Rotating electrical machines - Part 2-3: Specific test methods for determining losses and efficiency of converter-fed AC motors (IEC 60034-2-3:2020)

This part of IEC 60034 specifies test methods and an interpolation procedure for determining
losses and efficiencies of converter-fed motors within the scope of IEC 60034-1:2017. The
motor is then part of a variable frequency power drive system (PDS) as defined in
IEC 61800-9-2:2017.
Applying the approach of the comparable converter, the motor efficiency determined by use of
this document is applicable for comparison of different motor designs only.
The document also specifies procedures to determine motor losses at any load point (torque,
speed) within the base speed range (constant torque range, constant flux range) based on
determination of losses at seven standardized load points. This procedure is applicable to any
variable speed AC motor (induction and synchronous) rated according to IEC 60034-1:2017 for
operation on a variable frequency and variable voltage power supply.

Drehende elektrische Maschinen - Teil 2-3: Besondere Verfahren zur Bestimmung der Verluste und des Wirkungsgrades von umrichtergespeisten Wechselstrommaschinen (IEC 60034-2-3:2020)

Machines électriques tournantes - Partie 2-3: Méthodes d'essai spécifiques pour la détermination des pertes et du rendement des moteurs à courant alternatif alimentés par convertisseur (IEC 60034-2-3:2020)

l'IEC 60034-2-3:2020 spécifie les méthodes d’essai et la procédure d’interpolation relatives à la détermination des pertes et des rendements des moteurs alimentés par convertisseur relevant du domaine d’application de l’IEC 60034-1:2017. Le moteur est alors considéré comme faisant partie intégrante d'un système d’entraînement électrique de puissance (PDS – power drive system) à fréquence variable, comme cela est défini dans l’IEC 61800-9-2:2017.
Avec l’approche du convertisseur comparable, le rendement du moteur déterminé par l’utilisation du présent document s’applique uniquement à la comparaison des différentes conceptions de moteurs.
Le document spécifie également des procédures de détermination des pertes du moteur en tout point de charge (couple, vitesse) dans la plage de vitesses de base (plage de couples constants, plage de flux constants) à partir de la détermination des pertes au niveau de sept points de charge normalisés. Cette procédure s’applique à tout moteur à courant alternatif à vitesse variable (à induction et synchrone) assigné selon l’IEC 60034-1:2017 pour un fonctionnement à fréquence variable et alimenté en tension variable.

Električni rotacijski stroji - 2-3. del: Posebne preskusne metode za ugotavljanje izgub in izkoristka motorja na izmenični tok, napajanega prek pretvornikov (IEC 60034-2-3:2020)

General Information

Status
Published
Public Enquiry End Date
24-Mar-2019
Publication Date
06-Sep-2020
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
13-May-2020
Due Date
18-Jul-2020
Completion Date
07-Sep-2020

Relations

Buy Standard

Standard
EN IEC 60034-2-3:2020 - BARVE
English language
30 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Draft
prEN IEC 60034-2-3:2019 - BARVE
English language
21 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN IEC 60034-2-3:2020
01-oktober-2020
Električni rotacijski stroji - 2-3. del: Posebne preskusne metode za ugotavljanje
izgub in izkoristka motorja na izmenični tok, napajanega prek pretvornikov (IEC
60034-2-3:2020)
Rotating electrical machines - Part 2-3: Specific test methods for determining losses and
efficiency of converter-fed AC motors (IEC 60034-2-3:2020)
Drehende elektrische Maschinen - Teil 2-3: Besondere Verfahren zur Bestimmung der
Verluste und des Wirkungsgrades von umrichtergespeisten Wechselstrommaschinen
(IEC 60034-2-3:2020)
Machines électriques tournantes - Partie 2-3: Méthodes d'essai spécifiques pour la
détermination des pertes et du rendement des moteurs à courant alternatif alimentés par
convertisseur (IEC 60034-2-3:2020)
Ta slovenski standard je istoveten z: EN IEC 60034-2-3:2020
ICS:
29.160.01 Rotacijski stroji na splošno Rotating machinery in
general
SIST EN IEC 60034-2-3:2020 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
SIST EN IEC 60034-2-3:2020

---------------------- Page: 2 ----------------------
SIST EN IEC 60034-2-3:2020


EUROPEAN STANDARD EN IEC 60034-2-3

NORME EUROPÉENNE

EUROPÄISCHE NORM
May 2020
ICS 29.160.01

English Version
Rotating electrical machines - Part 2-3: Specific test methods for
determining losses and efficiency of converter-fed AC motors
(IEC 60034-2-3:2020)
Machines électriques tournantes - Partie 2-3: Méthodes Drehende elektrische Maschinen - Teil 2-3: Besondere
d'essai spécifiques pour la détermination des pertes et du Verfahren zur Bestimmung der Verluste und des
rendement des moteurs à courant alternatif alimentés par Wirkungsgrades von umrichtergespeisten
convertisseur Wechselstrommaschinen
(IEC 60034-2-3:2020) (IEC 60034-2-3:2020)
This European Standard was approved by CENELEC on 2020-04-23. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.


European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2020 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
 Ref. No. EN IEC 60034-2-3:2020 E

---------------------- Page: 3 ----------------------
SIST EN IEC 60034-2-3:2020
EN IEC 60034-2-3:2020 (E)
European foreword
The text of document 2/1974/FDIS, future edition 1 of IEC 60034-2-3, prepared by IEC/TC 2 "Rotating
machinery" was submitted to the IEC-CENELEC parallel vote and approved by CENELEC as
EN IEC 60034-2-3:2020.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2021-01-23
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2023-04-23
document have to be withdrawn

Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.

