Pillar fire hydrants

This European Standard specifies the minimum requirements, test methods, marking and evaluation of conformity for pillar hydrants for fire fighting purposes:
   to be installed in a water distribution system;
   sizes DN 80, DN 100 and DN 150;
   suitable for an allowable operating pressure, PFA, of PN 16 with or without drain facility;
   having vertical or horizontal, flanged, socket or spigot inlet;
   with one or two outlets and having outlets to national requirements;
   globe (screw down) or gate valve type.
This European Standard also provides for the evaluation of conformity of the pillar fire hydrants to the requirements of this European Standard.
This European Standard applies to fire hydrants for potable and non potable water and for filtered water. Additional requirements may apply for other liquids.
Couplings connected to outlets are outside the scope of this European Standard and should conform to national requirements.
Couplings connected to outlets are outside the scope of this document and shall conform to national requirements.

Überflurhydranten

Dieses Dokument legt die Mindestanforderungen und Prüfverfahren, die Kennzeichnung und die Konformitätsbewertung für Überflurhydranten für Feuerlöschzwecke fest:
-   zur Installation in Wasserversorgungssystemen;
-   mit den Nennweiten DN 80, DN 100 und DN 150;
-   geeignet für einen zulässigen Betriebsdruck PFA, mit PN 16, mit oder ohne Entleerungssystem;
-   mit vertikalem oder horizontalem Einlauf mit Flansch-, Muffen- oder Spitzenanschluss ;
-   mit einem oder zwei Abgängen nach den nationalen Anforderungen;
-   mit Ventil- oder Schieberabsperrung.
Dieses Dokument liefert auch die Konformitätsbewertung für Unterflurhydranten für Feuerlöschzwecke nach den Anforderungen dieser Norm.
Dieses Dokument gilt für Hydranten für Trink- und Nichttrinkwasser sowie für gefiltertes Wasser. Zusätzliche Anforderungen können für andere Flüssigkeiten gelten.
Kupplungen an Abgängen fallen nicht in den Anwendungsbereich dieser Norm und müssen den nationalen Anforderungen entsprechen.

Poteaux d'incendie

La présente Norme européenne contient des prescriptions minimales relatives aux poteaux destinés a la lutte contre l'incendie ainsi que des informations sur les méthodes d'essai applicables, le marquage et l'évaluation de la conformité. Il s'applique aux poteaux :
-   devant etre installés sur un réseau de distribution d'eau ;
-   de dimensions DN 80, DN 100 et DN 150 ;
-   approprié a une pression de fonctionnement admissible, PFA, de PN 16, avec ou sans dispositif de vidange ;
-   munis de raccordement d'entrée verticaux ou horizontaux, a bride, a extrémité a emboîter mâle ou femelle ;
-   comportant un ou deux orifices de sortie, conforme(s) aux prescriptions nationales ;
-   munis d'appareils de robinetterie de type robinet a soupape (a tige non montante) ou robinet-vanne.
La présente norme peut également etre utilisée pour l'évaluation de la conformité des poteaux d'incendie enterrés conformes aux prescriptions contenues dans la présente norme.
La présente norme s'applique aux poteaux d'incendie alimentés en eau potable et non potable et en eau filtrée. Des prescriptions complémentaires peuvent s'appliquer dans le cas d'autres liquides.
Les manchons d'assemblage raccordés aux orifices de sortie ne relevent pas du domaine d'application du présent document et il convient qu'ils soient conformes aux reglementations nationales.

Nadzemni hidranti

General Information

Status
Published
Publication Date
30-Nov-2005
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
01-Dec-2005
Due Date
01-Dec-2005
Completion Date
01-Dec-2005

Buy Standard

Standard
EN 14384:2005
English language
27 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Pillar fire hydrantsNadzemni hidrantiPoteaux d'incendieÜberflurhydrantenTa slovenski standard je istoveten z:EN 14384:2005SIST EN 14384:2005en13.220.10ICS:SLOVENSKI
STANDARDSIST EN 14384:200501-december-2005







EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 14384July 2005ICS 13.220.10English versionPillar fire hydrantsPoteaux d'incendieÜberflurhydrantenThis European Standard was approved by CEN on 20 June 2005.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Central Secretariat or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia,Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2005 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 14384:2005: E



EN 14384:2005 (E) 2 Contents Page Foreword.3 Introduction.4 1 Scope.5 2 Normative references.5 3 Terms and definitions.6 4 Design requirements.7 4.1 Dimensions.7 4.2 Shell.8 4.3 Elastomers.8 4.4 Obturator – main valve.9 4.5 Materials including lubricants in contact with water intended for human consumption.9 4.6 Leaktightness and mechanical strength.9 4.7 Components of the operating system.10 4.8 Closing direction.10 4.9 Opening turns.10 4.10 Resistance of the hydrant to operating loads.10 4.11 Operating mechanism.11 4.12 Inlet connections.11 4.13 Outlets.11 4.14 Drainage and venting systems.11 4.15 Security housing.12 4.16 Internal and external corrosion resistance.12 4.17 Colour.12 4.18 Resistance to disinfection products.12 4.19 Hydrants for non-potable water systems.12 4.20 Hydraulic characteristics.12 5 Test methods.13 5.1 General.13 5.2 General dimensions.13 5.3 Flow characteristics.13 6 Designation, marking and additional data.15 6.1 Designation.15 6.2 Marking of hydrants.15 6.3 Additional hydrant data.16 7 Evaluation of conformity.17 7.1 General.17 7.2 Initial type testing.17 7.3 Factory product control (FPC).18 Annex ZA (informative)
Clauses of this European Standard addressing the provisions of the EU Construction Products Directive (89/106/EEC).22 ZA.1 Scope and relevant clauses.22 ZA.2 Procedure for the attestation of conformity of pillar fire hydrants.23 ZA.3 CE marking.24 ZA.4 Certificate and Declaration of Conformity.26 Bibliography.27



EN 14384:2005 (E) 3 Foreword This European Standard (EN 14384:2005) has been prepared by Technical Committee CEN/TC 192 “Fire service equipment”, the secretariat of which is held by BSI, in cooperation with CEN/TC 164 "Water supply" and CEN/TC 69 “Industrial Valves”. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by January 2006, and conflicting national standards shall be withdrawn at the latest by January 2006. This European Standard has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s). For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this European Standard. This is one of a series of standards for fire hydrants. This is the first edition of this European Standard. No International Standard exists for pillar fire hydrants. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.



EN 14384:2005 (E) 4 Introduction The purpose of a fire hydrant installation is to provide a connection (i.e. hydrant) to the water main to which the firefighter can connect firefighting equipment. Pillar fire hydrants consist of one or more valves and connection outlets in a column shape, which emerges from below ground level, intended primarily to supply water for firefighting and also may be used by water utilities (as defined in 3.3). This European Standard is in conformity with the general requirements already established by CEN/TC 164 in the field of water supply. In respect of potential adverse effects on the quality of water intended for human consumption caused by the product covered by this European Standard: 1) this European Standard provides no information as to whether the product may be used without restriction in any of the Member States of the EU or EFTA, 2) it should be noted that, while awaiting the adoption of verifiable European criteria, existing national regulations concerning the use and/or the characteristics of this product remain in force.



