Gas safety shut-off devices for inlet pressure up to 10 MPa (100 bar)

This document specifies constructional, functional, testing and marking requirements, sizing and documentation of gas safety shut-off devices used in the pressure regulating stations in accordance with EN 12186 or EN 12279:
- for inlet pressures up to 100 bar and nominal diameters up to DN 400;
- for an operating temperature range from –20 °C to +60 °C,
which operate with fuel gases of the 1st and 2nd family in accordance with EN 437 in transmission and distribution networks and also in commercial and industrial installations.

Gas-Sicherheitsabsperreinrichtungen für Eingangsdrücke bis 10 MPa (100 bar)

Dieses Dokument legt Anforderungen an Konstruktion, Funktion, Prüfung, Kennzeichnung und Bemessung sowie die Dokumentation von Gas Sicherheitsabsperreinrichtungen fest:
-   für Eingangsdrücke bis 100 bar und Nennweiten bis DN 400;
-   für einen Betriebstemperaturbereich von -20 °C bis +60 °C;
soweit sie mit Brenngasen der 1. und 2. Gas Familie nach EN 437 in den Druckregelanlagen nach EN 12186 oder EN 12279 in Gastransport  und Gasverteilnetzen sowie in gewerblichen und industriellen Anlagen betrieben werden.
Der Begriff Gas Sicherheitsabsperreinrichtung wird im Weiteren, außer in Überschriften, mit SAE abgekürzt.
Für Standard Sicherheitsabsperreinrichtungen, die in den Druckregelanlagen nach EN 12186 oder EN 12279 verwendet werden, schließt Anhang ZA alle maßgebenden grundlegenden Sicherheitsanforderungen der Richtlinie 2014/68/EU (PED) ein.
Dieses Dokument behandelt folgende Temperaturklassen/Ausführungen von SAE:
-   Temperaturklasse 1: Betriebstemperaturbereich von -10 °C bis 60 °C;
-   Temperaturklasse 2: Betriebstemperaturbereich von -20 °C bis 60 °C;
-   Funktionsklasse A: SAE, die bei Beschädigung des Istwertaufnehmers oder Ausfall der externen Hilfsenergie schließen und bei denen die erneute Öffnung nur manuell möglich ist;
-   Funktionsklasse B: SAE, die bei Beschädigung des Istwertaufnehmers nicht schließen, aber geeigneten und zuverlässigen Schutz bieten, und bei denen die erneute Öffnung nur manuell möglich ist.
-   Ausführung IS (einheitlicher Festigkeitsbereich);
-   Ausführung DS (verschiedene Festigkeitsbereiche).
SAE, die den Anforderungen dieses Dokuments entsprechen, dürfen als übereinstimmend mit EN 14382 deklariert und mit der Kennzeichnung EN 14382 versehen werden.
Die Anforderungen dieses Dokuments an Werkstoffe und Funktionsverhalten können auf SAE angewendet werden, die thermische Energie oder die Wirkung elektrischer Energie für das Auslösen des Stellglieds verwenden. Die Betriebsparameter derartiger SAE sind in diesem Dokument nicht festgelegt.
Das SAE darf mit einem Abblasebegrenzer entsprechend den Anforderungen in Anhang J ausgerüstet sein.
Für einige Absätze und Unterabschnitte dieser Norm wird vollständig auf prEN 334:2016 verwiesen.
Dieses Dokument gilt nicht für:
-   SAE vor/an/in Haushalts Gasgeräten, die hinter Hausgaszählern installiert sind;
-   SAE, die für den Einbau in Druckregelgeräten in Anschlussleitungen ) mit einem Volumenstrom unter Normbedingungen Die dauerhafte Unversehrtheit von Sicherheitsabsperreinrichtungen wird durch wiederkehrende Funktions¬prüfungen sichergestellt. Für wiederkehrende Funktionsprüfungen wird im Allgemeinen auf nationale Vorschriften/Normen, sofern vorhanden, oder auf Verfahren des Anwenders/Herstellers verwiesen.
Dieses Dokument behandelt die Reaktion von SAE der Funktionsklasse A auf die festgelegten, vernünftiger-weise zu erwartenden Ausfälle in Zusammenhang mit Fail Close Verhalten, allerdings sollte beachtet werden, dass es andere Ausfallarten gibt, deren Folgen nicht zu denselben Reaktionen führen können (diese Risiken werden mittels Redundanz nach EN 12186 abgedeckt), und dass Restgefährdungen durch geeignete Überwachung während der Anwendung/Wartung gemindert werden sollten.
Dieses Dokument behandelt sowohl Sicherheitsabsperreinrichtungen, die als eigenständige Sicherheits-einrichtung nach der Druckgeräterichtlinie (2014/68/EU) klassifiziert werden können, als auch Sicherheitsabsperreinrichtungen, die für die erforderlichen Drucksicherung mittels Redundanz (z. B. in ein Regelgerät eingebaute Absperreinrichtung, Absperreinrichtung mit einer zweiten Absperreinrichtung) verwendet werden können. Umweltbezogene Betrachtungen wurden hinzugefügt.
Die Festlegungen in diesem Dokument entsprechen dem Stand der Technik zum Erarbeitungszeitpunkt.

