Switches for household and similar fixed-electrical installations -- Part 1: General requirements

Applies to manually operated general purpose switches for a.c. only, with a rated voltage not exceeding 440 V and a rated current not exceeding 63 A.

Schalter für Haushalt und ähnliche ortsfeste elektrische Installationen -- Teil 1: Allgemeine Anforderungen

Interrupteurs pour installations électriques fixes domestiques et analogues -- Partie 1: Prescriptions générales

S'applique aux interrupteurs à courant alternatif seulement à commande manuelle pour usages courants, de tension assignée ne dépassant pas 440 V et de courant assigné ne dépassant pas 63 A.

Switches for household and similar fixed electrical installations - Part 1: General requirements

General Information

Status
Withdrawn
Publication Date
31-Aug-2000
Withdrawal Date
09-Dec-2020
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
09-Dec-2020
Due Date
01-Jan-2021
Completion Date
10-Dec-2020

Relations

Buy Standard

Standard
EN 60669-1:2000
English language
107 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 60669-1:2000
01-september-2000
1DGRPHãþD
SIST EN 60669-1:1996
SIST EN 60669-1:1996/A2:1997
Switches for household and similar fixed electrical installations - Part 1: General
requirements
Switches for household and similar fixed-electrical installations -- Part 1: General
requirements
Schalter für Haushalt und ähnliche ortsfeste elektrische Installationen -- Teil 1:
Allgemeine Anforderungen
Interrupteurs pour installations électriques fixes domestiques et analogues -- Partie 1:
Prescriptions générales
Ta slovenski standard je istoveten z: EN 60669-1:1999
ICS:
29.120.40 Stikala Switches
SIST EN 60669-1:2000 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 60669-1:2000

---------------------- Page: 2 ----------------------

SIST EN 60669-1:2000

EUROPEAN STANDARD
 EN 60669-1



NORME EUROPÉENNE


 October 1999
EUROPÄISCHE NORM

ICS 29.120.40 Supersedes EN 60669-1:1995 + A2:1996



English version


Switches for household and similar fixed-electrical installations
Part 1: General requirements
(IEC 60669-1:1998, modified)


Interrupteurs pour installations électriques Schalter für Haushalt und ähnliche
fixes domestiques et analogues ortsfeste elektrische Installationen
Partie 1: Prescriptions générales Teil 1: Allgemeine Anforderungen
(CEI 60669-1:1998, modifiée) (IEC 60669-1:1998, modifiziert)







This European Standard was approved by CENELEC on 1999-01-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and
notified to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic,
Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway,
Portugal, Spain, Sweden, Switzerland and United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels

1999 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
©

  Ref. No. EN 60669-1:1999 E

---------------------- Page: 3 ----------------------

SIST EN 60669-1:2000
Page 2
EN 60669-1:1999
Foreword

The text of the International Standard IEC 60669-1:1998, prepared by SC 23B, Plugs, socket-
outlets and switches, of IEC TC 23, together with the common modifications prepared by the
Technical Committee CENELEC TC 23B, Switches for household and similar fixed electrical
installations, was submitted to the Unique Acceptance Procedure and was approved by
CENELEC as EN 60669-1 on 1999-01-01.

This European Standard supersedes EN 60669-1:1995 and its amendment A2:1996.

The following dates were fixed:

- latest date by which the EN has to be implemented
at national level by publication of an identical national
standard or by endorsement (dop) 2000-05-01
- latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2005-10-01

Annexes designated "normative" are part of the body of the standard.
Annexes designated "informative" are given for information only.
In this standard, annexes A, B, ZA and ZB are normative, annex ZC is informative.
Annexes ZA, ZB and ZC have been added by CENELEC.

---------------------- Page: 4 ----------------------

SIST EN 60669-1:2000
Page 3
EN 60669-1:1999
Endorsement notice

The text of the International Standard IEC 60669-1:1998 was approved by CENELEC as a
European Standard with agreed common modifications as given below.

