AC switching devices designed for indoor or outdoor installation, for operation at frequencies of 50 Hz and 60 Hz on systems having voltages above 1 000 V and applied for inductive current switching. It is applicable to switching devices (including circuit-breakers in accordance with IEC 62271-100) that are used to switch high‑voltage motor currents and shunt reactor currents and also to high-voltage contactors used to switch high-voltage motor currents as covered by IEC 62271-106. This fifth edition cancels and replaces the fourth edition published in 2017. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: references to IEC 62271-100 and IEC 62271-106 have been updated to the latest editions.

  • Standard
    61 pages
    English and French language
    sale 15% off

IEC 62271-212:2022 is available as IEC 62271-212:2022 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 62271-212;2022 specifies the service conditions, rated characteristics, general structural requirements and test methods of the assemblies of the main electrical functional units of a high-voltage transformer substation, duly interconnected, for AC voltages up to and including 52 kV on the high-voltage side and service frequency 50 Hz or 60 Hz. The CEADS is cable‑connected to the high-voltage network for indoor and outdoor applications of restricted access. This second edition cancels and replaces the first edition published in 2016. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: - clause numbering aligned with IEC 62271-1:2017, - rewording of title and scope of the document, - implement changes on internal arc definition and testing following the evolution of prefabricated substation concept according to IEC 62271-202, - general review of main test procedures such as temperature rise or dielectric test on interconnections, considering control equipment, communication, smart grid devices and integration of components, - general review of installation, operation, safety and maintenance requirements.

  • Standard
    84 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Standard
    84 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Amendment
    10 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    12 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Amendment
    10 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    12 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document applies to pressurized partitions used in indoor and outdoor installations of high-voltage AC and DC switchgear and controlgear with rated voltages (Ur) above 1 kV AC / 1,5 kV DC and with design pressure higher than 300 kPa, where the gas is used principally for its dielectric and/or arc-quenching properties.
Gases with insulating properties are dry air, inert gases, for example sulphur hexafluoride or nitrogen or a mixture of such gases.
The partitions comprise pressurized barriers in electrical equipment not necessarily limited to the following examples:
—   circuit-breakers;
—   switch-disconnectors;
—   disconnectors;
—   earthing switches;
—   current transformers;
—   voltage transformers;
—   surge arrestors;
—   busbars and connections;
—   cable connections / terminations
—   cable bushings
—   etc.
Partitions which are only pressurized from one side are also covered.
1 kV AC / 1,5 kV DC means it is valid for the apparatus applied and where the partitions are installed, however, the application of voltages below 1 kV AC / 1,5 kV DC as in e.g. current and voltage transformer are not excluded.
This document does not apply to high voltage bushings (see EN 60137, EN 61462 and EN 62155).

  • Standard
    16 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    15 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document applies to pressurized partitions used in indoor and outdoor installations of high-voltage AC and DC switchgear and controlgear with rated voltages (Ur) above 1 kV AC / 1,5 kV DC and with design pressure higher than 300 kPa, where the gas is used principally for its dielectric and/or arc-quenching properties. The partitions comprise pressurized barriers in electrical equipment not necessarily limited to the following examples: - circuit-breakers; - switch-disconnectors; - disconnectors; - earthing switches; - current transformers; - voltage transformers; - surge arresters; - busbars and connections; - cable connections/terminations; - cable bushings. Partitions which are only pressurized from one side are also covered. 1 kV AC / 1,5 kV DC means it is valid for the apparatus applied and where the partitions are installed; however, the application of voltages below 1 kV AC / 1,5 kV DC as in, for example, current and voltage transformers are not excluded. This document does not apply to high voltage bushings (see EN 60137, EN 61462 and EN 62155).

