Information technology - Data centre facilities and infrastructures - Part 1: General concepts

This European Standard:
a) details the issues to be addressed in a business risk and operating cost analysis enabling application of an appropriate classification of the data centre;
b) defines the common aspects of data centres including terminology, parameters and reference models (functional elements and their accommodation) addressing both the size and complexity of their intended purpose;
c) describes general aspects of the facilities and infrastructures required to support effective operation of telecommunications within data centres;
d) specifies a classification system, based upon the key criteria of “availability”, “security” and “energy-efficiency” over the planned lifetime of the data centre, for the provision of effective facilities and infrastructure;
e) describes the general design principles for data centres upon which the requirements of the EN 50600 series are based including symbols, labels, coding in drawings, quality assurance and education.

Informationstechnik - Einrichtungen und Infrastrukturen von Rechenzentren - Teil 1: Allgemeine Konzepte

Technologie de l’information - Installation et infrastructures de centres de traitement de données - Partie 1: Concepts généraux

Informacijska tehnologija - Vzpostavitev podatkovnega centra in infrastruktura - 1. del: Splošna zasnova

Ta evropski standard:
a) podrobno opredeljuje, katera vprašanja je treba obravnavati pri poslovnih tveganjih in operativni analizi stroškov, ki omogoča uporabo primerne klasifikacije podatkovnega centra;
b) opredeljuje skupne vidike podatkovnih centrov, vključno s terminologijo, parametri in referenčnimi modeli (funkcijskimi elementi ter njihovo namestitvijo), ki obravnavajo velikost in kompleksnost njihove uporabe;
c) opisuje splošne vidike prostorov in infrastrukture, ki je potrebna za učinkovito delovanje telekomunikacij znotraj podatkovnih centrov;
d) podaja sistem klasifikacije za zahteve glede učinkovitosti prostorov in infrastrukture, ki je osnovan na ključnih merilih »dostopnosti«, »varnosti« in »energetske učinkovitosti« v predvidenem času delovanja podatkovnih centrov;
e) opisuje splošna načela za načrtovanje podatkovnih centrov, na katerih temeljijo zahteve skupine standardov EN 50600, vključno s simboli, oznakami, kodiranjem v skicah, zagotavljanjem kakovosti in izobraževanjem.

General Information

Status
Published
Publication Date
08-Aug-2019
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
25-Jul-2019
Due Date
29-Sep-2019
Completion Date
09-Aug-2019

Relations

Buy Standard

Standard
EN 50600-1:2019 - BARVE
English language
31 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 50600-1:2019
01-september-2019
Nadomešča:
SIST EN 50600-1:2013
Informacijska tehnologija - Vzpostavitev podatkovnega centra in infrastruktura - 1.
del: Splošna zasnova
Information technology - Data centre facilities and infrastructures - Part 1: General
concepts
Informationstechnik - Einrichtungen und Infrastrukturen von Rechenzentren - Teil 1:
Allgemeine Konzepte
Technologie de linformation - Installation et infrastructures de centres de traitement de
données - Partie 1: Concepts généraux
Ta slovenski standard je istoveten z: EN 50600-1:2019
ICS:
35.020 Informacijska tehnika in Information technology (IT) in
tehnologija na splošno general
SIST EN 50600-1:2019 en,fr
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 50600-1:2019

---------------------- Page: 2 ----------------------

SIST EN 50600-1:2019


EUROPEAN STANDARD EN 50600-1

NORME EUROPÉENNE

EUROPÄISCHE NORM
June 2019
ICS 35.020; 35.160 Supersedes EN 50600-1:2012
English Version
Information technology - Data centre facilities and infrastructures
- Part 1: General concepts
Technologie de l'information - Installation et infrastructures Informationstechnik - Einrichtungen und Infrastrukturen von
de centres de traitement de données - Partie 1: Concepts Rechenzentren - Teil 1: Allgemeine Konzepte
généraux
This European Standard was approved by CENELEC on 2019-04-29. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden,
Switzerland, Turkey and the United Kingdom.



European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2019 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
 Ref. No. EN 50600-1:2019 E

---------------------- Page: 3 ----------------------

SIST EN 50600-1:2019
EN 50600-1:2019 (E)

Contents
European foreword . 3
Introduction . 4
1 Scope . 6
2 Normative references. 6
3 Terms, definitions and abbreviations . 7
3.1 Terms and definitions . 7
3.2 Abbreviations . 11
4 Conformance . 11
5 Business risk analysis . 12
5.1 General . 12
5.2 Business impact analysis . 12
5.3 Risk analysis . 13
6 Data centre design overview . 14
6.1 General . 14
6.2 Spaces and facilities . 15
7 Classification system for the design of data centre facilities and infrastructures . 17
7.1 General . 17
7.2 Availability . 17
7.2.1 General . 17
7.2.2 Single-site data centres . 17
7.2.3 Multi-site data centres . 20
7.3 Physical security . 20
7.3.1 General . 20
7.3.2 Protection against unauthorised access . 20
7.3.3 Protection against intrusion . 20
7.3.4 Protection against environmental events . 21
7.4 Energy efficiency enablement. 21
7.4.1 General . 21
7.4.2 Power distribution system . 22
7.4.3 Environmental monitoring and control . 22
7.4.4 Operational processes and KPIs . 22
8 Design and implementation process . 22
8.1 General . 22
8.2 Design phases . 23
8.2.1 Phase 1 - Strategy . 23
8.2.2 Phase 2 - Objectives . 24
8.2.3 Phase 3 - System specifications. 24
8.2.4 Phase 4 - Design proposal . 24
8.2.5 Phase 5 - Decision . 25
8.2.6 Phase 6 - Functional design . 25
8.2.7 Phase 7 - Approval . 25
8.2.8 Phase 8 - Final design and project plan . 25
8.2.9 Phase 9 - Contract . 25
8.2.10 Phase 10 - Construction . 25
8.2.11 Phase 11 - Operation . 25
9 Design Principles . 26
9.1 Design reference documentation . 26
9.2 Design principles to support energy efficiency . 26
9.3 Design principles for EMI . 26
9.4 Design principles to support operational excellence . 26
Annex A (informative) Overall availability and infrastructure availability . 27
Annex B (informative) Availability description . 30
Bibliography . 31

