Heat exchangers - Hydronic room fan coils units - Determination of the sound power level

This European Standard applies to hydronic fan coil units (FCU) as factory-made single assemblies which provide the functions of cooling and/or heating but do not include the source of cooling or heating.
The standard covers both air free delivery and air ducted units with a maximum external static pressure due to duct resistance of 120 Pa max.
This European Standard provides methods for the determination of the acoustical performance of fan coil units, defining standard working condition and installation.
It is not the purpose of this standard to specify the tests used for production or field testing.
NOTE   For the purpose of remaining clauses, the term “unit” is used to mean “fan coil unit” as defined in 3.1 of FprEN 1397:2015.

Wärmeübertrager - Wasser-Luft-Ventilatorkonvektoren - Bestimmung des Schallleistungspegels

Diese Europäische Norm gilt für fabrikmäßig gefertigte einzelne Baueinheiten von Wasser-Luft-Ventilator-konvektoren (Ventilatorkonvektor, FCU, en: fan coil unit), die eine Kühl- und/oder Heizfunktion bieten, jedoch keine eigene Kühl- oder Heizquelle enthalten.
Die vorliegende Norm deckt sowohl Geräte mit ungehinderter Luftabgabe als auch solche mit Luftkanalanschluss ab, die aufgrund des Kanalwiderstands einen maximalen statischen Außendruck von höchstens 120 Pa aufweisen.
Diese Europäische Norm enthält Verfahren für die Bestimmung des akustischen Verhaltens von Ventilator-konvektoren und definiert Norm-Betriebsbedingungen sowie den Einbau.
Die Festlegung von Produktions- oder Einsatzprüfungen ist nicht Zweck dieser Norm.
ANMERKUNG   In den folgenden Abschnitten steht die Benennung „Gerät“ für „Ventilatorkonvektor“ entsprechend der Definition nach FprEN 1397:2015, 3.1.

Échangeurs thermiques - Ventilo-convecteurs à eau - Détermination du niveau de puissance acoustique

La présente Norme européenne s'applique aux ventilo-convecteurs à eau en tant qu'ensembles autonomes fabriqués en usine, assurant des fonctions de refroidissement et/ou de chauffage, mais n'intégrant pas la source de refroidissement ou de chauffage.
Cette norme concerne les unités à soufflage libre et les unités raccordées sur l’air conçues pour une pression statique externe due à la résistance de circuit de 120 Pa maximum.
La présente Norme européenne fournit des méthodes de détermination des performances acoustiques des ventilo-convecteurs, la définition des conditions de fonctionnement standards et d'installation.
Cette norme européenne n'a pas pour objet de spécifier les types d'essais utilisés en production ou sur site.
NOTE   Pour les besoins des articles ci-après, le terme « unité » est utilisé pour désigner un « ventilo-convecteur » tel que défini en 3.1 du FprEN 1397:2015.

Prenosniki toplote - Ventilatorski konvektorji voda/zrak - Ugotavljanje ravni zvočne moči

Ta evropski standard velja za ventilatorske konvektorje voda/zrak (FCU) kot tovarniško izdelane enojne sestave, ki zagotavljajo funkciji ohlajanja in/ali ogrevanja, vendar ne vključujejo vira ohlajanja ali ogrevanja.
Ta standard zajema enote za prosto dovajanje zraka in enote s prezračevalnimi cevmi z maksimalnim zunanjim statičnim tlakom zaradi maksimalne tlačne odpornosti 120 Pa.
Ta evropski standard opisuje metode za določanje akustičnih lastnosti konvektorjev ter določa standardne delovne pogoje in namestitev.
Cilj tega standarda ni določanje preskusov za proizvodnjo ali preskušanje na terenu.
OPOMBA: V naslednjih točkah izraz »enota« pomeni »ventilatorski konvektor«, kot je določeno v točki 3.1 standarda FprEN 1397:2015.

General Information

Status
Withdrawn
Public Enquiry End Date
29-Jun-2015
Publication Date
30-Aug-2015
Withdrawal Date
16-Aug-2022
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
04-Aug-2022
Due Date
27-Aug-2022
Completion Date
17-Aug-2022

Relations

Buy Standard

Standard
EN 16583:2015
English language
22 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.PRþLWärmeübertrager - Wasser-Luft-Ventilatorkonvektoren - Bestimmung des SchallleistungspegelsÉchangeurs thermiques - Ventilo-convecteurs à eau - Détermination du niveau de puissance acoustiqueHeat exchangers - Hydronic room fan coils units - Determination of the sound power level27.060.30Grelniki vode in prenosniki toploteBoilers and heat exchangersICS:Ta slovenski standard je istoveten z:EN 16583:2015SIST EN 16583:2015en,fr,de01-oktober-2015SIST EN 16583:2015SLOVENSKI
STANDARD