  • Standard
    16 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    15 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of IEC 62271 applies to the procedures for handling of gases and gas mixtures for insulation and/or switching during installation, commissioning, repair, overhaul, normal and abnormal operations and disposal at the end-of-life of high-voltage switchgear and controlgear.
These procedures are regarded as minimum requirements to ensure the reliability of electric power equipment, the safety of personal working with these gases and gas mixtures and to minimize the impact on the environment. Additional requirements could be given or specified in the operating instruction manual of the manufacturer.
For each gas or gas mixture, which is known to be used in electric power equipment at the date of the publication of this document, a separate annex describes specifications, handling procedures, safety measures, etc. For gases or gas mixtures not covered by these annexes the electric power equipment manufacturer should provide the information needed, following the structure of these annexes. Such gases or gas mixtures should also be described in a next edition or in amendments to this edition.
NOTE 1 For the use of this document, high-voltage (HV) is defined as the rated voltage above 1 000 V. However, the term medium-voltage (MV) is commonly used for distribution systems with voltages above 1 kV and generally applied up to and including 52 kV.
NOTE 2 Throughout this standard, the term "pressure" stands for "absolute pressure".
NOTE 3 Reference is also made to (Cigré Brochure 802, 2020).
NOTE 4 For further details on gases, e.g. ecotoxicology, also refer to the chemical database ECHA (www.echa.europa.eu), which takes the actual volume band into consideration.
NOTE 5 When reference to circuit-breakers is made, only gas circuit-breakers are of interest. When vacuum circuit breakers are of interest, they are explicitly mentioned.

  • Standard
    241 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Standard
    241 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC Corrected Version

  • Corrigendum
    6 pages
    English and French language
    sale 10% off
    e-Library read for
    1 day
  • Corrigendum
    6 pages
    English and French language
    sale 10% off
    e-Library read for
    1 day

This part of IEC 62271 applies to the procedures for handling of gases and gas mixtures for insulation and/or switching during installation, commissioning, repair, overhaul, normal and abnormal operations and disposal at the end-of-life of high-voltage switchgear and controlgear. These procedures are regarded as minimum requirements to ensure the reliability of electric power equipment, the safety of personal working with these gases and gas mixtures and to minimize the impact on the environment. Additional requirements could be given or specified in the operating instruction manual of the manufacturer. For each gas or gas mixture, which is known to be used in electric power equipment at the date of the publication of this document, a separate annex describes specifications, handling procedures, safety measures, etc. For gases or gas mixtures not covered by these annexes the electric power equipment manufacturer should provide the information needed, following the structure of these annexes. Such gases or gas mixtures should also be described in a next edition or in amendments to this edition. NOTE 1 For the use of this document, high-voltage (HV) is defined as the rated voltage above 1 000 V. However, the term medium-voltage (MV) is commonly used for distribution systems with voltages above 1 kV and generally applied up to and including 52 kV. NOTE 2 Throughout this standard, the term "pressure" stands for "absolute pressure". NOTE 3 Reference is also made to (Cigré Brochure 802, 2020). NOTE 4 For further details on gases, e.g. ecotoxicology, also refer to the chemical database ECHA (www.echa.europa.eu), which takes the actual volume band into consideration. NOTE 5 When reference to circuit-breakers is made, only gas circuit-breakers are of interest. When vacuum circuit breakers are of interest, they are explicitly mentioned.

  • Standard
    241 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Standard
    241 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC Corrected Version

  • Corrigendum
    6 pages
    English and French language
    sale 10% off
    e-Library read for
    1 day
  • Corrigendum
    6 pages
    English and French language
    sale 10% off
    e-Library read for
    1 day

This part of IEC 62271 specifies requirements for gas-insulated metal-enclosed switchgear in which the insulation is obtained, at least partly, by an insulating gas or gas mixture other than air at atmospheric pressure, for alternating current of rated voltages above 52 kV, for indoor and outdoor installation, and for service frequencies up to and including 60 Hz.
For the purpose of this standard, the terms "GIS" and "switchgear" are used for "gas-insulated metal-enclosed switchgear".
The gas-insulated metal-enclosed switchgear covered by this standard consists of individual components intended to be directly connected together and able to operate only in this manner.
This standard completes and amends, if necessary, the various relevant standards applying to the individual components constituting GIS.