Clapets de sécurité pour pressions amont jusqu'à 10 MPa (100 bar)

Le présent document (prEN 14382:2016) a été élaboré par le Comité technique CEN/TC 235 « Régulateurs de pression de gaz et dispositifs de sécurité associés pour le transport et la distribution de gaz », dont le secrétariat est tenu par UNI.
Ce document est actuellement soumis à l'Enquête CEN.
Le présent document est destiné à remplacer l’EN 14382:2005+A1:2009.
Le présent document a été élaboré dans le cadre d'un mandat donné au CEN par la Commission Européenne et l'Association Européenne de Libre-Échange et vient à l'appui des exigences essentielles de la (de) Directive(s) UE.
Pour la relation avec la (les) Directive(s) UE, voir l'Annexe ZA informative, qui fait partie intégrante du présent document.
Les principales modifications par rapport à l'EN 14382:2005+A1:2009, concernent :
-   la mise à jour des références normatives ;
-   l'ajout de termes et définitions ;
-   la classification de deux CS en série en tant qu'accessoire de sécurité conformément à la DESP ;
-   une référence complète à l'prEN 334:2016 pour les embouts de raccordement, les caractéristiques nominales des brides, les diamètres nominaux et les dimensions entre-brides, les matériaux (métalliques et non métalliques), la vérification de la résistance des parties sous pression ;
-   l'essai de résistance réalisé sur une base statistique selon les dispositions de la DESP ;
-   les caractéristiques antistatiques ;
-   le limiteur d'évent en tant qu'accessoire éventuel à monter dans les CS ;
-   l'intégration d'exigences relatives à l'environnement ;
-   l'alignement des références normatives (Article 2), de l'Annexe G, de l'Annexe ZA et de ses articles pertinents par rapport aux règles du CEN.
La norme a fait l'objet d'une révision éditoriale.
Le présent document peut servir de ligne directrice pour les clapets de sécurité se situant en dehors des plages spécifiées dans la présente norme.
La présente édition a introduit l'application d'essais de résistance réalisés sur une base statistique pour les accessoires sous pression et les accessoires de sécurité fabriqués en série, sur la base de la Directive UE 2014/68/UE Annexe I article 3.2.2 et des Orientations 8/14. Les clapets de sécurité faisant l’objet du présent document sont des clapets de sécurité standard et, lorsqu’ils sont utilisés dans des postes de détente-régulation conformes à l’EN 12186 ou à l’EN 12279, ils sont considérés comme des équipements sous pression standard conformément au paragraphe 2 a) de l’Art. 1 de la Directive Équipements sous pression 2014/68/UE (DESP).
Pour les clapets de sécurité standard utilisés dans des postes de détente-régulation conformes à l'EN 12186 ou à l'EN 12279, le Tableau ZA.1 donné à l'Annexe ZA contient toutes les exigences essentielles applicables données à l'Annexe I de la DESP, sauf la résistance à la corrosion externe pour des applications dans des environnements corrosifs.

Plinske varnostne zaporne naprave za vstopne tlake do 10 MPa (100 bar)

Ta dokument določa konstrukcijske, funkcionalne in preskusne zahteve ter zahteve za označevanje, določanje velikosti in dokumentacijo plinskih varnostnih zapornih naprav, ki se uporabljajo v plinskih postajah za regulacijo tlaka v skladu s standardom EN 12186 ali EN 12279: – za vstopne tlake do 100 barov in nazivne premere do DN 400; – za delovno temperaturno območje od –20 °C do +60 °C, ki delujejo z gorivnimi plini 1. in 2. družine v skladu s standardom EN 437 v prenosnih in distribucijskih omrežjih ter tudi v komercialnih in industrijskih napravah.

