Clay roofing tiles for discontinuous laying - Determination of physical characteristics - Part 2: Test for frost resistance

This European Standard specifies the test method for the determination of frost resistance of clay roofing tiles and fittings. The test method is applicable in all CEN member countries in accordance with the required performance level of each member state.

Dachziegel für überdeckende Verlegung - Bestimmung der physikalischen Merkmale - Teil 2: Prüfung der Frostwiderstandsfähigkeit

Diese Europäische Norm legt das Prüfverfahren für die Bestimmung der Frostwiderstandsfähigkeit von Dachziegeln und Formziegeln fest.
Das Prüfverfahren gilt in allen CEN-Mitgliedsländern in Übereinstimmung mit dem im jeweiligen Mitgliedstaat geforderten Leistungsniveau.

Tuiles de terre cuite pour pose en discontinu - Détermination des caractéristiques physiques - Partie 2 : Essais de résistance au gel

La présente Norme européenne spécifie la méthode d'essai pour la détermination de la résistance au gel des tuiles et accessoires de terre cuite.
La méthode d'essai est applicable dans tous les états membres du CEN conformément au niveau de performances requis par chaque état membre.

Opečni strešniki - Ugotavljanje fizikalnih lastnosti - 2. del: Preskušanje odpornosti proti zamrzovanju

Ta evropski standard določa preskusne metode za ugotavljanje odpornosti proti zamrzovanju za opečne strešnike in opremo. Ta preskusna metoda se uporablja v vseh državah članicah CEN v skladu z zahtevanim nivojem zmogljivosti za vsako državo članico.

General Information

Status
Published
Publication Date
28-May-2013
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
28-May-2013
Due Date
02-Aug-2013
Completion Date
29-May-2013

Relations

Buy Standard

Standard
EN 539-2:2013
English language
18 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 539-2:2013
01-julij-2013
1DGRPHãþD
SIST EN 539-2:2006
SIST EN 539-2:2006/AC:2009
2SHþQLVWUHãQLNL8JRWDYOMDQMHIL]LNDOQLKODVWQRVWLGHO3UHVNXãDQMHRGSRUQRVWL
SURWL]DPU]RYDQMX
Clay roofing tiles for discontinuous laying - Determination of physical characteristics -
Part 2: Test for frost resistance
Dachziegel für überdeckende Verlegung - Bestimmung der physikalischen Merkmale -
Teil 2: Prüfung der Frostwiderstandsfähigkeit
Tuiles de terre cuite pour pose en discontinu - Détermination des caractéristiques
physiques - Partie 2 : Essais de résistance au gel
Ta slovenski standard je istoveten z: EN 539-2:2013
ICS:
91.060.20 Strehe Roofs
91.100.25 .HUDPLþQLJUDGEHQLL]GHONL Ceramic building products
SIST EN 539-2:2013 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 539-2:2013

---------------------- Page: 2 ----------------------

SIST EN 539-2:2013


EUROPEAN STANDARD
EN 539-2

NORME EUROPÉENNE

EUROPÄISCHE NORM
May 2013
ICS 91.100.25 Supersedes EN 539-2:2006
English Version
Clay roofing tiles for discontinuous laying - Determination of
physical characteristics - Part 2: Test for frost resistance
Tuiles de terre cuite pour pose en discontinu - Dachziegel für überdeckende Verlegung - Bestimmung der
Détermination des caractéristiques physiques - Partie 2: physikalischen Eigenschaften - Teil 2: Prüfung der
Essais de résistance au gel Frostwiderstandsfähigkeit
This European Standard was approved by CEN on 14 March 2013.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same
status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.





EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2013 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 539-2:2013: E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------

SIST EN 539-2:2013
EN 539-2:2013 (E)
Contents Page
Foreword .3
1 Scope .4
2 Normative references .4
3 Terms and definitions .4
4 Test pieces .8
5 Test method (European single test method) .8
Annex A (normative) Determination of the dry density by hydrostatic weighting . 17
Bibliography . 18

2

---------------------- Page: 4 ----------------------

SIST EN 539-2:2013
EN 539-2:2013 (E)
Foreword
This document (EN 539-2:2013) has been prepared by Technical Committee CEN/TC 128 “Roof covering
products for discontinuous laying and products for wall cladding”, the secretariat of which is held by IBN.
This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by November 2013, and conflicting national standards shall be withdrawn
at the latest by November 2013.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 539-2:2006.
In comparison to the previous edition, modifications have been made in Clause 1, subclauses 3.1, 3.5, 3.6
and 3.8, Clause 5 and Annex A. The test methods A, B, C and D are withdrawn.
This part of EN 539 is preceded by:
 EN 539-1, Clay roofing tiles for discontinuous laying — Determination of physical characteristics —
Part 1: Impermeability test
This part of EN 539 is one of a series of standards concerning clay roofing tiles, the list of which is indicated
below:
 EN 1304, Clay roofing tiles and fittings — Products definitions and specifications
 EN 538, Clay roofing tiles for discontinuous laying — Flexural strength test
 EN 1024, Clay roofing tiles for discontinuous laying — Determination of geometric characteristics
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech
Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.