EN 14384:2005 (E) 5 1 Scope This European Standard specifies the minimum requirements, test methods, marking and evaluation of conformity for pillar hydrants for fire fighting purposes:  to be installed in a water distribution system;  sizes DN 80, DN 100 and DN 150;  suitable for an allowable operating pressure, PFA, of PN 16 with or without drain facility;  having vertical or horizontal, flanged, socket or spigot inlet;  with one or two outlets and having outlets to national requirements;  globe (screw down) or gate valve type. This European Standard also provides for the evaluation of conformity of the pillar fire hydrants to the requirements of this European Standard. This European Standard applies to fire hydrants for potable and non potable water and for filtered water. Additional requirements may apply for other liquids. Couplings connected to outlets are outside the scope of this European Standard and should conform to national requirements. 2 Normative references The following referenced documents are indispensable for the application of this European Standard. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 681-1, Elastomeric seals — Material requirements for pipe joint seals used in water and drainage applications — Part 1: Vulcanized rubber EN 1074-1:2000, Valves for water supply — Fitness for purpose requirements and appropriate verification tests — Part 1: General requirements EN 1074-2:2000, Valves for water supply — Fitness for purpose requirements and appropriate verification tests — Part 2: Isolating valves EN 1074-6:2004, Valves for water supply — Fitness for purpose requirements and appropriate verification tests — Part 6: Hydrants EN 1092-1, Flanges and their joints — Circular flanges for pipes, valves, fittings and accessories, PN designated — Part 1: Steel flanges EN 1092-2, Flanges and their joints — Circular flanges for pipes, valves, fittings and accessories, PN designated — Part 2: Cast iron flanges EN 1503-1, Valves — Materials for bodies, bonnets and covers — Part 1: Steels specified in European Standards EN 1503-3, Valves — Materials for bodies, bonnets and covers — Part 3: Cast irons specified in European Standards
EN ISO 9001:2000, Quality management systems — Requirements (ISO 9001:2000)



EN 14384:2005 (E) 6 3 Terms and definitions For the purposes of this European Standard, the following terms and definitions apply. 3.1 hydrant connection to a water supply system including an isolating valve [EN 1074-6:2004] 3.2 fire hydrant hydrant designed to supply water for fire fighting during all phases of the fire 3.3 pillar fire hydrant fire hydrant with column shape, which emerges from below ground level, intended primarily to supply water for firefighting and also may be use by water utilities 3.4 dry pillar fire hydrant pillar fire hydrant, the column of which empties automatically when the main valve is closed 3.5 wet pillar fire hydrant pillar fire hydrant, the column of which remains full of water 3.6 break system mechanism which allows the above ground part of the hydrant to separate from the below ground part when subjected to impact whilst maintaining the seal of the main valve 3.7 obturator movable component of the valve whose position in the fluid flow path permits, restricts or obstructs the fluid flow (see EN 736-2) 3.8 loose obturator device for controlling flow out of a pipeline but which prevents flow into a pipeline 3.9 shell pressure-containing envelope of the valve NOTE It normally comprises the body and, when included in the design, a bonnet or cover and the body bonnet or body cover joint (see EN 736-2). 3.10 DN nominal size alphanumeric designation of the size of pipework components used for reference purposes. It comprises the letters DN followed by a dimensionless round number which is loosely related to the effective dimensions, in millimetres, of the bore or external diameter of the end connections [EN 1074-1:2000] 3.11 PN nominal pressure alphanumeric designation used for reference purposes and related to a combination of numerical and dimensional characteristics of a component of a pipe system. It comprises the letters PN followed by a dimensionless round number [EN 1074-1:2000]



EN 14384:2005 (E) 7 3.12 allowable maximum operating pressure PMA maximum hydrostatic pressure including surge that a component can withstand from time to time in service [EN 1074-1:2000] 3.13 allowable operating pressure PFA maximum hydrostatic pressure that a component can withstand continuously in service [EN 1074-1:2000] 3.14 allowable test pressure PEA maximum hydrostatic pressure that a newly installed component can withstand for a relatively short duration when either fixed above ground level or laid and backfilled underground in order to ensure the integrity and tightness of the pipeline (see EN 1074-1) 3.15 flow coefficient Kv (Cv) rate of flow in cubic metres per hour that will cause a differential pressure of one bar through the fire hydrant (see EN 736-3) 4 Design requirements 4.1 Dimensions Dimensions (see Figure 1) shall be as follows:  H ≥ 300 mm. The nominal outlet angle a shall be 60° ≤ a ≤ 90°. All the outlets shall be within an included nominal angle b of 180°, and shall allow all the hose couplings to be fitted at the same time. The tolerances on the nominal angles a and b shall be ± 5°. General dimensions shall be measured according to 5.2.