  • Standard
    82 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 62271-102:2018 applies to alternating current disconnectors and earthing switches, designed for indoor and outdoor installations for nominal voltages above 1 000 V and for service frequencies up to and including 60 Hz.
This second edition cancels and replaces the first edition published in 2001, Amendment 1:2011 and Amendment 2:2013. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:  
new numbering according to IEC 17/1025/RQ to harmonize with ISO/IEC Directives, Part 2, and IEEE Std. C37.100.1;
clause numbering has been aligned with IEC 62271-1:2017;
the Scope has been extended to cover all indoor and outdoor installations. Consideration of switching devices having disconnecting and/or earthing switch functionalities, apart from other functions, are also covered by this document;
ratings have been moved from Annexes B, C and E to Clause 5; the order of the subclauses now corresponds to the order of subclauses in Clause 7;
new rating values for bus-transfer current and bus-transfer voltage have been assigned;
new class of mechanical endurance for earthing switches has been added (M1);
subclause "Rated values of electrical endurance for earthing switches" is now called "Classification of earthing switches for short-circuit making capability";
new subclause with ratings for ice-coating has been added;
new subclause with classification of bus-charging switching capability has been added;
new withstand requirements for interlocking devices have been added;
the way to comply with the requirements of the isolating distance of disconnectors has been modified;
design and construction requirements for position-indicating devices have been modified, aligning the requirements for position indication and signalling;
the value of the operating force has been changed;
the test procedures and validation criteria have been revised and modified where necessary;
requirements for applied voltage during single-phase test on non-simultaneous closing earthing switches have been changed;
non-verifiable requirements have been deleted;
a new subclause has been added for testing mechanical interlocking devices;
the high- and low-temperature test is mandatory if the temperature limits for the service conditions of the apparatus (defined by the manufacturer) are above +40 °C or below −5 °C, and a more detailed testing procedure is given;
the testing procedure to verify the proper functioning of the position-indicating device allows a more practicable testing for every technology used;
a new Annex B has been added with title: "Current-switching capability required of disconnectors and earthing switches";
a new Annex C has been added with title: "Tolerances on test quantities for type tests";
a new Annex E has been added with title: "Extension of validity of type tests".

  • Standard
    444 pages
    English and French language
    sale 15% off
  • Standard
    222 pages
    English and French language
    sale 15% off

IEC 62271-209:2019 is available as IEC 62271-209:2019 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.
IEC 62271-209:2019 covers the connection assembly of fluid-filled and extruded cables to gas-insulated metal enclosed switchgear (GIS), in single- or three-phase arrangements where the cable terminations are fluid-filled or dry-type and there is a separating insulating barrier between the cable insulation and the gas insulation of the switchgear. This second edition cancels and replaces the first edition published in 2007. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
a) New numbering in accordance with ISO/IEC directives, Part 2 (2016) and to IEC 62271‑1:2017;
b) Clause 3: addition of a definition for plug-in cable termination, filling pressure and minimum function pressure for insulation;
c) Clause 7: An additional dielectric type test for plug-in cable termination was added; also a pressure type test as well as a leak rate test on the insulator of a cable termination was implemented;
d) Clause 12: New clause about safety practices;
e) Clause 13: New clause about influence of the product on the environment;
f) New informative Annex A: Mechanical forces applied on the flange of the cable connection enclosure.

  • Standard
    103 pages
    English and French language
    sale 15% off
  • Standard
    47 pages
    English and French language
    sale 15% off