Endorsement notice
The text of the International Standard IEC 60034-2-3:2020 was approved by CENELEC as a
European Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards
indicated:
1
IEC/TS 60034-25:2014 NOTE Harmonized as CLC/TS 60034-25:— (not modified)
IEC 61800-2:2015 NOTE Harmonized as EN 61800-2:2015 (not modified)
IEC 61800-4:2002 NOTE Harmonized as EN 61800-4:2003 (not modified)



1
To be published. Stage at the time of publication: CLC/prTS 60034-25:2017.
2

---------------------- Page: 4 ----------------------
SIST EN IEC 60034-2-3:2020
EN IEC 60034-2-3:2020 (E)
Annex ZA
(normative)

Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1  Where an International Publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
NOTE 2  Up-to-date information on the latest versions of the European Standards listed in this annex is available here:
www.cenelec.eu.
Publication Year Title EN/HD Year
IEC 60034-1 2017 Rotating electrical machines - Part 1: Rating - -
and performance
IEC 60034-2-1 2014 Rotating electrical machines - Part 2-1: EN 60034-2-1 2014
Standard methods for determining losses
and efficiency from tests (excluding
machines for traction vehicles)
IEC 61000-2-4 2002 Electromagnetic compatibility (EMC) - Part EN 61000-2-4 2002
2-4: Environment - Compatibility levels in
industrial plants for low-frequency conducted
disturbances
IEC 61800-9-2 2017 Adjustable speed electrical power drive EN 61800-9-2 2017
systems - Part 9-2: Ecodesign for power
drive systems, motor starters, power
electronics and their driven applications -
Energy efficiency indicators for power drive
systems and motor starters




3

---------------------- Page: 5 ----------------------
SIST EN IEC 60034-2-3:2020

---------------------- Page: 6 ----------------------
SIST EN IEC 60034-2-3:2020




IEC 60034-2-3

®


Edition 1.0 2020-03




INTERNATIONAL



STANDARD




NORME



INTERNATIONALE
colour

inside










Rotating electrical machines –

Part 2-3: Specific test methods for determining losses and efficiency of

converter-fed AC motors




Machines électriques tournantes –

Partie 2-3: Méthodes d'essai spécifiques pour la détermination des pertes


et du rendement des moteurs à courant alternatif alimentés par convertisseur













INTERNATIONAL

ELECTROTECHNICAL

COMMISSION


COMMISSION

ELECTROTECHNIQUE


INTERNATIONALE




ICS 29.160.01 ISBN 978-2-8322-7842-0




Warning! Make sure that you obtained this publication from an authorized distributor.

Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distributeur agréé.

® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale

---------------------- Page: 7 ----------------------
SIST EN IEC 60034-2-3:2020
– 2 – IEC 60034-2-3:2020 © IEC 2020
CONTENTS
FOREWORD . 4
INTRODUCTION . 6
1 Scope . 8
2 Normative references . 8
3 Terms and definitions . 8
4 Symbols and abbreviated terms . 9
5 Basic requirements . 10
5.1 Instrumentation . 10
5.1.1 General . 10
5.1.2 Power analyser and transducers . 10
5.1.3 Mechanical output of the motor . 11
5.2 Converter set-up . 11
5.2.1 General . 11
5.2.2 Comparable converter set-up for rated voltages up to 1 kV . 11
5.2.3 Testing with converters with rated voltages above 1 kV . 12
5.2.4 Testing with other converters . 12
6 Test method for the determination of the efficiency of converter-fed motors . 12
6.1 Selection of determination method . 12
6.2 Method 2-3-A – Direct measurement of input and output . 13
6.2.1 Test set-up . 13
6.2.2 Test procedure . 13
6.2.3 Efficiency determination. 13
6.2.4 Measurement at seven standardized operating points . 14
6.3 Method 2-3-B – Summation of losses with determination of additional high
frequency loss at converter supply at no-load operation . 14
6.3.1 General . 14
6.3.2 Test set-up . 14
6.3.3 Test procedure . 14
6.3.4 Efficiency determination. 15
6.4 2-3-C – Alternate Efficiency Determination Method (AEDM) . 15
6.5 2-3-D – Determination of efficiency by calculation . 15
7 Interpolation of losses at any operating point . 16
7.1 General . 16
7.2 Interpolation procedure . 16
7.3 Analytical determination of relative losses at any operating point . 16
7.4 Additional losses due to frequency converter voltage drop . 18
7.5 Alternate operating points to determine interpolation coefficients . 18
7.6 Optional determination of interpolation error . 19
Annex A (informative) Losses of AC motors . 21
A.1 General . 21
2
A.2 Stator and rotor winding I R losses P (P + P ) . 21
LSR LS LR
A.3 Iron losses (P ) . 21
Lfe
A.4 Additional load losses (P ) . 22
LL
A.5 Friction and windage losses (P ) . 22
Lfw
A.6 Additional high frequency losses (P ) . 23
LHL

---------------------- Page: 8 ----------------------
SIST EN IEC 60034-2-3:2020
IEC 60034-2-3:2020 © IEC 2020 – 3 –
Annex B (informative) Exemplary determination of losses and efficiency at various
load points . 24
B.1 General . 24
B.2 Determination of the interpolation coefficients . 24
B.3 Calculation of losses and efficiency for certain operating points . 25
Bibliography . 27