General Information

Status
Published
Public Enquiry End Date
01-Jun-2016
Publication Date
24-Sep-2019
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
13-Sep-2019
Due Date
18-Nov-2019
Completion Date
25-Sep-2019

Relations

Buy Standard

Standard
EN 14382:2019
English language
78 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Draft
prEN 14382:2016
English language
78 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 14382:2019
01-november-2019
Nadomešča:
SIST EN 14382:2005+A1:2009
SIST EN 14382:2005+A1:2009/AC:2009
Plinske varnostne zaporne naprave za vstopne tlake do 10 MPa (100 bar)
Gas safety shut-off devices for inlet pressure up to 10 MPa (100 bar)
Gas-Sicherheitsabsperreinrichtungen für Eingangsdrücke bis 10 MPa (100 bar)
Clapets de sécurité pour pressions amont jusqu'à 10 MPa (100 bar)
Ta slovenski standard je istoveten z: EN 14382:2019
ICS:
23.060.40 Tlačni regulatorji Pressure regulators
SIST EN 14382:2019 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
SIST EN 14382:2019

---------------------- Page: 2 ----------------------
SIST EN 14382:2019


EN 14382
EUROPEAN STANDARD

NORME EUROPÉENNE

August 2019
EUROPÄISCHE NORM
ICS 23.060.40 Supersedes EN 14382:2005+A1:2009
English Version

Gas safety shut-off devices for inlet pressure up to 10 MPa
(100 bar)
Clapets de sécurité pour pressions amont jusqu'à 10 Gas-Sicherheitsabsperreinrichtungen für
MPa (100 bar) Eingangsdrücke bis 10 MPa (100 bar)
This European Standard was approved by CEN on 23 April 2019.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.





EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2019 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 14382:2019 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
SIST EN 14382:2019
EN 14382:2019 (E)
Contents Page


European foreword . 5
1 Scope . 7
2 Normative references . 8
3 Terms and definitions . 9
3.1 General terms and definition of type of gas safety shut-off devices . 9
3.2 Terms and definition of components of safety devices . 10
3.3 Terms, symbols and definitions related to the functional performance . 16
3.4 Possible values of all variables. 17
3.5 Terms, symbols and definitions related to the set value of the trip pressure . 17
3.6 Terms, symbols and definitions related to the flow . 18
3.7 Terms, symbols and definitions related to accuracy and some other performances . 18
3.8 Terms, symbols and definitions related to the design and tests . 19
3.9 Summary of symbols, terms, subclauses and units. 21
4 Construction requirements . 22
4.1 Basic requirements . 22
4.2 Materials . 25
4.3 Strength of housings and other parts. 26
4.4 Strength of elastomeric diaphragms . 29
5 Functional and characteristic requirements . 30
5.1 General . 30
5.2 Accuracy group . 31
5.3 Response time . 32
5.4 Relatching difference and unlatching . 32
5.5 Closing force . 32
5.6 Endurance and accelerated ageing . 33
5.7 Strength of the trip mechanism, valve seat and closing member against the dynamic
impact of flowing gas . 33
5.8 Antistatic characteristics . 33
5.9 Flow coefficient . 33
5.10 Final visual inspection . 33
6 Testing . 34
6.1 General . 34
6.2 Tests . 34
6.3 Type test . 35
6.4 Selection of test samples . 35
6.5 Routine tests . 36
6.6 Production surveillance . 36
7 Test and verification methods . 36
7.1 Dimensional check and visual inspection . 36
7.2 Materials check . 36
7.3 Verification of the strength of parts under pressure . 36
2