This part of IEC 62271 specifies the service conditions, rated characteristics, general structural requirements and test methods of enclosed high-voltage prefabricated substations. These prefabricated substations are cable-connected to AC high-voltage networks with highest operating voltage up to and including 52 kV and power frequencies up to and including 60 Hz. They can be manually operated from inside (walk-in type) or from outside (non-walk-in type).They are designed for outdoor installation at locations with public accessibility and where protection of personnel is provided.
These prefabricated substations can be situated at ground level or partially or completely below ground level. The last are also called underground prefabricated substations.
In general, two types of prefabricated substations are considered in this standard:
- high-voltage switching prefabricated substations;
- high-voltage/low-voltage transformer prefabricated substations (step-up and step-down).
A high-voltage switching prefabricated substation comprises an enclosure containing in general the following electrical components:
- high-voltage switchgear and controlgear;
- auxiliary equipment and circuits.
A high-voltage/low-voltage transformer prefabricated substation comprises an enclosure containing in general the following electrical components:
- power transformers;
- high-voltage and low-voltage switchgear and controlgear;
- high-voltage and low-voltage interconnections;
- auxiliary equipment and circuits.
However, relevant provisions of this standard are applicable to designs where not all these electrical components exist (for example, a prefabricated substation consisting of power transformer and low-voltage switchgear and controlgear).
The listed electrical components of a high-voltage/low-voltage transformer prefabricated substation can be incorporated in the prefabricated substation either as separate components or as an assembly type CEADS according to IEC 62271-212.
This standard covers only designs using natural ventilation. However, relevant provisions of this standard are applicable to designs using other means of ventilation except the rated power of the prefabricated substation and associated class of enclosure (see 5.101), the continuous current tests (see 7.5) and all temperature rise related requirements, which would require an agreement between manufacturer and user.
NOTE IEC 61936-1 [1] provides general rules for the design and erection of high-voltage power installations. As well, it specifies additional requirements for the external connections, erection and operation at the place of installation of high-voltage prefabricated substations compliant with IEC 62271-202, which are regarded as a component of such installation. Non-prefabricated high-voltage substations, 483 are generally covered by IEC 61936-1 [1].

  • Standard
    124 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of IEC 62271 applies to rigid HV gas-insulated transmission lines (GIL) in which the insulation is obtained, at least partly, by a non-corrosive insulating gas, other than air at atmospheric pressure, for alternating current of rated voltages above 52 kV, and for service frequencies up to and including 60 Hz. It is intended that this international standard shall be used where the provisions of IEC 62271-203 do not cover the application of GIL (see Note 3).
At each end of the HV gas-insulated transmission line, a specific element may be used for the connection between the HV gas-insulated transmission line and other equipment like bushings, power transformers or reactors, cable boxes, metal-enclosed surge arresters, voltage transformers or GIS, covered by their own specification.
Unless otherwise specified, the HV gas-insulated transmission line is designed to be used under normal service conditions.
Note 1 to entry: In this international standard, the term "HV gas-insulated transmission line" is abbreviated to "GIL".
Note 2 to entry: In this international standard, the word "gas" means gas or gas mixture, as defined by the manufacturer.
Note 3 to entry: Examples of GIL applications are given:
- where all or part of the HV gas-insulated transmission line is directly buried; or
- where the HV gas-insulated transmission line is located, wholly or partly, in an area accessible to public; or
- where the HV gas-insulated transmission line is long (typically longer than to 500 m) and the typical gas compartment length exceeds the common practice of GIS technology.

  • Standard
    58 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of IEC 62271 specifies the service conditions, rated characteristics, general structural
requirements and test methods of the assemblies of the main electrical functional units of a
high-voltage transformer substation, duly interconnected, for AC voltages up to and including
52 kV on the high-voltage side and service frequency 50 Hz or 60 Hz. The CEADS is
cable-connected to the high-voltage network for indoor and outdoor applications of restricted
access.
A CEADS as defined in this document is designed and tested to be a single product with a
single serial number and one set of documentation.
The functions of a CEADS are:
– high-voltage/high-voltage or high-voltage/low-voltage transformation;
and some or all the following:
– switching and control for the operation of the high-voltage circuit(s);
– switching and control for the operation of the low-voltage circuit(s);
– protection of the power transformer functional unit.
The main functions are integrated in the following functional units:
– high-voltage functional unit;
– power transformer functional unit;
– low-voltage functional unit.
NOTE For the purpose of this document a self-protected transformer is not considered as a CEADS, but as a
functional unit, designed and type tested to its own product standard IEC 60076-13:2006.