Figure 1 – Standardized operating points . 17

Table 1 – Preferred test methods . 12
Table 2 – Other test methods . 13
Table 3 – Normative operating points . 17
Table 4 – Non-normative alternate operating points . 19
Table A.1 – Recommended split of windage and friction losses for IC 411 self-
ventilated motors . 22
Table B.1 – Name plate data . 24
Table B.2 – Reference values . 24
Table B.3 – Losses for the 7 operating points . 25
Table B.4 – Interpolation coefficients . 25
Table B.5 – User-defined operating points . 26
Table B.6 – Calculated losses for the user-defined operating points . 26

---------------------- Page: 9 ----------------------
SIST EN IEC 60034-2-3:2020
– 4 – IEC 60034-2-3:2020 © IEC 2020
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________

ROTATING ELECTRICAL MACHINES –

Part 2-3: Specific test methods for determining losses and
efficiency of converter-fed AC motors

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC Publication(s)”). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of patent
rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60034-2-3 has been prepared by IEC technical committee 2:
Rotating machinery.
This first edition cancels and replaces IEC TS 60034-2-3, published in 2013.
The text of this International Standard is based on the following documents:
FDIS Report on voting
2/1974/FDIS 2/1982/RVD

Full information on the voting for the approval of this International Standard can be found in the
report on voting indicated in the above table.
This document has been drafted in accordance with the ISO/IEC Directives, Part 2.

---------------------- Page: 10 ----------------------
SIST EN IEC 60034-2-3:2020
IEC 60034-2-3:2020 © IEC 2020 – 5 –
A list of all parts in the IEC 60034 series, published under the general title Rotating electrical
machines, can be found on the IEC website.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under "http://webstore.iec.ch" in the data related to
the specific document. At this date, the document will be
reconfirmed,
withdrawn,
replaced by a revised edition, or
amended.

IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct understanding
of its contents. Users should therefore print this document using a colour printer.

---------------------- Page: 11 ----------------------
SIST EN IEC 60034-2-3:2020
– 6 – IEC 60034-2-3:2020 © IEC 2020
INTRODUCTION
The objective of this document is to define test methods for determining total losses including
additional high frequency motor losses and efficiency of converter-fed motors. Additional high
frequency losses appear in addition to the losses on nominally sinusoidal power supply as
determined by the methods of IEC 60034-2-1:2014. Results determined according to this
document are intended to allow comparison of losses and efficiency of different motors when
fed by converters.
Furthermore, the document gives seven standardized operating points to characterize the
development of losses and efficiency across the whole torque/speed range. An interpolation
procedure is provided to calculate losses and efficiency at any operating point (torque, speed).
In power-drive systems (PDS), the motor and the frequency converter are often manufactured
by different suppliers. Motors of the same design are produced in large quantities. They may
be operated from the grid or from frequency converters of many different types, supplied by
many different manufacturers. The individual converter properties (switching frequency, DC link
voltage level, etc.) will also influence the system efficiency. As it is impractical to determine
motor losses for every combination of motor, frequency converter, connection cable, output
filter and parameter settings, this document describes a limited number of approaches,
depending on the voltage level and the rating of the machine under test.
The losses determined according to this document are not intended to represent the losses in
the final application. They provide, however, an objective basis for comparing different motor
designs with respect to suitability for converter operation.
In general, when fed from a converter, motor losses are higher than during operation on a
nominally sinusoidal system. The additional high frequency losses depend on the harmonic
spectrum of the impressed converter output quantity (either current or voltage) which is
influenced by its circuitry and control method. For further information,
see IEC TS 60034-25:2014.
It is not the purpose of this document to define test procedures either for power drive systems
or for frequency converters alone.
Comparable converter
Latest experience and theoretical analysis have shown that the additional high frequency motor
losses generally do not increase much with load. The methods in this document are mainly
based on supplies from converters with pulse width modulation (PWM).
With respect to these types of converters and the growing need for verification of compliance
with national energy efficiency regulations, this document defines a so-called comparable
converter for testing of low voltage motors.
In principle, the comparable converter is a voltage source with a typical high frequency harmonic
content supplying the machine under test. It is not applicable to medium voltage motors.
Limitations for the application of the comparable converter
It has to be noted that the test method with the comparable converter described herein is a
standardized method intended to give comparable efficiency figures for standardized test
conditions. A motor ranking with respect to suitability for converter operation may be derived,
but it is not equivalent to determining of the actual motor losses for operation with a specific
converter which requires a test of the whole power drive system (PDS) with the specific
converter used in the final application.

---------------------- Page: 12 ----------------------
SIST EN IEC 60034-2-3:2020
IEC 60034-2-3:2020 © IEC 2020 – 7 –
Deviations are also expected for motors driven by multi-level voltage source or current source
converters where the additional high frequency motor losses differ much more depending on
speed and load than for two-level voltage source converters. Hence the determination of losses
and efficiency should preferably use procedures where the motor is operated together with the
same converter with which it is driven in service.
Another option is the determination of the additional high frequency motor losses by calculation.
If this is requested by the customer, the pulse pattern of the converter is required. Such
procedures are not part of this document.
The provided interpolation procedure for the determination of losses and efficiency at any
operating point (torque, speed) is limited to the base speed range (constant torque range,
constant flux range).