---------------------- Page: 4 ----------------------
SIST EN 14382:2019
EN 14382:2019 (E)
7.4 Verification of the strength of parts transmitting actuating forces . 36
7.5 Shell and inner metallic partition walls strength test . 37
7.6 Alternative shell and inner metallic partition walls strength test . 37
7.7 External tightness test . 37
7.8 Internal sealing test . 38
7.9 Test method and acceptance criteria to verify the antistatic characteristics . 38
7.10 Accuracy group . 38
7.11 Response time . 43
7.12 Relatching difference and unlatching . 44
7.13 Verification of closing force . 45
7.14 Endurance and accelerated ageing . 45
7.15 Resistance to gas of non-metallic parts . 45
7.16 Verification of the strength of the trip mechanism, valve seat and closing member
against dynamic impact of flowing gas . 45
7.17 Final visual inspection . 46
8 Field surveillance . 46
9 Documentation . 47
9.1 Documentation related to type test . 47
9.2 Documentation related to the routine tests . 47
9.3 Documentation related to production surveillance in accordance with 6.6 . 47
9.4 Operating instructions . 48
9.5 Information on sizing . 48
10 Marking . 49
10.1 General requirements . 49
10.2 Basic requirements . 49
10.3 Other additional requirements . 49
10.4 Markings for the various connections. 50
10.5 Identification of auxiliary devices . 50
11 Packaging and transportation of finished product . 50
Annex A (informative) Ice formation . 51
A.1 General . 51
A.2 Requirements . 51
A.3 Tests . 51
)
Annex B (informative) Compliance evaluation . 52
B.1 General . 52
B.2 Introduction. 52
B.3 Procedure . 52
B.4 Manufacturer’s compliance evaluation . 53
B.5 Issue of the certificate of compliance . 53
Annex C (informative) Pressure drop and flow coefficient . 54
C.1 Calculation method for pressure drop throughout the SSD . 54
C.2 Test method for the determination of the flow coefficients . 55
Annex D (normative) Alternative test method for verification of the strength of the trip
mechanism, valve seat and closing member . 56
3

---------------------- Page: 5 ----------------------
SIST EN 14382:2019
EN 14382:2019 (E)
D.1 Test method . 56
D.2 Test method for the determination of the dynamic factor C . 56
r
D.3 Test method for a series of SSDs . 57
Annex E (informative) Sizing equation . 59
Annex F (informative) Inspection certificate . 60
Annex G (informative) Order specification . 62
G.1 General . 62
G.2 Minimum specifications . 62
G.3 Optional specifications . 63
Annex H (informative) Acceptance test . 64
Annex I (informative) Suitability of safety shut-off device for damp operating conditions -
Test procedure, requirement and acceptance criteria. 65
Annex J (normative) Vent limiter . 66
J.1 General . 66
J.2 Scope . 66
J.3 Terms, symbols and definitions . 66
J.4 Requirements . 67
J.5 Testing and acceptance criteria . 68
J.6 Documentation . 69
J.7 Specific marking on vent limiter . 69
Annex K (informative) Glossary . 70
Annex L (informative) Environmental Provisions . 73
Annex ZA (informative) Relationship between this European Standard and the Essential
Requirements of Directive 2014/68/EU aimed to be covered . 76
Bibliography . 78


4

---------------------- Page: 6 ----------------------
SIST EN 14382:2019
EN 14382:2019 (E)
European foreword
This document (EN 14382:2019) has been prepared by Technical Committee CEN/TC 235 “Gas
pressure regulators and associated safety devices for use in gas transmission and distribution”, the
secretariat of which is held by UNI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by February 2020, and conflicting national standards
shall be withdrawn at the latest by February 2020.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 14382:2005+A1:2009.
In comparison with the previous edition, the following technical modifications have been made:
— normative references have been updated;
— terms and definitions have been added;
— classification of two in series SSDs as safety accessory to PED;
— full reference to EN 334:2019 for end connections, flange rating, nominal and face to face
dimensions, materials (metallic and non-metallic), verification of strength of pressure bearing
parts;
— statistical strength test on the basis of PED provisions;
— antistatic characteristics;
— vent limiter as possible fixture to be assembled in the SSDs;
— integration of environmental requirements;
— alignment of normative references (Clause 2), Annex G, Annex ZA and its relevant clauses to CEN
rules.
The standard has been editorially revised.
This document can be used as a guideline for gas safety shut off devices outside the ranges specified in
this standard.
This edition has introduced the application of statistical strength testing for series produced pressure
and safety accessories on the basis of EU Directive 2014/68/EU Annex I article 3.2.2 and Guideline H-
14. Safety shut-off devices dealt with in this document are standard safety shut-off devices and, when
used in pressure regulating stations complying with EN 12186 or EN 12279, they are considered as
standard pressure equipment in accordance with Clause 2 a) of Art. 1 of Pressure Equipment Directive
2014/68/EU (PED).
5