SIST EN 16583:2015



EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 16583
August 2015 ICS 27.060.30 English Version
Heat exchangers - Hydronic room fan coils units - Determination of the sound power level
Échangeurs thermiques - Ventilo-convecteurs à eau - Détermination du niveau de puissance acoustique
Wärmeübertrager - Wasser-Luft-Ventilatorkonvektoren - Bestimmung des Schallleistungspegels This European Standard was approved by CEN on 27 June 2015.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2015 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 16583:2015 ESIST EN 16583:2015



EN 16583:2015 (E) 2 Contents Page
European foreword .3 1 Scope .4 2 Normative references .4 3 Terms and definitions .5 4 Measuring instruments .5 5 Operation of the unit .6 6 Installation .7 6.1 General .7 6.2 Non ducted units.7 6.2.1 General .7 6.2.2 Floor mounted unit .7 6.2.3 Wall mounted unit .8 6.2.4 High wall mounted unit .9 6.2.5 Cassette and under ceiling mounted units . 10 6.2.6 Under floor mounted . 10 6.3 Ducted units . 10 6.3.1 General . 10 6.3.2 Discharge or inlet sides . 11 6.3.3 Sound level radiated by the casing . 17 7 Acoustic measurement . 18 7.1 Frequency range . 18 7.2 Acoustic standard. 18 7.3 Diffuse field . 18 7.4 Free field . 19 7.5 In-duct measurement . 19 8 Uncertainty . 19 9 Test report . 20 9.1 General information . 20 9.2 Additional information . 20 9.3 Test results . 20 10 Data to be recorded . 21 11 Manufacturer's data . 21 Bibliography . 22
SIST EN 16583:2015



EN 16583:2015 (E) 3 European foreword This document (EN 16583:2015) has been prepared by Technical Committee CEN/TC 113 “Heat pumps and air conditioning units”, the secretariat of which is held by AENOR. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by February 2016, and conflicting national standards shall be withdrawn at the latest by February 2016. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. According to the CEN/CENELEC Internal Regulations, the national standards organisations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. SIST EN 16583:2015



EN 16583:2015 (E) 4 1 Scope This European Standard applies to hydronic fan coil units (FCU) as factory-made single assemblies which provide the functions of cooling and/or heating but do not include the source of cooling or heating. The standard covers both air free delivery and air ducted units with a maximum external static pressure due to duct resistance of 120 Pa max. This European Standard provides methods for the determination of the acoustical performance of fan coil units, defining standard working condition and installation. It is not the purpose of this standard to specify the tests used for production or field testing. NOTE For the purpose of remaining clauses, the term “unit” is used to mean “fan coil unit” as defined in 3.1 of EN 1397:2015. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1397:2015, Heat exchangers - Hydronic room fan coil units - Test procedures for establishing the performance
EN ISO 3741, Acoustics - Determination of sound power levels and sound energy levels of noise sources using sound pressure - Precision methods for reverberation test rooms (ISO 3741) EN ISO 3743-1, Acoustics - Determination of sound power levels and sound energy levels of noise sources using sound pressure - Engineering methods for small movable sources in reverberant fields - Part 1: Comparison method for a hard-walled test room (ISO 3743-1) EN ISO 3743-2, Acoustics - Determination of sound power levels of noise sources using sound pressure - Engineering methods for small, movable sources in reverberant fields - Part 2: Methods for special reverberation test rooms (ISO 3743-2) EN ISO 3744, Acoustics - Determination of sound power levels and sound energy levels of noise sources using sound pressure - Engineering methods for an essentially free field over a reflecting plane (ISO 3744) EN ISO 3745, Acoustics - Determination of sound power levels and sound energy levels of noise sources using sound pressure - Precision methods for anechoic rooms and hemi-anechoic rooms (ISO 3745) EN ISO 9614-1, Acoustics - Determination of sound power levels of noise sources using sound intensity - Part 1: Measurement at discrete points (ISO 9614-1) EN ISO 9614-2, Acoustics - Determination of sound power levels of noise sources using sound intensity - Part 2: Measurement by scanning (ISO 9614-2) EN ISO 9614-3, Acoustics - Determination of sound power levels of noise sources using sound intensity - Part 3: Precision method for measurement by scanning (ISO 9614-3) EN ISO 80000-8:2007, Quantities and units - Part 8: Acoustics (ISO 80000-8:2007, corrected 2007-08-15) SIST EN 16583:2015