3

---------------------- Page: 5 ----------------------

SIST EN 539-2:2013
EN 539-2:2013 (E)

1 Scope
This European Standard specifies the test method for the determination of frost resistance of clay roofing tiles
and fittings.
The test method is applicable in all CEN member countries in accordance with the required performance level
of each member state.
2 Normative references
Not applicable.
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1
pit
superficial fault consisting of a fraction of material detached from the body of the product on the visible surface
of the product with a mean dimension of over 7 mm
Note 1 to entry: This is often due to the expansion of a particle of, for example, chalk or pyrites.
[SOURCE: EN 1304:2013, 3.5.18.2]

Figure 1 — Example of pit

3.2
hair crack
superficial crack having a width of not more than 0,20 mm

Figure 2 — Example of hair crack
4

---------------------- Page: 6 ----------------------

SIST EN 539-2:2013
EN 539-2:2013 (E)
3.3
nascent crack
crack formation at the edge, with the crack only penetrating slightly into the interior of the ceramic body

Figure 3 — Example of nascent crack

3.4
surface crack
crack more than 0,20 mm wide and with a length of more than 30 mm, which does not pass through the
thickness of the product

Figure 4 — Example of surface crack
3.5
surface damage
loss of a part of the ceramic body material from the surface of the product with the longest dimension greater
than 15 mm together with the widest dimension perpendicular to the length greater than 5 mm
3.5.1
scaling
surface raising, nascent chipping, or crack, which initiates damage

Figure 5 — Example of scaling

5

---------------------- Page: 7 ----------------------

SIST EN 539-2:2013
EN 539-2:2013 (E)
3.5.2
chip
loss of a fraction of the body material of the product

Figure 6 — Example of chip

3.5.3
peeling
loss of a part of the superficial layer of the product

Figure 7 — Example of peeling

3.5.4
flaking
progressive loss of body material affecting parts or the whole thickness of the product

Figure 8 — Example of flaking

6

---------------------- Page: 8 ----------------------

SIST EN 539-2:2013
EN 539-2:2013 (E)
3.6
structural crack
structural fault consisting of a more or less regular crack running throughout the entire thickness of the product
and visible to the naked eye
[SOURCE: EN 1304:2013, 3.5.17.2]

Figure 9 — Example of structural crack

3.7
loss of ribs
loss of body material from the interlocking ribs sufficient to influence their function

Figure 10 — Example of loss of ribs

3.8
break
structural fault consisting of a separation of the product into two or more fragments
[SOURCE: EN 1304:2013, 3.5.17.1]

Figure 11 — Example of break

7

---------------------- Page: 9 ----------------------

SIST EN 539-2:2013
EN 539-2:2013 (E)
3.9
delamination
lamellar flaking which can lead to the delamination of the body in a succession of parallel layers

Figure 12 — Example of delamination

3.10
calibration device
roof tile or ceramic slab which may be specially made to possess the characteristics defined within 5.4.1.1 and
which will not be damaged during the calibration
4 Test pieces
If the tiles or fittings are placed on the market with a ceramic coating and/or treatment, the tests shall be
carried out on test pieces which have this same coating and/or treatment.
When the tiles or fittings are taken from a site or building, they shall be tested in the state in which they are
found, but the interpretation of the test results shall take into account the stresses to which these installed
products have been subjected.
5 Test method (European single test method)
5.1 Principle
Test pieces are progressively immersed in water for a period of seven days, then covered on their back with a
damp cloth, and then placed in a freezing chamber where they are subjected to freeze/thaw cycles.
During these cycles, the products are frozen by air and thawed by water on all of their surfaces at the same
time.
The damage that occurs during the test is recorded.
The number of cycles of each level is specified in this European Standard.
5.2 Apparatus
5.2.1 Freeze/thaw unit
The freeze/thaw unit shall consist of a freezing chamber, fan, cooling units, water level regulator, water drain
and programme control unit. The freeze/thaw unit shall be closed on all sides. An example is given in Figure 13.
The freeze/thaw unit shall be provided with a rack to hold the test pieces as specified in 5.4.2.5.
Temperature sensor(s) shall be fitted inside the freezing chamber to permit monitoring of the temperature
distribution inside the chamber. The temperature sensor(s), e.g. measurement thermocouples or resistance
8

---------------------- Page: 10 ----------------------

SIST EN 539-2:2013
EN 539-2:2013 (E)
thermometers and suitable recording instruments, shall have an error limit of ± 0,5 K. Tolerances are given by
taking into account the uncertainty of the recording instruments.
If necessary, deflectors should be fitted to maintain a uniform temperature distribution.
It shall be possible to regulate the cooling capacity of the unit (see 5.2.2) to ensure that the cooling and ice
formation rates as measured in a calibration tile are in accordance with the freeze/thaw curve given in
Figure 14.
A water feed shall be provided to ensure that both surfaces of the tile are uniformly flooded by water. The
water temperature shall be (11 ± 6) °C.
In order to achieve a steady and reproducible sequence of the freeze/thaw cycles, the freeze/thaw unit shall
be equipped with a programme control unit to allow the cooling and the thawing processes to be carried out in
the required time.

Key
1 water input
2 heat exchanger
3 roofing tile fixing
4 circulating fan
Figure 13 — Example of freeze/thaw unit
5.2.2 Regulation of the cooling capacity of the freeze/thaw unit
5.2.2.1 Methods of control
The method of regulating the cooling capacity of the freeze/thaw unit depends on whether or not the
freeze/thaw unit has a fixed cooling capacity or a variable cooling capacity. The methods to be adopted for
each of these two options are described in 5.2.2.2 and 5.2.2.3.
5.2.2.2 Freeze/thaw units with fixed cooling capacity
The cooling capacity of the unit is fixed or held constant and the mass and water content of the test pieces
that is required to meet the freeze/thaw curve is established by test. Thereaft
...