---------------------- Page: 7 ----------------------
SIST EN 14382:2019
EN 14382:2019 (E)
For standard safety shut-off devices used in pressure regulating stations complying with EN 12186 or
EN 12279, Table ZA.1 given in Annex ZA includes all applicable Essential Requirements given in Annex I
of PED except external corrosion resistance for applications in corrosive environments.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive(s).
For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this
document.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland,
Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Republic of North Macedonia, Norway,
Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the
United Kingdom.
6

---------------------- Page: 8 ----------------------
SIST EN 14382:2019
EN 14382:2019 (E)
1 Scope
This document specifies constructional, functional, testing marking and sizing requirements and
documentation of gas safety shut-off devices:
— for inlet pressures up to 100 bar and nominal diameters up to DN 400;
— for an operating temperature range from –20 °C to +60 °C;
which operate with fuel gases of the 1st and 2nd family as defined in EN 437, used in the pressure
regulating stations in accordance with EN 12186 or EN 12279, in transmission and distribution
networks and also in commercial and industrial installations.
“Gas safety shut-off devices” will hereafter be called “SSDs” except in titles.
For standard safety shut-off devices when used in pressure regulating stations complying with
EN 12186 or EN 12279, Annex ZA lists all applicable Essential Safety Requirements of Directive
2014/68/EU (PED).
This document considers the following temperature classes/types of SSDs:
— temperature class 1: operating temperature range from –10 °C to 60 °C;
— temperature class 2: operating temperature range from –20 °C to 60 °C;
— functional class A: SSDs that close when damage to the pressure detecting element occurs or when
external power fails and whose re-opening, is possible only manually;
— functional class B: SSDs that do not close when damage to the pressure detecting element occurs
but provide suitable and reliable protection and whose re-opening, is possible only manually;
— type IS: (integral strength type);
— type DS: (differential strength type).
SSDs complying with the requirements of this document may be declared as “in conformity with
EN 14382“ and bear the mark “EN 14382”.
The material and functional requirements specified in this document may be applied to SSDs which use
thermal energy or the effects of electrical energy to trip the operation of the closing member. For these
SSDs the operational parameters are not specified in this document.
The SSD may incorporate a vent limiter, complying with the requirements in Annex J.
This standard for some paragraphs and sub clauses makes full reference to EN 334:2019.
This document does not apply to:
— SSDs upstream from/on/in domestic gas-consuming appliances which are installed downstream of
domestic gas meters;
1
— SSDs designed to be incorporated into pressure-regulating devices used in service lines with
3
volumetric flow rate ≤ 200 m /h at normal conditions and inlet pressure ≤ 5 bar.

1
The service lines are those defined in EN 12279
7

---------------------- Page: 9 ----------------------
SIST EN 14382:2019
EN 14382:2019 (E)
Continued integrity of safety shut-off devices is ensured by periodic functional checks. For periodic
functional checks it is common to refer to national regulations/standards where existing or
users/manufacturers practices.
This document considers the reaction of the SSDs functional class A to the specified reasonable
expected failures in terms of “fail close” behaviour, but it should be consider that there are other types
of failures whose consequences cannot bring to the same reactions (these risks are covered via
redundancy as per EN 12186) and that residual hazards should be reduced by a suitable surveillance in
use / maintenance.
In this document, both safety shut-off devices that can be classified as “safety accessories” by
themselves according the Pressure Equipment Directive (2014/68/EU) as well as safety shut-off
devices that can be used to provide the necessary pressure protection through redundancy (e.g. shutoff
device integrated in a pressure regulator, shut-off device with a second shut-off device) are considered.
Addition of environmental considerations;
The provisions in this document are in line with the state of art at the moment of writing.
This document does not intend to limit the improvement of actual provisions (materials, requirements,
test methods, acceptance criteria, etc.) or the developing of new provisions for SSDs where they are
suitable to ensure an equivalent level of reliability.
Some clauses of this standard should be re-considered at the time when characteristics for non-
conventional gases will be available.
Gas safety shut-off devices according to this European standard do not have their own source of ignition
and therefore are not within the scope of European Directive 2014/34/EU. Any additional component
(e.g. proximity switch, travel transducer etc.) should be independently considered in the framework of
assemblies per ATEX Guideline to the application of Directive 2014/34/EU of the European Parliament
and of the Council of 26nd February 2014, edition December 2017, §§42 and 43.
The document includes also environmental considerations.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 334:2019, Gas pressure regulators for inlet pressures up to 100 bar
EN 1092-1:2007+A1:2013, Flanges and their joints - Circular flanges for pipes, valves, fittings and
accessories, PN designated - Part 1: Steel flanges
EN 1092-2:1997, Flanges and their joints - Circular flanges for pipes, valves, fittings and accessories, PN
designated - Part 2: Cast iron flanges
EN 1092-3:2003, Flanges and their joints - Circular flanges for pipes, valves, fittings and accessories, PN
designated - Part 3: Copper alloy flanges
EN 1092-4:2002, Flanges and their joints - Circular flanges for pipes, valves, fittings and accessories, PN
designated - Part 4: Aluminium alloy flanges
EN 1349:2009, Industrial process control valves
EN 1759-1:2004, Flanges and their joint - Circular flanges for pipes, valves, fittings and accessories, Class
designated - Part 1: Steel flanges, NPS 1/2 to 24
8