COMMON MODIFICATIONS

1 Scope


Add after note 1:

Unless otherwise specified in subsequent parts, this standard applies to switches
intended to be used at 50 Hz.

NOTE 2 - Switches according to this standard are intended for functional purposes only.

Renumber subsequent notes.

2 Normative references

Replace the text of clause 2 by :

NOTE - Normative references to international publications are listed in Annex ZA (normative).

3 Definitions

3.1.3
Replace by “void”.

Add the following definitions :

3.1.6
switch of normal gap construction
switch construction having a clearance between the contacts in the open position
not less than 3 mm

3.1.7
switch of micro-gap construction
switch construction having a clearance between the contacts in the open position
less than 1,2 mm

3.1.8
switch without gap construction
switch having a semiconductor switching device which has no contact gap


3.21
type test
(IEV 151-04-15) test of one or more switches made to a certain design to show that
the design meets certain specifications


3.22
routine test
(IEV 151-04-16) test to which each individual switch is subjected during and/or after
manufacture to ascertain whether it complies with certain criteria

---------------------- Page: 5 ----------------------

SIST EN 60669-1:2000
Page 4
EN 60669-1:1999

3.23
surface-type switch
switch, which when mounted, projects wholly above the surface on which it is
mounted


3.24
flush-type switch
switch mainly intended to be mounted in a flush-type box

3.25
semi flush-type switch
switch mainly intended to be mounted in a semi flush-type box

3.26
panel-type switch
switch mainly intended for mounting to a panel having an aperture through which
the intended accessible surface of the switch protrudes

3.27
architrave-type switch
switch having a cover plate of such proportions that it may be accommodated within
an architrave

3.28
live part
(IEV 826-03-01) conductor or conductive part intended to be energised in normal
use, including a neutral conductor but, by convention not a PEN conductor

NOTE - A protective conductor (PE) is not a live part.


3.29
actuating member
(IEV 442-04-16) part which is pulled, pushed or turned or otherwise moved to cause
an operation

4 General requirements

Add after the first paragraph:

Where tolerances are not specified in this standard the values are to be regarded

as nominal.

5 General notes on tests

5.4 Replace the 11th paragraph by:

Switches marked with a dual voltage are tested at the higher voltage.

Replace the last paragraph by:

Momentary contact switches are not to be submitted to the tests of 18.2 and 19.2.

6 Ratings

---------------------- Page: 6 ----------------------

SIST EN 60669-1:2000
Page 5
EN 60669-1:1999
6.1 Replace the first and second paragraphs by:

Switches shall preferably have rated voltages of 250 V and 400 V.

The values 230 V, 380 V and 440 V may be used.

For momentary contact switches the preferred rated voltages are 130 V and 250 V.

6.2
In the first paragraph add "45 A" after "40 A".

Replace the second paragraph by:

The rated current shall not be less than 6 A, except that rated currents of 1 A, 2 A
and 4 A are allowed for momentary contact switches, electromagnetic remote
control switches and time delay switches.


7 Classification

7.1.4 Delete, in the second dashed text, the word "splash-proof".

Delete, in the third dashed text, the word "jet-proof".

7.1.7 Add at the end of the subclause:

NOTE - See Annex ZB for special national conditions.

7.2 Table 1, column 1, add the value "45" after "40".


8 Marking

8.1 Add:

NOTE - See Annex ZB for special national conditions.

8.3 On the last paragraph before note 2, replace the words "on removal of any cover or
cover-plate which may be present when the switch is mounted and wired as in
normal use" by "during installation".

Add:

NOTE - See Annex ZB for special national conditions.

8.6 Replace the first sentence of the first paragraph by:

If switches of pattern numbers 2, 3, 03 and switches having a rated voltage
exceeding 250 V and rated current exceeding 16 A are marked to indicate the
switch position, they shall be so marked that the direction of the movement of the
actuating member to its different positions or the actual switch position is clearly
indicated.

Delete the last but one paragraph and the relevant note 2.