---------------------- Page: 13 ----------------------
SIST EN IEC 60034-2-3:2020
– 8 – IEC 60034-2-3:2020 © IEC 2020
ROTATING ELECTRICAL MACHINES –

Part 2-3: Specific test methods for determining losses and
efficiency of converter-fed AC motors



1 Scope
This part of IEC 60034 specifies test methods and an interpolation procedure for determining
losses and efficiencies of converter-fed motors within the scope of IEC 60034-1:2017. The
motor is then part of a variable frequency power drive system (PDS) as defined in
IEC 61800-9-2:2017.
Applying the approach of the comparable converter, the motor efficiency determined by use of
this document is applicable for comparison of different motor designs only.
The document also specifies procedures to determine motor losses at any load point (torque,
speed) within the base speed range (constant torque range, constant flux range) based on
determination of losses at seven standardized load points. This procedure is applicable to any
variable speed AC motor (induction and synchronous) rated according to IEC 60034-1:2017 for
operation on a variable frequency and variable voltage power supply.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies.
For undated references, the latest edition of the referenced document (including any
amendments) applies.
IEC 60034-1:2017, Rotating electrical machines – Part 1: Rating and performance
IEC 60034-2-1:2014, Rotating electrical machines – Part 2-1: Standard methods for
determining losses and efficiency from tests (excluding machines for traction vehicles)
IEC 61000-2-4:2002, Electromagnetic compatibility (EMC) – Part 2-4: Environment –
Compatibility levels in industrial plants for low-frequency conducted disturbances
IEC 61800-9-2:2017, Adjustable speed electrical power drive systems – Part 9-2: Ecodesign for
power drive systems, motor starters, power electronics and their driven applications – Energy
efficiency indicators for power drive systems and motor starters
3 Terms and definitions
For the purposes of this document, the terms and definitions given in IEC 60034-1:2017,
IEC 60034-2-1:2014 as well as the following apply.
ISO and IEC maintain terminological databases for use in standardization at the following
addresses:
• IEC Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http://www.iso.org/obp

---------------------- Page: 14 ----------------------
SIST EN IEC 60034-2-3:2020
IEC 60034-2-3:2020 © IEC 2020 – 9 –
3.1
motor losses with converter supply
when powered by a converter, motor losses are a combination of losses caused by fundamental
frequency and losses caused by the converter high frequencies
3.2
fundamental losses
fundamental losses in the motor can be segregated into five different components: iron losses
(varying with motor frequency and applied fundamental voltage), friction and windage losses
(varying with motor speed), rotor winding losses, stator winding losses and additional load
losses (all three varying with motor current). Fundamental losses are the losses of a motor
running with application of rated voltage at fundamental frequency that does not contain any
further high frequencies.
3.3
additional high frequency losses
additional high frequency losses are produced in the motor by the non-sinusoidal voltage and
current waveforms generated by the converter and are in addition to the losses of iron, friction
and windage, rotor winding, stator winding and additional load loss (fundamental losses)
3.4
base speed range
speed range from standstill up to the highest speed where the motor can be supplied with a
voltage that changes in proportion to the speed so that the magnetic flux remains constant
(constant ratio U/f) for induction machines and according to the MTPA (maximum torque per
ampere) for synchronous machines. Within the base speed range, the maximum motor torque

is constant (constant torque range), if constant flux control is used.
3.5
switching frequency
number of switching events of one semiconductor within one second. It determines, together
with the selected pulse pattern and the converter topology, the lowest frequency of non-
controllable high frequencies or inter-harmonics at the IPC (in-plant point of coupling) or the
motor
Note 1 to entry: For a two level converter, the pulse frequency measured phase to phase is two times the switching
frequency defined in 3.5 in case of continuous modulation and about 1,33 times the switching frequency defined in
3.5 in case of discontinuous modulation. A switching event is once on and once off of one semiconductor.
4 Symbols and abbreviated term
...

SLOVENSKI STANDARD
oSIST prEN IEC 60034-2-3:2019
01-marec-2019
(OHNWULþQLURWDFLMVNLVWURMLGHO3RVHEQHSUHVNXVQHPHWRGH]DXJRWDYOMDQMH
L]JXELQL]NRULVWNDPRWRUMDQDL]PHQLþQLWRNQDSDMDQHJDSUHNSUHWYRUQLNRY
Rotating electrical machines - Part 2-3: Specific test methods for determining losses and
efficiency of converter-fed AC motor
Ta slovenski standard je istoveten z: prEN IEC 60034-2-3:2019
ICS:
29.160.01 Rotacijski stroji na splošno Rotating machinery in
general
oSIST prEN IEC 60034-2-3:2019 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN IEC 60034-2-3:2019

---------------------- Page: 2 ----------------------
oSIST prEN IEC 60034-2-3:2019
2/1933/CDV

COMMITTEE DRAFT FOR VOTE (CDV)
PROJECT NUMBER:
IEC 60034-2-3 ED1
DATE OF CIRCULATION: CLOSING DATE FOR VOTING:
2019-01-04 2019-03-29
SUPERSEDES DOCUMENTS:
2/1879/CD,2/1903A/CC

IEC TC 2 : ROTATING MACHINERY
SECRETARIAT: SECRETARY:
United Kingdom Mr Charles Whitlock
OF INTEREST TO THE FOLLOWING COMMITTEES: PROPOSED HORIZONTAL STANDARD:


Other TC/SCs are requested to indicate their interest, if any, in
this CDV to the secretary.
FUNCTIONS CONCERNED:

EMC ENVIRONMENT QUALITY ASSURANCE SAFETY
SUBMITTED FOR CENELEC PARALLEL VOTING NOT SUBMITTED FOR CENELEC PARALLEL VOTING
Attention IEC-CENELEC parallel voting
The attention of IEC National Committees, members of
CENELEC, is drawn to the fact that this Committee Draft for
Vote (CDV) is submitted for parallel voting.
The CENELEC members are invited to vote through the
CENELEC online voting system.