  • Standard
    84 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Standard
    84 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of IEC 62271 specifies the service conditions, rated characteristics, general structural requirements and test methods of enclosed high-voltage prefabricated substations. These prefabricated substations are cable-connected to AC high-voltage networks with an operating voltage up to and including 52 kV and power frequencies up to and including 60 Hz. They can be manually operated from inside (walk-in type) or from outside (non-walk-in type). They are designed for outdoor installation at locations with public accessibility and where protection of personnel is provided. These prefabricated substations can be situated at ground level or partially or completely below ground level. The last are also called "underground prefabricated substations". In general, two types of prefabricated substations are considered in this document: - high-voltage switchgear prefabricated substations; - high-voltage/low-voltage transformer prefabricated substations (step-up and step-down). A high-voltage switchgear prefabricated substation comprises an enclosure containing in general the following electrical components: - high-voltage switchgear and controlgear; - auxiliary equipment and circuits. A high-voltage/low-voltage transformer prefabricated substation comprises an enclosure containing in general the following electrical components: - power transformer(s); - high-voltage and low-voltage switchgear and controlgear; - high-voltage and low-voltage interconnections; - auxiliary equipment and circuits. However, relevant provisions of this document are applicable to designs where not all these electrical components exist (for example, a prefabricated substation consisting of power transformer and low-voltage switchgear and controlgear). The listed electrical components of a high-voltage/low-voltage transformer prefabricated substation can be incorporated in the prefabricated substation either as separate components or as an assembly type CEADS according to IEC 62271-212. This document covers only designs using natural ventilation. However, relevant provisions of this document are applicable to designs using other means of ventilation except the rated power of the prefabricated substation and associated class of enclosure (see 5.101), the continuous current tests (see 7.5) and all temperature rise related requirements, which would need an agreement between manufacturer and user. NOTE 1 IEC 61936-1 [1]1 provides general rules for the design and erection of high-voltage power installations. As well, it specifies additional requirements for the external connections, erection and operation at the place of installation of high-voltage prefabricated substations compliant with IEC 62271-202, which are regarded as a component of such installation. Non-prefabricated high-voltage substations, are generally covered by IEC 61936-1 [1]. NOTE 2 High-voltage switchgear prefabricated substations can include instrument transformers, according to IEC 61869 (all parts). These substations are not high-voltage/low-voltage transformer prefabricated substations.

  • Standard
    124 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 62271-214:2019 specifies requirements for internal arc classification of metal-enclosed pole-mounted switchgear installations used for alternating current with rated voltages above 1 kV and up to and including 52 kV with service frequencies up to and including 60 Hz. This document is applicable to three-phase, two-phase and single phase equipment. Enclosures may include fixed and removable components and may be filled with fluid (liquid or gas) to provide insulation.

  • Standard
    34 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 62271-4:2022 applies to the procedures for handling of gases for insulation and/or switching during installation, commissioning, repair, overhaul, normal and abnormal operations and disposal at the end‑of‑life of electric power equipment.
These procedures are regarded as minimum requirements to ensure the reliability of electric power equipment, the safety of personnel working with these gases and to minimize the impact on the environment. Additional requirements could be given or specified in the operating instruction manual of the manufacturer.
This second edition cancels and replaces the first edition of IEC 62271-4 published in 2013. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
title has been modified;
handling procedures of alternatives to SF6, which are used for insulation and/or switching, are added;
the main clauses are independent from the type of gas;
for each gas a separate annex describes gas specific information, handling procedures, safety measure, etc.;
information about SF6 (former Annex E) and about environmental effects of SF6 and its mixtures (former Annex F) has been moved to IEC 60376;
information about by-products of SF6 and its mixtures (former Annex G), the procedure for evaluating the potential effects on health of by-products of SF6 and its mixtures (former Annex H) and the cryogenic reclaim of SF6 (former Annex I) have been moved to IEC 60480.