8.8 Change note 2 into a requirement and replace its first sentence by:

---------------------- Page: 7 ----------------------

SIST EN 60669-1:2000
Page 6
EN 60669-1:1999

If special precautions are necessary in order to ensure that, after installation, the
conditions necessary to meet the requirements of this standard are achieved, the
instruction sheet shall include clear information with regard to the following:


9 Checking of dimensions

Add after the first paragraph:

The manufacturer of the switch shall specify in his catalogue the type of boxes
(flush or surface, etc.) in which his switches are to be mounted.


10 Protection against electric shock

10.2 Add:

NOTE - See Annex ZB for special national conditions.

10.3 Replace "covers or cover-plates" by "covers, cover-plates and other parts of the
enclosure".

Add:

NOTE - See Annex ZB for special national conditions.

10.3.1 Replace "covers or cover-plates" by " covers, cover-plates and other parts of the
enclosure".

10.3.2 Replace "covers or cover-plates" by "covers, cover-plates and other parts of the
enclosure".

Add:

NOTE - See Annex ZB for special national conditions.

---------------------- Page: 8 ----------------------

SIST EN 60669-1:2000
Page 7
EN 60669-1:1999
10.5 Add after the third paragraph:

NOTE 1 - See Annex ZB for special national conditions.


11 Provision for earthing

11.1 Change notes 1 and 2 into requirements.

11.2 Replace the second paragraph by:

They shall have a capacity not less than that of the corresponding terminals for the
supply conductors.

Add:

NOTE - See Annex ZC for A-deviations.

11.3 At the beginning of the paragraph, replace "Switches" by "Surface-type switches".


12 Terminals

12.2.1 In table 2, replace the value "40" by "45".

12.2.4 Replace the second paragraph by:

Terminals the body of which is made of materials as detailed in 22.5, are
considered as complying with this requirement.

12.2.5 Delete the paragraph before table 4.

Replace the text of note 1 in table 4 by "Void".

12.2.6 In the last paragraph, replace "in case where they exist in the relevant IEC
standard" by "if any, according to HD 21.3,"

Replace the note by:

NOTE - See Annex ZB for special national conditions.

12.3.1 Number the present note as note 1, and add:

NOTE 2 - The tests of 12.3.12 are carried out using rigid solid conductors only.

---------------------- Page: 9 ----------------------

SIST EN 60669-1:2000
Page 8
EN 60669-1:1999
12.3.2 Replace table 7 by:

Table 7 - Relationship between rated currents and connectable cross-sectional areas
of copper conductors for screwless terminals

Rated current Conductors
Nominal cross-sectional Diameter of the largest Diameter of the largest
A areas
rigid conductor flexible conductors
2
mm
mm mm
Up to and including 4 0,75-1 1,19 -
Above 4 and including 6 1-1,5 1,45 1,73
1)
Above 6 and including 16 1,5-2,5 2,13 2,21
1)
Each supply terminal of switches other than those of patter numbers 3, 03, and 7, shall allow the connection
2
of 2 x 2,5 mm conductors. In such cases terminals for rated current 10 A with separate independent clamping
means for each conductor shall be used.

12.3.11 Replace table 8 by:

Table 8 - Test current for the verification of the electrical and thermal stresses
in normal use of screwless terminals

Rated current Test current Cross sectional area of the
 conductor
2
A A
mm
Up to and including 4 9 0,75
Above 4 and including 6 13,5 1
Above 6 and including 10 17,5 1,5
Above 10 and including 16 22 2,5

12.3.12 Replace in the paragraph after note 3 the reference “table 8” by “table 9”.


13 Constructional requirements

13.12 Replace in table 12, column 1, the value "40" by "40-45".

13.15.2 Replace the note by:

NOTE - See Annex ZB for special national conditions.


15 Resistance to ageing, to harmful ingress of water and to humidity

15.1 Replace in the 9th paragraph, the value "55 %" by "75 %".

15.2.1 Add after the last paragraph:

During the test, the drain hole, if any, of switches with IP higher than IPX4 shall not
be opened.