EN 14384:2005 (E) 8 2HIH2abb1 Key 1 Ground
H1 Distance from outlet to ground 2 Point of connection to the water supply
H2 Distance from top of hydrant to point of a Nominal outlet angle
connection to water supply b Nominal outlets included angle Figure 1 — General dimensions 4.2 Shell The shell of the pillar fire hydrants shall be made of the materials given in Table 1. Table 1 — Shell materials Material Reference standard Flake graphite cast iron EN 1503-3 Spheroidal graphite cast iron EN 1503-3 Steel EN 1503-1
4.3 Elastomers All elastomeric seals within the hydrant shall comply with EN 681-1. They shall be either type WA for cold potable water use or suitable for the fluid with which they come into contact (see 4.6).



EN 14384:2005 (E) 9 4.4 Obturator – main valve Any design of the main valve shall be accepted provided that it meets the requirements of this European Standard. The manufacturer shall declare if the design of the hydrant permits the obturator to be replaced in situ. NOTE For safety reasons the replacement should be carried out when the fire hydrant is not under pressure. 4.5 Materials including lubricants in contact with water intended for human consumption Pending the introduction of a common European Approvals Scheme ‘E.A.S.’, all materials including lubricants in the construction of a hydrant, that are likely to come into contact with water for human consumption, shall comply with the national regulations in the country of use. 4.6 Leaktightness and mechanical strength 4.6.1 General The hydrant shall be suitable for use at the relevant pressures shown in Table 2, and shall meet the requirements of 4.6.2 to 4.6.4. Table 2 — Pressures PN PFA MPa (bar) PMA MPa (bar) PEA a (1) MPa (bar) 16 1,6 (16) 2,0 (20) 2,5 (25) a PEA only applies to valves not in the closed position.
4.6.2 Shell and all pressure containing components (including steam seals) 4.6.2.1 Leaktightness When tested in accordance with Annex A of EN 1074-1:2000, using the values of PEA from Table 2, there shall be no visible sign of leakage past the valve. NOTE This is equivalent to rate "A" as defined in EN 1074-1:2004. 4.6.2.2 Mechanical strength Having successfully passed the leak tightness test, additionally, the hydrant shall not present any sign of defect. 4.6.3 Obturator 4.6.3.1 Leaktightness When tested in accordance with Annex B of EN 1074-1:2000, using the value 1,1 × PFA from Table 2, there shall be no visible sign of leakage past the valve. NOTE This is equivalent to rate "A" as defined in EN 1074-1:2004.



EN 14384:2005 (E) 10 4.6.3.2 Mechanical strength Having successfully passed the leak tightness test, additionally, the hydrant shall not present any sign of defect. 4.6.4 Operating cycles, endurance The requirements and test method shall be in accordance with EN 1074-6:2004, 5.5.1, by using the values given in Table 3 for the MOT. 4.6.5 Endurance of the non-return device (where fitted) The requirements and test method shall be in accordance with EN 1074-6:2004, 5.5.2. 4.7 Components of the operating system In the case of a fire hydrant with a break system, the components of the operating system shall be joined at the breaking level in a manner that will separate if the column is broken by impact. The break system shall be tested in accordance with EN 1074-6:2004, 5.1.3.2. 4.8 Closing direction The hydrant shall be closed by turning the operating device in a clockwise direction when viewed from above. 4.9 Opening turns The actual total number of turns (N, with a tolerance of ± 1) to fully open the hydrant, together with at least opening direction marks shall be clearly marked on the upper part of the fire hydrant as shown in Figure 2. In the case of a wet pillar hydrant, the markings shall be close to each operating device. The manufacturer shall declare the number of turns of the operating device from commencement of flow to fully open (effective turns), the number of turns of the operating device prior to the commencement of flow (dead turns) and its addition (total turns).
Figure 2 — Example of opening marks
4.10 Resistance of the hydrant to operating loads 4.10.1 Maximum operating torque (MOT) for operating loads When tested in accordance with EN 1074-6:2004, Annex C, the torque required to seal the hydrant shall meet the appropriate value given in Table 3. Three torque ranges are specified:  Range 1 and Range 2: Handwheel diameter ≤ 500 mm or lever length ≤ 500 mm,  Range 3:
Handwheel diameter > 500 mm or lever length > 500 mm.