This document is still under study and subject to change. It should not be used for reference purposes.
Recipients of this document are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.

TITLE:
Rotating electrical machines – Part 2-3: Specific test methods for determining losses and efficiency of
converter-fed AC motor

PROPOSED STABILITY DATE: 2021

NOTE FROM TC/SC OFFICERS:


Copyright © 2018 International Electrotechnical Commission, IEC. All rights reserved. It is permitted to download this
electronic file, to make a copy and to print out the content for the sole purpose of preparing National Committee positions.
You may not copy or "mirror" the file or printed version of the document, or any part of it, for any other purpose without
permission in writing from IEC.

---------------------- Page: 3 ----------------------
oSIST prEN IEC 60034-2-3:2019
– 2 – IEC CDV 60034-2-3 © IEC 2018
CONTENTS
INTRODUCTION . 4
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 6
4 Symbols and abbreviated terms . 7
5 Basic requirements . 8
5.1 Instrumentation . 8
5.1.1 General . 8
5.1.2 Power analyser and transducers . 8
5.1.3 Mechanical output of the motor . 9
5.2 Converter set-up . 9
5.2.1 General . 9
5.2.2 Comparable converter set-up for rated voltages up to 1 kV . 9
5.2.3 Testing with converters with rated voltages above 1 kV . 10
5.2.4 Testing with other converters . 10
6 Test method for the determination of the efficiency of converter-fed motors . 10
6.1 Selection of determination method . 10
6.2 Method 2-3-A - Input-output method . 10
6.2.1 Test set-up . 10
6.2.2 Test procedure . 11
6.2.3 Efficiency determination . 11
6.2.4 Measurement at seven standardized operating points . 11
6.3 Method 2-3-B - Summation of losses with determination of additional high
frequency loss at converter supply at no-load operation . 11
6.3.1 Test set-up . 12
6.3.2 Test procedure . 12
6.3.3 Efficiency determination . 12
6.4 Alternate Efficiency Determination Method (AEDM) . 12
6.5 Determination of efficiency by calculation . 13
7 Interpolation of losses at any operating point . 13
7.1 Interpolation procedure . 13
7.2 Analytical determination of relative losses at any operating point . 13
7.3 Additional losses due to frequency converter voltage drop . 15
7.4 Alternate operating points to determine interpolation coefficients . 15
7.5 Optional determination of interpolation error . 16
Annex A (informative) Losses of AC motors . 17
2
A.1 Stator and rotor winding I R losses P (P + P ) . 17
LSR LS LR
A.2 Iron losses (P ) . 17
Lfe
A.3 Additional load losses (P ) . 17
LL
A.4 Friction and windage losses (P ) . 18
Lfw
A.5 Additional high frequency losses (P ) . 18
LHL
Annex B (informative) Exemplary determination of losses and efficiency at various load
points . 19
Bibliography . 21

Figure 1 – Standardized operating points . 14

---------------------- Page: 4 ----------------------
oSIST prEN IEC 60034-2-3:2019
IEC CDV 60034-2-3 © IEC 2018 – 3 –

Table 1 – Preferred test methods . 10
Table 2 – Other test methods . 10
Table 3 – Normative operating points . 14
Table 4 – Non-normative alternate operating points . 15
Table A.1 – Recommended split of windage and friction losses for IC 411 self-
ventilated motors . 18

Frei verwendbar

---------------------- Page: 5 ----------------------
oSIST prEN IEC 60034-2-3:2019
– 4 – IEC CDV 60034-2-3 © IEC 2018
1 INTERNATIONAL ELECTROTECHNICAL COMMISSION
2 ____________
3
4 ROTATING ELECTRICAL MACHINES –
5
6 Part 2-3: Specific test methods
7 for determining losses and efficiency of converter-fed AC motors
8
9 INTRODUCTION
10 The objective of this standard is to define test methods for determining total losses including
11 additional high frequency motor losses and efficiency of converter-fed motors. Additional high
12 frequency losses appear in addition to the losses on nominally sinusoidal power supply as
13 determined by the methods of IEC 60034-2-1. Results determined according to this standard
14 are intended to allow comparison of losses and efficiency of different motors when fed by
15 converters.
16 Furthermore, the standard gives seven standardized operating points to characterize the
17 development of losses and efficiency across the whole torque/speed range. An interpolation
18 procedure is provided to calculate losses and efficiency at any operating point (torque,
19 speed).
20 In power-drive systems (PDS), the motor and the frequency converter are often manufactured
21 by different suppliers. Motors of the same design are produced in large quantities. They may
22 be operated from the grid or from frequency converters of many different types, supplied by
23 many different manufacturers. The individual converter properties (switching frequency, DC
24 link voltage level, etc.) will also influence the system efficiency. As it is impractical to
25 determine motor losses for every combination of motor, frequency converter, connection
26 cable, output filter and parameter settings, this standard describes a limited number of
27 approaches, depending on the voltage level and the rating of the machine under test.
28 The losses determined according to this standard are not intended to represent the losses in
29 the final application. They provide, however, an objective basis for comparing different motor
30 designs with respect to suitability for converter operation.
31 In general, when fed from a converter, motor losses are higher than during operation on a
32 nominally sinusoidal system. The additional high frequency losses depend on the harmonic
33 spectrum of the impressed converter output quantity (either current or voltage) which is
34 influenced by its circuitry and control method. For further information, see IEC/TS 60034-25.
35 It is not the purpose of this standard to define test procedures either for power drive systems
36 or for frequency converters alone.
37 Comparable converter
38 Latest experience and theoretical analysis have shown that the additional high frequency
39 motor losses generally do not generally increase much with load. The methods in this
40 standard are mainly based on supplies from converters with pulse width modulation (PWM).
41 With respect to these types of converters and the growing need for verification of compliance
42 with national energy efficiency regulations, this standard defines a so-called comparable
43 converter for testing of low voltage motors.
44 In principle, the comparable converter is a voltage source with a typical high frequency
45 harmonic content supplying the machine under test. It is not applicable to medium voltage
46 motors.