  • Standard
    500 pages
    English and French language
    sale 15% off

This part of IEC 62271 applies to rigid HV gas-insulated transmission lines (GIL) in which the insulation is obtained, at least partly, by a non-corrosive insulating gas, other than air at atmospheric pressure, for alternating current of rated voltages above 52 kV, and for service frequencies up to and including 60 Hz. It is intended that this international standard shall be used where the provisions of IEC 62271-203 do not cover the application of GIL (see Note 3). At each end of the HV gas-insulated transmission line, a specific element may be used for the connection between the HV gas-insulated transmission line and other equipment like bushings, power transformers or reactors, cable boxes, metal-enclosed surge arresters, voltage transformers or GIS, covered by their own specification. Unless otherwise specified, the HV gas-insulated transmission line is designed to be used under normal service conditions. Note 1 to entry: In this international standard, the term "HV gas-insulated transmission line" is abbreviated to "GIL". Note 2 to entry: In this international standard, the word "gas" means gas or gas mixture, as defined by the manufacturer. Note 3 to entry: Examples of GIL applications are given: - where all or part of the HV gas-insulated transmission line is directly buried; or - where the HV gas-insulated transmission line is located, wholly or partly, in an area accessible to public; or - where the HV gas-insulated transmission line is long (typically longer than to 500 m) and the typical gas compartment length exceeds the common practice of GIS technology.

  • Standard
    58 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of IEC 62271 specifies requirements for gas-insulated metal-enclosed switchgear in which the insulation is obtained, at least partly, by an insulating gas or gas mixture other than air at atmospheric pressure, for alternating current of rated voltages above 52 kV, for indoor and outdoor installation, and for service frequencies up to and including 60 Hz. For the purpose of this document, the terms "GIS" and "switchgear" are used for "gas-insulated metal-enclosed switchgear". The gas-insulated metal-enclosed switchgear covered by this document consists of individual components intended to be directly connected together and able to operate only in this manner. This document completes and amends, if applicable, the various relevant standards applying to the individual components constituting GIS.

  • Standard
    82 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 62271-107:2019 is available as IEC 62271-107:2019 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 62271-107:2019 applies to three-pole-operated fused circuit-switchers designed with rated voltages above 1 kV up to and including 52 kV for use on three-phase alternating current systems of either 50 Hz or 60 Hz. This third edition cancels and replaces the second edition published in 2012. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) technical changes introduced by the second edition of IEC 62271-1 are applied, where relevant; b) rated TRV is removed and TRV is now treated as a test parameter), as in IEC 62271-100; c) the term "thermal current" is no longer used; the rated continuous current is linked to the installed fuse-links, and values shall be provided by the manufacturer together with the list of the acceptable fuse-links; for tests purpose, the highest rated continuous current listed is referred, where previously the wording was "rated maximum thermal current", for consistency with IEC 62271-105; d) making and breaking test duties are independent type tests (as some may be omitted if the switching device has been validated as a load-break switch). However, TDIt0 and TDIlow are kept as a sequence as they are linked to the same rated value (It0); e) differentiation has been introduced between requirements expressed for fulfilling the function expected from a fused circuit-switcher, from requirements only relevant when the function is performed by a stand-alone device. The goal is to avoid duplication or conflicts of requirements with a standard dealing with assemblies, when the function is implemented within such an assembly.

  • Standard
    57 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 62271-212:2022 is available as IEC 62271-212:2022 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.
IEC 62271-212;2022 specifies the service conditions, rated characteristics, general structural requirements and test methods of the assemblies of the main electrical functional units of a high-voltage transformer substation, duly interconnected, for AC voltages up to and including 52 kV on the high-voltage side and service frequency 50 Hz or 60 Hz. The CEADS is cable‑connected to the high-voltage network for indoor and outdoor applications of restricted access. This second edition cancels and replaces the first edition published in 2016. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
- clause numbering aligned with IEC 62271-1:2017,
- rewording of title and scope of the document,
- implement changes on internal arc definition and testing following the evolution of prefabricated substation concept according to IEC 62271-202,
- general review of main test procedures such as temperature rise or dielectric test on interconnections, considering control equipment, communication, smart grid devices and integration of components,
- general review of installation, operation, safety and maintenance requirements.