EN 16583:2015 (E) 5 3 Terms and definitions For the purposes of this document, the following terms and definitions apply. 3.1 hydronic fan-coil unit factory-made single assembly which provides one or more of the functions of forced circulation of air, heating, cooling, dehumidification and filtering of air, but which does not include the source of heating or cooling Note 1
to entry: This device includes at least a liquid-to-air heat exchanger and a fan, and may be designed for free or ducted intake air and/or for free or ducted delivery of supply air. 3.2 total electric power input total electric power absorbed by the unit, including fan(s) and auxiliary devices but excluding any electrical resistance heater 3.3 standard fan speed fan speed setting declared by the manufacturer and used for setting the air flow rate conditions of ducted units Note 1 to entry: The fan speed setting can be declared by the manufacturer as a certain wiring, a switch position or a steering voltage. 3.4 external static pressure positive pressure difference measured between the air outlet and inlet sections of the unit 3.5 acoustics for acoustic quantities, the definitions of EN ISO 80000-8:2007 apply 4 Measuring instruments The acoustic instruments shall fulfil the requirements of the acoustic standard used for the test. Other measurements can be necessary for the tests: — Electrical: voltage (V), current (A), total electric power input (W); — Pressure (Pa); — Rotation speed (min-1). Measurements for the ambient conditions: — Relative humidity (%); — Air Temperature (°C); — Atmospheric pressure (kPa). Table 1 gives the uncertainties allowed for these measurement values. SIST EN 16583:2015



EN 16583:2015 (E) 6 Table 1 — Uncertainties of measurement for indicated values Measured quantity Unit Uncertainty of measurement Air
— static pressure difference Pa ± 3 Pa (ûm ≤ 100 Pa)
±=m%=(ûm > 100 Pa) Electrical quantities
— Voltage V ± 0,5 % — Current A ± 0,5 % — Power W ± 1 % or minimum 1 W Rotation speed min-1 ± 1 % Relative humidity HR 5 % Atmospheric pressure kPa 1 % Temperature °C ± 0,5 K 5 Operation of the unit The testing conditions are given in EN 1397:2015 except the following: — The acoustic test shall be performed without connection to water supply, without water staying in the water circuit, with dry coil surface and an inlet air temperatures between 15 °C and 25 °C. — The control of the relative humidity is not required. If the unit includes flaps, they shall be adjusted in a fixed position according to the manufacturer instructions. If this information is not available, their position shall correspond to the maximum mechanical open position. NOTE 1 This maximum mechanical open position might differ from the minimum airflow resistance. For testing, the unit shall include an air filter but no any other accessory for air inlet or diffusion or others. Dampers for fresh air intake shall be closed. NOTE 2 No modification such as sealing is made on the unit before testing. For ducted units, an external static pressure difference of 50 Pa (± 1 Pa) shall be applied to the unit for the standard fan speed declared by the manufacturer. If other speeds are tested, the same network curve resistance shall be used. See Figure 1. If the resistance is obtained by using an auxiliary fan, preliminary tests shall be done to determine the external static difference for each additional speed. SIST EN 16583:2015



EN 16583:2015 (E) 7
Key 1 ductwork load curve 2 reference standard speed 3 other speeds X external static pressure difference Y flow rate Figure 1 — Setup external static pressure difference of ducted units for other speeds 6 Installation 6.1 General The typical types of units are presented in the annex of EN 1397:2015. Tests shall be made in suitable acoustic test chambers. 6.2 Non ducted units 6.2.1 General The target is the sound power level radiated by the whole unit, without distinction of inlet or discharge sides nor casing radiation. 6.2.2 Floor mounted unit The unit shall be installed on the hard floor at a minimum of 1 500 mm away from any wall out of any symmetry axis. The feet provided by the manufacturer shall be used. For aerodynamic purpose, the space between the feet shall be closed in the rear part to simulate the wall, with a rigid and reflective plate, with the same width of the unit and not exceeding its height. See Figure 2. SIST EN 16583:2015



EN 16583:2015 (E) 8 This plate shall be in chipboard or equivalent, density 600 kg/m³ to 700 kg/m³, and thickness 19 mm to 22 mm.
Key 1 fan coil unit 2 feet 3 plate to close the space between the feet on the rear side 4 front side of the fan coil unit 5 rear side of the fan coil unit Figure 2 — Floor mounted unit with a closing plate between the feet 6.2.3 Wall mounted unit For low-wall mounting units, the distance to the floor given by the manufacturer shall be respected. Without information from the manufacturer, this distance shall be 150 mm. For aerodynamic purpose, the space between the unit
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.