---------------------- Page: 6 ----------------------
oSIST prEN IEC 60034-2-3:2019
IEC CDV 60034-2-3 © IEC 2018 – 5 –
47 Limitations for the application of the comparable converter
48 It has to be noted that the test method with the comparable converter described herein is a
49 standardized method intended to give comparable efficiency figures for standardized test
50 conditions. A motor ranking with respect to suitability for converter operation may be derived,
51 but it is not equivalent to determining of the actual motor losses for operation with a specific
52 converter which requires a test of the whole power drive system (PDS) with the specific
53 converter used in the final application.
54 Deviations are also expected for motors driven by multi-level voltage source or current source
55 converters where the additional high frequency motor losses differ much more depending on
56 speed and load than for two-level voltage source converters. Hence the determination of
57 losses and efficiency should preferably use procedures where the motor is operated together
58 with the same converter with which it is driven in service.
59 Another option is the determination of the additional high frequency motor losses by
60 calculation. If this is requested by the customer, the pulse pattern of the converter is required.
61 Such procedures are not part of this standard.
62 The provided interpolation procedure for the determination of losses and efficiency at any
63 operating point (torque, speed) is limited to the base speed range (constant torque range,
64 constant flux range).
65
Frei verwendbar

---------------------- Page: 7 ----------------------
oSIST prEN IEC 60034-2-3:2019
– 6 – IEC CDV 60034-2-3 © IEC 2018
66 ROTATING ELECTRICAL MACHINES –
67
68 Part 2-3: Specific test methods
69 for determining losses and efficiency of converter-fed AC motors
70
71
72
73 1 Scope
74 This standard specifies test methods and an interpolation procedure for determining losses
75 and efficiencies of converter-fed motors within the scope of IEC 60034-1. The motor is then
76 part of a variable frequency power drive system (PDS) as defined in IEC 61800-9-2.
77 Applying the approach of the comparable converter, the motor efficiency determined by use of
78 this standard is applicable for comparison of different motor designs only.
79 The standard also specifies procedures to determine motor losses at any load point (torque,
80 speed) within the base speed range (constant torque range, constant flux range) based on
81 determination of losses at seven standardized load points. This procedure is applicable to any
82 variable speed AC motor (induction and synchronous) rated according to IEC 60034-1 for
83 operation on a variable frequency and variable voltage power supply.
84 2 Normative references
85 The following documents, in whole or in part, are normatively referenced in this document and
86 are indispensable for its application. For dated references, only the edition cited applies. For
87 undated references, the latest edition of the referenced document (including any
88 amendments) applies.
89 IEC 60034-1, Rotating electrical machines – Part 1: Rating and performance
90 IEC 60034-2-1:2014, Rotating electrical machines – Part 2-1: Standard methods for
91 determining losses and efficiency from tests (excluding machines for traction vehicles)
92 IEC 60034-2-2, Rotating electrical machines – Part 2-2: Specific methods for determining
93 separate losses of large machines from test – Supplement to IEC 60034-2-1
94 IEC 61000-2-4, Electromagnetic compatibility (EMC) – Part 2-4: Environment – Compatibility
95 levels in industrial plants for low-frequency conducted disturbances
96 IEC TS 61800-8, Adjustable speed electrical power drive systems. – Part 8: Specification of
97 voltage on the power interface
98 IEC 61800-9-2:2017, Adjustable speed electrical power drive systems – Part 9-2: Ecodesign
99 for power drive systems, motor starters, power electronics & their driven applications - Energy
100 efficiency indicators for power drive systems and motor starters
101
102 3 Terms and definitions
103 For the purposes of this document the terms and definitions given in IEC 60034-1, IEC 60034-
104 2-1:2014 as well as the following apply.
105 3.1
106 motor losses with converter supply
107 When powered by a converter, motor losses are a combination of losses caused by
108 fundamental frequency and losses caused by the converter high frequencies.