---------------------- Page: 10 ----------------------
SIST EN 14382:2019
EN 14382:2019 (E)
EN 1759-3:2003, Flanges and their joints - Circular flanges for pipes, valves, fittings and accessories, Class
designated - Part 3: Copper alloy flanges
EN 1759-4:2003, Flanges and their joint - Circular flanges for pipes, valves, fittings and accessories, class
designated - Part 4: Aluminium alloy flanges
EN 10204:2004, Metallic products - Types of inspection documents
EN 12186:2014, Gas infrastructure - Gas pressure regulating stations for transmission and distribution -
Functional requirements
EN 12279:2000, Gas supply systems - Gas pressure regulating installations on service lines - Functional
requirements
EN 13906-1:2013, Cylindrical helical springs made from round wire and bar - Calculation and design -
Part 1 : Compression springs
EN 13906-2:2013, Cylindrical helical springs made from round wire and bar - Calculation and design -
Part 2: Extension springs
EN 13906-3:2014, Cylindrical helical springs made from round wire and bar - Calculation an
...

SLOVENSKI STANDARD
oSIST prEN 14382:2016
01-marec-2016
Plinske varnostne zaporne naprave za vstopne tlake do 100 bar
Gas safety shut-off devices for inlet pressure up to 100 bar
Ta slovenski standard je istoveten z: prEN 14382
ICS:
23.060.40 7ODþQLUHJXODWRUML Pressure regulators
oSIST prEN 14382:2016 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 14382:2016

---------------------- Page: 2 ----------------------
oSIST prEN 14382:2016


DRAFT
EUROPEAN STANDARD
prEN 14382
NORME EUROPÉENNE

EUROPÄISCHE NORM

April 2016
ICS 23.060.40 Will supersede EN 14382:2005+A1:2009
English Version

Gas safety shut-off devices for inlet pressure up to 100 bar

This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 235.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.


EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2016 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 14382:2016 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
oSIST prEN 14382:2016
prEN 14382:2016 (E)
Contents Page
European foreword . 6
1 Scope . 7
2 Normative references . 8
3 Terms, definitions and symbols . 9
3.1 General terms and definition of type of gas safety shut-off devices . 9
3.2 Terms and definition of components of safety devices . 10
3.3 Terms, symbols and definitions related to the functional performance . 16
3.3.1 Terms related to types of pressure . 16
3.3.2 Other terms related to pressure . 16
3.3.3 Possible values of all variables. 17
3.3.4 Terms, symbols and definitions related to the set value of the trip pressure . 17
3.3.5 Terms, symbols and definitions related to the flow . 18
3.3.6 Terms, symbols and definitions related to accuracy and some other performances . 18
3.4 Terms, symbols and definitions related to the design and tests . 19
3.5 Summary of symbols, terms, sub-clauses and units . 21
4 Construction requirements . 22
4.1 Basic requirements . 22
4.1.1 General . 22
4.1.2 Types of gas shut-off devices . 23
4.1.3 End connections . 24
4.1.4 Flange ratings . 24
4.1.5 Nominal sizes and face-to-face dimensions . 24
4.1.6 Sealing of the adjusting device . 24
4.1.7 Set range . 24
4.1.8 External visual Indication of the position of the closing member . 24
4.1.9 Springs . 24
4.1.10 Parts transmitting actuating forces . 24
4.1.11 Replaceable parts that can be affected by erosion or abrasion . 24
4.2 Materials . 25
4.2.1 Requirements for metallic materials . 25
4.2.2 Requirements for elastomeric materials (vulcanized rubber materials) . 25
4.2.3 Requirements for non-metallic materials different from those in 4.2.2 . 25
4.3 Strength of housings and other parts. 26
4.3.1 Body and its inner metallic partition walls . 26
4.3.2 Flanges . 26
4.3.3 Other pressure bearing parts . 26
4.3.4 Integral strength gas safety shut-off devices. 27
4.3.5 Differential strength gas safety shut-off devices . 27
4.3.6 Inner metallic partition walls . 27
4.3.7 Minimum values of safety factor for pressure bearing parts . 28
4.3.8 Welded joint coefficient . 28
4.4 Strength of elastomeric diaphragms . 28
4.4.1 Diaphragms of gas safety shut off devices class A . 28
4.4.2 Diaphragms of gas safety shut off devices class B . 28
5 Functional and characteristic requirements . 29
2