EN 14384:2005 (E) 11 Table 3 — Torque
Maximum operating torque (Nm) Minimum strength torque (Nm) Hydrant DN 80 100 150 80 100 150 Torque range 1 80 80 80 250 250 250 Torque range 2 125 125 125 250 250 250 Torque range 3 105 130 195 210 260 380 4.10.2 Minimum strength torque (mST) When tested in accordance with EN 1074-2:2000, Annex A, the torque required for the resistance of the hydrant shall meet the appropriate value given in Table 3. 4.11 Operating mechanism The mechanism shall be operated either by means of a key or a handwheel, of a design valid in the country of use. 4.12 Inlet connections Inlet flanges shall be suitable for connecting to flanges conforming with EN 1092-1 or EN 1092-2, depending on the shell material. Depending on the customer need, the flanges may additionally accommodate older pattern flanges in accordance with national requirements. Where the inlet is of a proprietary type the manufacturer shall declare its dimensions. NOTE A future revision of the standard will give a list of acceptable provisions, allowing each Member State to choose those provisions they wish. 4.13 Outlets The number and sizes of outlet(s) shall be as follows:  DN of the body has to be equal or bigger than the DN of the outlets;  number of outlets has to be at least two for DN 150 (not for the other DNs). The design of the outlets shall conform to national requirements valid in the country of use. 4.14 Drainage and venting systems The performance of the draining system, where fitted to the hydrant, shall comply with the requirements of EN 1074-6:2004, 5.6. In addition, the manufacturer shall declare the volume of retained water and the time for draining. If an air inlet system is provided the system shall be automatically shut when the pillar is under water pressure and shall be opened when the main valve is closed.



EN 14384:2005 (E) 12 4.15 Security housing When incorporated, the security housing shall be designed and constructed so that, when opened, it does not obstruct the fitting of the hose coupling, the operating mechanism or the drainage system. The closing device for the housing shall be in conformity with regulatory requirements applicable in the country of use. 4.16 Internal and external corrosion resistance 4.16.1 General The internal surfaces which are in continuous contact with the water, and all external surfaces of the hydrant (including bolts) which are in continuous contact with the surrounding soil, water or atmosphere, shall be resistant to corrosion and ageing by appropriate selection of materials. 4.16.2 Coatings All cast iron components shall be coated to protect against corrosion and protect the quality of water intended for human consumption within the hydrant, if applicable. 4.16.3 Other components Other component parts of the hydrant to those in 4.16.1 shall be manufactured from materials that will resist corrosion for the design life of the product under the conditions of use for which it is intended. 4.17 Colour Where national regulations on colour exist, the hydrants colour shall comply with these. Where the colour is not subject to such regulation, the colour may be agreed between the user/purchaser and the manufacturer. 4.18 Resistance to disinfection products Where applicable, the requirement and test shall be in accordance with 5.4 of EN 1074-1:2000. 4.19 Hydrants for non-potable water systems In the case where the hydrant does not transport water intended for human consumption, the manufacturer shall ensure that all materials used in the hydrant (where they come into contact with the fluid) shall not be adversely affected by that fluid. 4.20 Hydraulic characteristics When tested in accordance with 5.3, the Kv shall not be less than the appropriate value given in Table 4.