---------------------- Page: 8 ----------------------
oSIST prEN IEC 60034-2-3:2019
IEC CDV 60034-2-3 © IEC 2018 – 7 –
109 3.2
110 fundamental losses
111 Fundamental losses in the motor can be segregated into five different components: iron
112 losses (varying with motor frequency and applied fundamental voltage), friction and windage
113 losses (varying with motor speed), rotor winding losses, stator winding losses and additional
114 load losses (all three varying with motor current). Fundamental losses are the losses of a
115 motor running with application of rated voltage at fundamental frequency that does not contain
116 any further high frequencies.
117 3.3
118 additional high frequency losses
119 Additional high frequency losses are produced in the motor by the non-sinusoidal voltage and
120 current waveforms generated by the converter and are in addition to the losses of iron, friction
121 and windage, rotor winding, stator winding and additional load loss (fundamental losses).
122 3.4
123 base speed range
124 The speed range from standstill up to the highest speed where the motor can be supplied with
125 a voltage that changes in proportion to the speed so that the magnetic flux remains constant
126 (constant ratio U/f) for induction machines and according to the MTPA (maximum torque per
127 ampere) for synchronous machines. Within the base speed range, the maximum motor torque
128 is constant (constant torque range), if constant flux control is used.
129 3.5
130 switching frequency
131 The switching frequency is the number of switching events of one semiconductor within one
132 second. It determines, together with the selected pulse pattern and the converter topology,
133 the lowest frequency of non-controllable high frequencies or inter-harmonics at the IPC (in-
134 plant point of coupling) or the motor.
135 NOTE For a two level converter, the pulse frequency measured phase to phase is two times the switching
136 frequency defined in 3.5 in case of continuous modulation and about 1.33 times the switching frequency defined in
137 3.5 in case of discontinuous modulation. A switching event is once on and once off of one semiconductor.
138
139 4 Symbols and abbreviated terms
140 For the purposes of this document the symbols given in IEC 60034-2-1, IEC TS 61800-8 as
141 well as the following apply.
142 PWM Pulse width modulation,
143 f Frequency, Hz,
144 f Fundamental motor frequency, Hz,
Mot
145 f Rated motor frequency, Hz,
N
146 f Switching frequency, Hz,
sw
147 I No-load current, A,
0
148 I Rated current, A,
N
149 MTPA Maximum torque per ampere control applied to interior permanent magnet
150 synchronous motors
–1
151 n Speed, min
–1
152 n Rated speed, min ,
N
–1
153 n Reference speed, min ,
ref
154 P Power, W,

155 P Constant losses at converter supply, W,
Ccon
Frei verwendbar

---------------------- Page: 9 ----------------------
oSIST prEN IEC 60034-2-3:2019
– 8 – IEC CDV 60034-2-3 © IEC 2018
156 P Constant losses at sinusoidal supply according to IEC 60034-2-1:2014, W,
Csin
157 PDS Power drive system,
158 P Additional high frequency loss due to converter supply, W,
LHL
159 P Rated power, W,
N
160 P Reference power, W,
ref
161 P Motor input power at converter supply, W,
1C
162 P Motor input power as tested according to IEC 60034-2-1:2014, W,
1_60034-2-1
163 P Motor output power at converter supply, W,
2C
164 P Motor output power as tested according to IEC 60034-2-1:2014, W,
2_60034-2-1
165 T Machine torque, Nm,
166 T Machine torque at converter supply, Nm,
C
167 T Rated torque, Nm,
N
168 T Reference torque, Nm,
ref
169 U Rated motor voltage, V.
N
170 η Efficiency.
171 5 Basic requirements
172 5.1 Instrumentation
173 5.1.1 General
174 Unless otherwise stated in this standard, the arithmetic average of the three line currents and
175 voltages shall be used.
176 When testing electric machines under load, slow fluctuations in the output power and other
177 measured quantities may be unavoidable. Therefore for each load point many readings shall
178 be taken automatically by a suitable digital meter over a period of at least 15 s but not more
179 than 60 s and this average shall be used for the determination of efficiency.
180 Considering the high frequencies involved in converters feeding AC motors and their
181 contribution to the motor losses, the measuring equipment has to be selected according to the
182 range of relevant frequencies with sufficient accuracy.
183 For temperature measurements, a thermosensor installed in the hot spot may be optionally
184 used, as described in IEC 60034-2-1:2014.
185 5.1.2 Power analyser and transducers
186 The instrumentation for measuring power and current at the motor’s input shall basically meet
187 the requirements of IEC 60034-2-1:2014, but due to higher frequency components the
188 following additional requirements shall also apply.
189 The specified uncertainty of the power meters shall be 0,2% of the rated apparent power of
190 the motor or better for the total active power at 50 or 60 Hz. This is the total uncertainty of the
191 power meter including possible sensors.
192 NOTE 1 For example, when a three-phase motor has a rated voltage of 400 V and a rated current of 10 A then the
193 power meter's active power uncertainty should be 0,2% of √3 times 4000 VA, which is 13,9 W or better.
194 The bandwidth of power meters and sensors shall be sufficiently wide that the error in the
195 measurement of total active power for the entire frequency range (beyond 50 Hz and 60 Hz) is
196 less than or equal to 0,3% of the apparent power.
197 NOTE 2 In general, a bandwidth from 0 Hz up to 10 times of switching frequency is sufficient.
198