---------------------- Page: 4 ----------------------
oSIST prEN 14382:2016
prEN 14382:2016 (E)
5.1 General . 29
5.1.1 Shutting-off and opening . 29
5.1.2 Mounting position . 29
5.1.3 Bypass . 29
5.1.4 Ice formation . 29
5.1.5 Failure modes . 29
5.1.6 Pressure drop. 30
5.1.7 Shell strength . 30
5.1.8 External tightness . 30
5.1.9 Internal sealing . 30
5.2 Accuracy group . 31
5.3 Response time . 31
5.4 Relatching difference and unlatching . 31
5.4.1 Relatching difference . 31
5.4.2 Unlatching under mechanical impact. 31
5.5 Closing force . 31
5.6 Endurance and accelerated ageing . 32
5.7 Strength of the trip mechanism, valve seat and closing member against the dynamic
impact of flowing gas . 32
5.8 Antistatic characteristics . 32
5.9 Flow coefficient . 32
5.10 Final visual inspection . 33
5.10.1 Requirements for final visual inspection after type tests . 33
5.10.2 Requirements for final visual inspection after routine tests and production
surveillance . 33
6 Testing . 33
6.1 General . 33
6.2 Tests . 33
6.3 Type test . 35
6.4 Selection of test samples . 35
6.5 Routine tests . 35
6.6 Production surveillance . 35
7 Test and verification methods . 35
7.1 Dimensional check and visual inspection . 35
7.2 Materials check . 36
7.3 Verification of the strength of parts under pressure . 36
7.3.1 Metallic pressure bearing parts and inner metallic partition walls . 36
7.3.2 Elastomeric pressure containing parts. 36
7.4 Verification of the strength of parts transmitting actuating forces . 36
7.5 Shell and inner metallic partition walls strength test . 36
7.6 Alternative shell and inner metallic partition walls strength test . 36
7.7 External tightness test . 36
7.7.1 External tightness test of metallic housing . 36
7.7.2 External tightness test of chambers bounded on at least one side by a diaphragm. 37
7.8 Internal sealing test . 37
7.9 Test method and acceptance criteria to verify the antistatic characteristics . 38
7.10 Accuracy group . 38
7.10.1 General conditions . 38
7.10.2 Accuracy Group test at ambient temperature . 38
7.10.3 Accuracy Group test at the limit temperatures –20 °C or –10 °C and 60 °C . 39
7.10.4 Verification of the upper limit of the highest set range for overpressure monitoring . 39
7.10.5 Determination of flow coefficient . 40
3