  • Standard
    165 pages
    English and French language
    sale 15% off
  • Amendment
    6 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    4 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 62271-202:2022 specifies the service conditions, rated characteristics, general structural requirements and test methods of enclosed high-voltage prefabricated substations. These prefabricated substations are cable-connected to AC high-voltage networks with an operating voltage up to and including 52 kV and power frequencies up to and including 60 Hz. They can be manually operated from inside (walk-in type) or from outside (non-walk-in type). They are designed for outdoor installation at locations with public accessibility and where protection of personnel is provided.
This third edition cancels and replaces the second edition published in 2014. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
the whole document contents and structure are reviewed with due consideration of IEC 62271-1:2017;
modification of the title and scope to include high-voltage switchgear prefabricated substations;
inclusion of CEADS as a possible component of MV/LV prefabricated substation;
in 7.2.101, the possible influence of surrounding elements on the dielectric performance of high-voltage components as high-voltage switchgear and controlgear and high-voltage interconnections non-metal-enclosed or without earthed screen are now considered;
new informative Annex G with testing procedure to evaluate the impact of solar radiation in temperatures inside the enclosure and how to apply it;
new informative Annex H for appropriate consideration of installation conditions of electronic equipment;
the rated power of a prefabricated substation is now defined as a three-parameter rated value. See 5.101.1;
minimum dimensions for access doors to the prefabricated substation in 6.104.4 and for free height of operation aisle in 6.105.3 have been introduced;
continuous current (temperature rise) test methods have been revised/clarified where necessary;
Figure D.1, which shows the mineral-oil-immersed power transformer load factor inside the enclosure, has been corrected.
The contents of the corrigendum of August 2023 have been included in this copy.

  • Standard
    243 pages
    English and French language
    sale 15% off
  • Amendment
    6 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    4 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 62271-204:2022 is available as IEC 62271-204:2022 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 62271-204:2022 applies to rigid HV gas‑insulated transmission lines (GIL) in which the insulation is obtained, at least partly, by an insulating gas or gas mixture other than air at atmos­pheric pressure, for alternating current of rated voltages above 52 kV, and for service frequencies up to and including 60 Hz. This second edition cancels and replaces the first edition published in 2011. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
- update to be in line with IEC 62271-1:2017 and alignment of the voltage ratings and the test voltages.
- addition of new information for welds on pressurized parts and gas tightness.

  • Standard
    254 pages
    English language
    sale 15% off
  • Standard
    110 pages
    English and French language
    sale 15% off

IEC 62271-203:2022 specifies requirements for gas-insulated metal-enclosed switchgear in which the insulation is obtained, at least partly, by an insulating gas or gas mixture other than air at atmospheric pressure, for alternating current of rated voltages above 52 kV, for indoor and outdoor installation, and for service frequencies up to and including 60 Hz. This third edition cancels and replaces the second edition published in 2011. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
- the document has been aligned with IEC 62271-1:2017;
- beside SF6 also alternative gases have been implemented where needed;
- the terms and definitions have been updated and terms not used have been removed;
- Subclause 6.16 “Gas and vacuum tightness” has been updated;
- Subclause 6.16.3 “Closed pressure systems”: Two classes of gas has been introduced:
- GWP ≤ 1 000
- GWP > 1 000
and the tightness requirements for type tests for gasses with GWP > 1 000 has been reduced from 0,5 % to 0,1 % per year per gas compartment;
- Subclause 6.108 “Interfaces”: Typical maximum pressures in service for interfaces connected to GIS have been defined;
- Subclauses 7.102 through 7.108 have been restructured;
- Subclause 7.107 “Corrosion test on earthing connections” has been updated;
- Subclause 7.108 “Corrosion tests on sealing systems of enclosures and auxiliary equipment” has been updated;
- Annex F ‘Service Continuity’ has been modified and aligned with the recommendations of CIGRE WG B3.51.

  • Standard
    157 pages
    English and French language
    sale 15% off

This part of IEC 62271 is applicable to AC series capacitor by-pass switches designed for outdoor installation and for operation at frequencies of 50 Hz and 60 Hz on systems having voltages above 52 kV. It is only applicable to by-pass switches for use in three-phase systems. This document is also applicable to the operating devices of by-pass switches and to their auxiliary equipment.