15.2.2 Replace this subclause by:

Switches with a degree of protection IPX4 are tested according to EN 60529.
15.2.3 Replace this subclause by:

---------------------- Page: 10 ----------------------

SIST EN 60669-1:2000
Page 9
EN 60669-1:1999

Switches with a degree of protection IPX5 are tested according to EN 60529.

Add the following subclause:

15.2.4  During the test of 15.2.2 or 15.2.3 care shall be taken not to disturb the
switch, for instance with shocks or jerks, to such an extent that the results of the
test are modified.

If the accessory is provided with a drain hole, inspection shall show that water
having entered the specimen does not accumulate and drip off without further
damage to the whole equipment.

NOTE 1 - For a degree of protection higher than IPX4, it may be necessary to open the drain hole for
inspection.

NOTE 2 - If the accessory is not provided with drain holes, consideration should be given to the
dispersal of any accumulation of water which may occur.

Immediately after the test of 15.2.2 or 15.2.3 the specimens shall withstand the
electric strength test as specified in 16.2. This test shall begin within 5 min after
completion of the test of 15.2.2 or 15.2.3.


16 Insulation resistance and electric strength

16.2 Replace in Table 14, item 3, third column, "(note 2)" by "(note 1)".

17 Temperature rise

Add the following row to table 15 between the values given for rated currents "40"
and "63":

45 51 16


19 Normal operation

19.1 In table 17, replace the value "40" by "45".

In the 14th paragraph after table 17, replace the words "length 0,3 m ± 0,015 m" by
"length of at least 1 m".

19.2 Replace the second paragraph, page 107, by:

Switches of pattern N° 7 are tested as a double switch of pattern number N° 6.
While testing one part, the other part is in the off position.

Add, in the last but one paragraph, after the words "in clause 17," the words "using
conductors as specified in this subclause, and .".

---------------------- Page: 11 ----------------------

SIST EN 60669-1:2000
Page 10
EN 60669-1:1999
20 Mechanical strength

Delete in the first dashed text “other than ordinary”.


22 Screws, current carrying parts and connections

22.1 Delete the second sentence of the second paragraph.


23 Creepage distances, clearances and distances through sealing compound

1) 1) 6)
23.1 In table 20, item 2, replace the values "4 " by "4 "
6)
In table 20, item 7, replace the value "3" by "3 "
In table 20, item 9, replace the value “3” by “2,5”.

Add at the bottom of table 20:


6) Clearances and creepage distances between live parts of different polarity are reduced to 1 mm for
the distance between the lead wires in the pinch of a neon indicator lamp with external resistor.

Add the following subclause:

23.3  Ordinary surface-type switches shall not have bare current-carrying strips at
the back.

Compliance is checked by inspection.


24 Resistance of insulating material to abnormal heat, to fire and to tracking

24.1.1 Replace the existing item b) by:

b) for parts of insulating material not necessary to retain current-carrying parts and
parts of the earthing circuit in position, even though they are in contact with them,
and parts of insulating materials necessary to hold in position the earthing terminal
in an enclosure, by the test made at a temperature of 650 °C.


Annex B Additional requirements for switches having facilities for the outlet and
retention of flexible cables
3 Definition

Renumber 3.21 as 3.201.

8 Marking

8.1 Add the following paragraph at the end of this subclause:

In addition for switches where a cord anchorage is intended to clamp effectively
flexible cables other than those nominal cross-sectional areas appropriate to the
rating of the switch as given in Table 2, then the minimum and maximum sizes for
which the anchorage is provided may be marked in an area adjacent to the

---------------------- Page: 12 ----------------------

SIST EN 60669-1:2000
Page 11
EN 60669-1:1999
anchorage, e.g. "6 mm - 16 mm" or "6-16". This information shall be put on the
switch and/or the packaging unit.

13 Constructional requirements

13.16 In the first paragraph, replace: "code designation 60227 IEC 53" by "code
designation 60227 IEC 52 or 60227 IEC 53".

Repla
...