---------------------- Page: 5 ----------------------
oSIST prEN 14382:2016
prEN 14382:2016 (E)
7.11 Response time . 41
7.12 Relatching difference and unlatching . 42
7.12.1 Trip pressure for over-pressure monitoring . 42
7.12.2 Lower trip pressure. 42
7.13 Verification of closing force . 43
7.14 Endurance and accelerated ageing . 44
7.15 Resistance to gas of non-metallic parts . 44
7.16 Verification of the strength of the trip mechanism, valve seat and closing member
against dynamic impact of flowing gas . 44
7.17 Final visual inspection . 45
7.17.1 Final visual inspection after type test . 45
7.17.2 Final visual inspection after routine tests and production surveillance . 45
8 Field surveillance . 45
9 Documentation . 45
9.1 Documentation related to type test . 45
9.1.1 Documentation required prior to type test . 45
9.1.2 Test report . 46
9.2 Documentation related to the routine tests . 46
9.3 Documentation related to production surveillance in accordance with 6.6 . 46
9.3.1 Documentation to be available for production surveillance . 46
9.3.2 Production surveillance report . 46
9.4 Operating instructions . 46
9.5 Information on sizing . 47
10 Marking . 47
10.1 General requirements . 47
10.2 Basic requirements . 48
10.3 Other additional requirements . 48
10.4 Markings for the various connections . 48
10.5 Identification of auxiliary devices. 49
11 Packaging and transportation of finished product . 49
Annex A (informative) Ice formation . 50
A.1 General . 50
A.2 Requirements . 50
A.3 Tests . 50
Annex B (informative) Compliance evaluation . 51
B.1 General . 51
B.2 Introduction . 51
B.3 Procedure. 51
B.4 Manufacturer’s compliance evaluation . 52
B.5 Issue of the certificate of compliance . 52
Annex C (informative) Pressure drop and flow coefficient . 53
C.1 Calculation method for pressure drop throughout the SSD . 53
C.2 Test method for the determination of the flow coefficients . 54
Annex D (normative) Alternative test method for verification of the strength of the trip
mechanism, valve seat and closing member . 55
4

---------------------- Page: 6 ----------------------
oSIST prEN 14382:2016
prEN 14382:2016 (E)
D.1 Test method . 55
D.2 Test method for the determination of the dynamic factor C . 55
r
D.3 Test method for a series of SSDs . 56
Annex E (informative) Sizing equation . 58
Annex F (informative) Inspection certificate. 59
Annex G (informative) Order specification . 61
G.1 General . 61
G.2 Minimum specifications . 61
G.3 Optional specifications . 62
Annex H (informative) Acceptance test . 63
Annex I (informative) Suitability of safety shut-off device for damp operating conditions . 64
I.1 Test procedure, requirement and acceptance criteria . 64
Annex J (normative) Vent limiter . 65
J.1 General . 65
J.2 Scope . 65
J.3 Terms, symbols and definitions . 65
J.4 Requirements . 66
J.5 Testing and acceptance criteria . 66
J.6 Documentation . 68
J.7 Specific marking on vent limiter . 68
Annex K (informative) Glossary and sub-clauses . 69
Annex L (informative) Environmental Provisions . 72
Annex ZA (informative) Relationship between this European Standard and the Essential
Requirements of EU Directive 2014/68/EU . 76
Bibliography . 78

5

---------------------- Page: 7 ----------------------
oSIST prEN 14382:2016
prEN 14382:2016 (E)
European foreword
This document (prEN 14382:2016) has been prepared by Technical Committee CEN/TC 235 “Gas
pressure regulators and associated safety devices for use in gas transmission and distribution”, the
secretariat of which is held by UNI.
This document is currently submitted to the CEN Enquiry.
This document will supersede EN 14382:2005+A1:2009.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive(s).
For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this
document.
The main amendments in comparison to EN 14382:2005+A1:2009, deal with:
— Up-dated the normative references;
— Added terms and definitions;
— Classification of two in series SSDs as safety accessory to PED;
— Full reference to prEN 334:2016 for end connections, flange rating, nominal and face to face
dimensions, materials (metallic and non-metallic), verification of strength of pressure bearing
parts;
— Statistical strength test on the basis of PED provisions;
— Antistatic characteristics;
— Vent limiter as possible fixture to be assembled in the SSDs;
— Integration of environmental requirements;
— Alignment of Normative references (Clause 2), Annex G, Annex ZA and its relevant clauses to CEN
rules.
The standard has been editorially revised.
This document can be used as a guideline for gas safety shut off devices outside the ranges specified in
this standard.
This edition has introduced the application of statistical strength testing for series produced pressure
and safety accessories on the basis of EU Directive 2014/68/EU Annex I article 3.2.2 and Guideline
8/14. Safety shut-off devices dealt with in this document are standard safety shut-off devices and, when
used in pressure regulating stations complying with EN 12186 or EN 12279, they are considered as
standard pressure equipment in accordance with Clause 2 a) of Art. 1 of Pressure Equipment Directive
2014/68/EU (PED).
Fo
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.