  • Standard
    12 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 62271-209:2019 is available as IEC 62271-209:2019 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 62271-209:2019 covers the connection assembly of fluid-filled and extruded cables to gas-insulated metal enclosed switchgear (GIS), in single- or three-phase arrangements where the cable terminations are fluid-filled or dry-type and there is a separating insulating barrier between the cable insulation and the gas insulation of the switchgear. This second edition cancels and replaces the first edition published in 2007. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) New numbering in accordance with ISO/IEC directives, Part 2 (2016) and to IEC 62271‑1:2017; b) Clause 3: addition of a definition for plug-in cable termination, filling pressure and minimum function pressure for insulation; c) Clause 7: An additional dielectric type test for plug-in cable termination was added; also a pressure type test as well as a leak rate test on the insulator of a cable termination was implemented; d) Clause 12: New clause about safety practices; e) Clause 13: New clause about influence of the product on the environment; f) New informative Annex A: Mechanical forces applied on the flange of the cable connection enclosure.

  • Standard
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC Corrected version

  • Corrigendum
    13 pages
    French language
    sale 10% off
    e-Library read for
    1 day
  • Corrigendum
    13 pages
    French language
    sale 10% off
    e-Library read for
    1 day

IEC Corrected version

  • Corrigendum
    13 pages
    French language
    sale 10% off
    e-Library read for
    1 day
  • Corrigendum
    13 pages
    French language
    sale 10% off
    e-Library read for
    1 day

IEC corrected version

  • Corrigendum
    4 pages
    English and French language
    sale 10% off
    e-Library read for
    1 day

This part of IEC 62271 is applicable to three-phase AC circuit-breakers designed for indoor or
outdoor installation and for operation at frequencies of 50 Hz and/or 60 Hz on systems having
voltages above 1 000 V. This document includes only direct testing methods for makingbreaking
tests. For synthetic testing methods refer to IEC 62271-101.
NOTE In a direct testing method one source is used to supply the voltage and current during the making and
breaking tests.
This part of IEC 62271 is not applicable to:
– circuit-breakers with a closing mechanism for dependent manual operation;
– circuit-breakers intended for use on motive power units of electrical traction equipment;
these are covered by IEC 60077 (all parts) [1]1;
– generator circuit-breakers installed between generator and step-up transformer; these are
covered by the IEC 62271-37-013 [2];
– self-tripping circuit-breakers with tripping devices that cannot be made inoperative during
testing. Tests on automatic circuit reclosers are covered by IEC 62271-111 [3];
– tests to prove the performance under abnormal conditions that are not described in this
document are subject to agreement between manufacturer and user. Such abnormal
conditions are, for example, cases where the voltage is higher than the rated voltage of the
circuit-breaker, conditions which can occur due to sudden loss of load on long lines or
cables.

  • Standard
    158 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Standard
    299 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 62271-101:2021 mainly applies to AC circuit-breakers within the scope of IEC 62271-100. It provides the general rules for testing AC circuit-breakers, for making and breaking capacities over the range of test duties described in 7.102 to 7.111 of IEC 62271-100:2021, by synthetic methods. It has been proven that synthetic testing is an economical and technically correct way to test high-voltage AC circuit-breakers according to the requirements of IEC 62271-100 and that it is equivalent to direct testing. The methods and techniques described are those in general use. The purpose of this document is to establish criteria for synthetic testing and for the proper evaluation of results. Such criteria will establish the validity of the test method without imposing restraints on innovation of test circuitry. This third edition cancels and replaces the second edition published in 2012 and Amendment 1:2017. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the second edition: a) alignment with the third edition of IEC 62271-100:2021; b) update this document with the last methods and techniques used for synthetic tests.

  • Standard
    158 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Standard
    299 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of IEC 62271 applies to AC high-speed earthing switches (hereafter termed HSES) designed for indoor and outdoor installation and for operation at service frequencies of 50 Hz and 60 Hz on systems having voltages of 550 kV and above.
HSESs described in this document are intended to extinguish the secondary arc remaining after clearing faults on transmission lines by the circuit-breakers.
For more detailed information on HSESs, refer to Annex A.

  • Standard
    30 pages
    English language
    sale 10% off
    e-Library read for
    1 day