---------------------- Page: 10 ----------------------
oSIST prEN IEC 60034-2-3:2019
IEC CDV 60034-2-3 © IEC 2018 – 9 –
199 It is preferred to feed current and voltage directly into the power analyser. If an external
200 current transducer is required, no conventional current transformers shall be used. Instead,
201 wide bandwidth shunts or zero-flux transducers shall be used.
202 Fundamental voltage shall be measured at the motor terminals using a digital power analyser
203 equipped with suitable software (FFT, Fast Fourier Transformation).
204 Internal line filters in digital power meters shall be turned off. Synchronization filters (also
205 known as zero-cross filters) that are not in the signal path may be used.
206 For power measurement, the three-wattmeter method is preferred. All cables used to transmit
207 measurement signals shall be shielded. It has to be noted, that the cable shield is not routed
208 through the current transformers.
209 5.1.3 Mechanical output of the motor
210 The instrumentation used to measure supply frequency shall have an accuracy of ±0,1% of
211 full scale. The speed measurement should be accurate within 0,1 revolution per minute for
-1
212 and 0,03% above.
speeds up to 3000 min
213 The instrumentation used to measure the torque shall have a minimum class of 0,2 when the
214 rated efficiency is expected to be below 90% and 0,1 or better for higher efficiencies. The
215 minimum torque measured shall be at least 10% of the torque meter’s nominal torque. If a
216 better class instrument is used, the allowed torque range can be extended accordingly.
217 5.2 Converter set-up
218 5.2.1 General
219 For all tests using the comparable converter, it should be parameterized according to the
220 requirements of this standard or, if a unique combination of converter and motor is to be
221 tested, the converter should be parameterized according to the specific application
222 requirements. The chosen parameter settings shall be recorded in the test report.
223 5.2.2 Comparable converter set-up for rated voltages up to 1 kV
224 The comparable converter has to be understood as a voltage source independent of load
225 current.
226 It has to be noted, that the so-called comparable converter operating mode is not intended or
227 requested for any commercial application, but it is a typical set-up. The purpose of the
228 comparable converter set-up is to establish comparable test conditions for motors designed
229 for operation with commercially available converters.
230 The reference conditions defined below shall only be used for verification of compliance with
231 national energy efficiency regulations, in particular the 90% speed and 100% torque load
232 point. For all other purposes including the interpolation procedure according to Annex A
233 preferably the original system configuration should be used.
234 The following reference conditions are defined:
235 • Two level voltage source converter.
236 • No additional components influencing output voltage or output current shall be
237 installed between the comparable converter and the motor, except those required for
238 the measuring instruments.
239 • Operation at 90% speed and rated torque with constant rated flux (approx. 90% of
240 rated voltage) for both induction machines and synchronous machines.
241 NOTE The rated flux is defined by the rated voltage given on the name plate of the motor. Therefore, a
242 measurement at the 90% speed and 100% torque point with rated flux will be fully replicable for regulation
243 authorities.
-1
244 • For motors with a rated speed up to 3600 min , the switching frequency shall not be
245 higher than 4 kHz.
Frei verwendbar

---------------------- Page: 11 ----------------------
oSIST prEN IEC 60034-2-3:2019
– 10 – IEC CDV 60034-2-3 © IEC 2018
-1
246 • For motors with a rated speed above 3600 min , the switching frequency shall not be
247 higher than 8 kHz.
248 NOTE The conductor cross-sectional area of the motor cable should be selected such that the voltage drop is
249 not significant at rated load. An example for a typical test setup can be found in IEC 61800-9-2.
250
251 5.2.3 Testing with converters with rated voltages above 1 kV
252 For converters with voltage ratings above 1 kV a generally accepted comparable converter
253 and cable length cannot be specified. Such motors, cables and specific converters can only
254 be tested as a complete power drive system because the pulse patterns of frequency
255 converters for higher output powers vary between manufacturers and differ greatly between
256 no-load and rated load.
257 5.2.4 Testing with other converters
258 Motors that are operated with converters that produce a voltage with less harmonic content
259 than in case of supply by the comparable converter, for example multi-level converters or
260 converters with higher switching frequencies, will typically have lower losses compared with
261 measurements made with the reference converter at 4 or 8 kHz switching frequency.
262 Reference measurements on such motors shall still be performed under the reference
263 conditions as given above. Motor efficiency values measured under non-reference conditions
264 can be provided in the motor documentation.
265 6 Test method for the determination of the efficiency of converter-fed motors
266 6.1 Selection of determination method
267 For the verification of the rated losses and energy efficiency according to energy efficiency
268 classification schemes, the preferred method 6.2 shall be applied. Verification may be
269 required by end-users and regulators.
270 Table 1 – Preferred test methods
Ref Method Description Subclause Required facility
2-3-A Input-output Torque measurement 6.2 Torque meter or dynamometer
for full-load; Comparable or
specific converter supply
271
272 Alternate efficiency determining methods according to 6.3, 6.4 and 6.5 may be used for other
273 requirements.
274 Table 2 – Other test methods
Ref Method Description Subclause Required facility
2-3-B Summation of losses Additional high 6.3 Sinusoidal supply and specific
frequency loss converter supply at no-load

determination with operation
converter for final
application
  6.4
  6.5
275
276 6.2 Method 2-3-A - Input-output method
277 6.2.1 Test set-up
278 This is a test method in which the mechanical power P of a machine is determined by
2C
279 measurement of the shaft torque and speed. The electrical power P of the stator is
1C
280 measured in the same test.

---------------------- Page: 12 ----------------------
oSIST prEN IEC 60034-2-3:2019
IEC CDV 60034-2-3 © IEC 2018 – 11 –
281 6.2.2 Test procedure
282 Tests shall be conducted with converter and an assembled motor with the essential
283 components in place, to obtain test conditions equal or very similar to normal operating
284 conditions.
285 Couple the motor under test to a load machine with a torque meter or a dynamometer.
286 Operate the machine under test at rated torque and speed until thermal equilibrium (rate of
287 change of 1 K or less per half hour) has been reached.
288 At the end of the heat run, record:
289 T Output torque at converter supply
C
290 n Speed
291 P Motor input power at converter supply
1C
292 Check the offset of the torque meter after stopping the machines. In case of permanent
293 magnet machines, physically uncouple the motor under test, in order to avoid residual torque
294 in unexcited condition induced by permanent magnets.
295 Correct the output torque T by the determined offset.
C
296 6.2.3 Ef
...