EN 14384:2005 (E) 13 Table 4 — Flow characteristics, minimum Kv factor
Size and number of outlets to be tested Hydrant DN 1 x 37,5 mm 2 x 37,5 mm 1 x 50 mm 2 x 50 mm 1 x 65 mm 2 x 65 mm 1 x 100 mm 2 x 100 mm 1 x 150 mm 2 x 150 mm 80 and 100 30 60 40 60 80 140 1601 – – – 150 – – – – 80 140 160 280 300 – 1 Does not apply for DN 80. – Combination of DN and size of the outlet not allowed.
5 Test methods 5.1 General For safety reasons, before applying any hydrostatic pressure, release all air from within the component under test. 5.2 General dimensions Measure or gauge the specified dimensions. Determine that the ground level indication is clearly marked. 5.3 Flow characteristics The flow characteristics of each of the fire hydrant outlets (with the couplings) shall be tested individually and if there are two outlets of the same DN they may be tested together. The minimum Kv values shall be according to Table 4. NOTE For example, a DN 150 hydrant having two DN 100 outlets and one DN 65 outlet can be tested with either each outlet tested separately or the DN 100 (Kv > 80) tested alone and the other two DN 65 tested together (Kv > 140). Carry out the test with the hydrant in the upright service position as follows. Connect a length of pipe with the same hydrant nominal diameter to the inlet flange. In the case of vertical connection hydrants, in order to test the sample in the service position, connect the inlet flange to a 90° pipe curve with a radius equal to 2,5 times the nominal pipe diameter. The tapping of pressure shall be at a distance from the connection flange at least 2 times the nominal diameter. Upstream from the inlet tapping point a length of pipe of at least 10 times nominal diameter shall be provided. For the single outlet test, in the outlet, a pipe with equal nominal diameter shall be connected. One tapping for pressure reading shall be installed at a distance, downstream of the outlet connection, of at least 10 times the nominal diameter. A typical test arrangement is shown in Figure 3. Where two outlets are to be tested, pipes of equal nominal diameters of the outlets shall be connected and then brought together in a “Y” formation to a single pipe of the same DN as the inlet. The pressure tapping shall be installed at 10 times the nominal diameter downstream of the joining of the two outlet pipes.



EN 14384:2005 (E) 14 14563210102ad2d Key 1 Pressure tapping2 Control valve 3 Pressure tapping 4 Control valve 5 Flow meter 6 Test sample X Gravity differential pressure D Nominal inlet pipe size d Nominal outlet pipe size Figure 3 — Typical test arrangement
Carry out the measurement with either an independent or differential gauge. In any case, the uncertainty of the differential pressure measurement shall not be higher than 2 %. Measure the flow upstream or downstream the hydrant, with an uncertainty not higher than 5 %. Carry out the measurement for three different values of flow, covering the differential pressure ranges shown in Table 5. Table 5 — Differential pressure ranges Differential pressure ranges kPa (bar) 40 to 50 (0,4 to 0,5) 70 to 80 (0,7 to 0,8) 100 to 110 (1,0 to 1,1)



EN 14384:2005 (E) 15 For each measurement, calculate Kv as follows: 2p1pQKv−=
(1) where Q is the measured flow (m3/h); p1 – p2 is the measured differential pressure (bar). The Kv for the hydrant is the mean of the three values obtained. 6 Designation, marking and additional data 6.1 Designation The relevant letter (A, B, C or D) shall designate the hydrant as shown in Table 6. Table 6 — Designation Types Without break system With break system With drainage (dry) A C Without drainage (wet) B D
6.2 Marking of hydrants All hydrants shall be durably marked on the upper part with the following:  direction of opening;  number of turns to open. In addition, all hydrants shall be securely and durably marked, with the following:  reference to this European Standard, i.e. EN 14384;  DN;  PN;  manufacturer's mark;  date of manufacture;  designation letter;  suitability for the conveyed fluid system; If potable water, reference to EN 1074-6. NOTE Where ZA.3 covers the same information as this subclause, the requirements of this subclause are met.



EN 14384:2005 (E) 16 6.3 Additional hydrant data The manufacturer's accompanying commercial documentation (e.g. a catalogue) shall give the information listed in 6.2 and provide the following additional information: Number of this European Standard, i.e. EN 14384 Dimensions:  according to 4.1, with reference to Figure 1. Shell material:  according to Table 1. Details of obturator. Approvals of materials for contact with water intended for human consumption (if relevant):  details of compliance with national regulations in the country of use. Resistance to operating loads:  range ( MOT, MST). Inlet flanges:  EN 1092-1 or EN 1092-2;  inlet is of a proprietary type. Installation and maintenance guide Outlet connectors:  details of conformity to national requirements in the country of use. Draining (if applicable):  volume of retained water;  time for draining. Hydraulic characteristics: Kv value. Internal and external corrosion resistance. Coatings (if applicable):  details of coating type colour and thickness. Resistance to corrosion of other component parts. Resistance to disinfection products (
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.