2

---------------------- Page: 4 ----------------------

SIST EN 50600-1:2019
EN 50600-1:2019 (E)
European foreword
This document (EN 50600-1:2019) has been prepared by CLC/TC 215 “Electrotechnical aspects of
telecommunication equipment”.
The following dates are fixed:
• latest date by which this document has to be (dop) 2020–04–29
implemented at national level by publication of
an identical national standard or by
endorsement
• latest date by which the national standards (dow) 2022–04–29
conflicting with this document have to be
withdrawn

This document supersedes EN 50600-1:2012.
The following major modifications have been made compared to EN 50600-1:2012:
a) reference to Key Performance Indicators of EN 50600-4-X included;
b) Clause 7 (Availability) has been revised;
c) the design processes (Clause 8) and design principles (Clause 9) have been moved from an annex
to the main body of the document;
d) existing Annex A has been removed;
e) new Annexes A and B have been added.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a mandate given to CENELEC by the European Commission
and the European Free Trade Association.
3

---------------------- Page: 5 ----------------------

SIST EN 50600-1:2019
EN 50600-1:2019 (E)
Introduction
The unrestricted access to internet-based information demanded by the information society has led to an
exponential growth of both internet traffic and the volume of stored/retrieved data. Data centres are
housing and supporting the information technology and network telecommunications equipment for data
processing, data storage and data transport. They are required both by network operators (delivering
those services to customer premises) and by enterprises within those customer premises.
Data centres usually need to provide modular, scalable and flexible facilities and infrastructures to easily
accommodate the rapidly changing requirements of the market. In addition, energy consumption of data
centres has become critical both from an environmental point of view (reduction of environmental
footprint) and with respect to economical considerations (cost of energy) for the data centre operator.
The implementation of data centres varies in terms of:
a) purpose (enterprise, co-location, co-hosting or network operator facilities);
b) security level;
c) physical size;
d) accommodation (mobile, temporary and permanent constructions).
The needs of data centres also vary in terms of availability of service, the provision of security and the
objectives for energy efficiency. These needs and objectives influence the design of data centres in terms
of building construction, power distribution, environmental control, telecommunications cabling and
physical security as well as the operation of the data centre. Effective management and operational
information is required to monitor achievement of the defined needs and objectives.
Recognizing the substantial resource consumption, particularly of energy, of larger data centres, it is also
important to provide tools for the assessment of that consumption both in terms of overall value and of
source mix and to provide Key Performance Indicators (KPIs) to evaluate trends and drive performance
improvements.
At the time of publication of this European Standard, EN 50600 series is designed as a framework of
standards and technical reports covering the design, the operation and management as well as the key
performance indicators for energy efficient operation of the data centre.
The EN 50600-2 series defines the requirements for the data centre design.
The EN 50600-3 series defines the requirements for the operation and the management of the data
centre.
The EN 50600-4 series defines the key performance indicators for the data centre.
The CLC/TR 50600-99-X Technical Reports cover recommended practices and guidance for specific
topics around data centre operation and design.
This series of European Standards specifies requirements and recommendations to support the various
parties involved in the design, planning, procurement, integration, installation, operation and maintenance
of facilities and infrastructures within data centres. These parties include:
1) owners, operators, facility managers, ICT managers, project managers, main contractors;
2) consulting engineers, architects, building designers and builders, system and installation designers,
auditors, test and commissioning agents;
3) facility and infrastructure integrators, suppliers of equipment;
4) installers, maintainers.
4

---------------------- Page: 6 ----------------------

SIST EN 50600-1:2019
EN 50600-1:2019 (E)
The inter-relationship of the standards and technical reports within the EN 50600 series is shown in
Figure 1.

Figure 1 – Schematic relationship between EN 50600 series of standards
This European Standard specifies general requirements for data centres for all kinds of data centres
irrespective of their size and physical construction. It introduces a classification system for availability,
physical security and energy efficiency enablement.
EN 50600-2-X standards specify requirements and recommendations for particular facilities and
infrastructures to support the relevant classification for “availability”, “physical security” and “energy
efficiency enablement” selected from EN 50600-1.
EN 50600-3-X documents specify requirements and recommendations for data centre operations,
processes and management.
EN 50600-4-X documents specify requirements and recommendations for key performance indicators
(KPIs) used to assess and improve the resource usage efficiency and effectiveness, respectively, of a
data centre.
This European Standard is intended for use by and collaboration between architects, building designers
and builders, system and installation designers.
This series of European Standards does not address the selection of information technology and network
telecommunications equipment, software and associated configuration issues.
5

---------------------- Page: 7 ----------------------

SIST EN 50600-1:2019
EN 50600-1:2019 (E)
1 Scope
This document:
a) describes the general principles for data centres upon which the requirements of the EN 50600
series are based;
b) defines the common aspects of data centres including terminology, parameters and reference
models (functional elements and their accommodation) addressing both the size and complexity of
their intended purpose;
c) describes general aspects of the facilities and infrastructures required to support data centres;
d) specifies a classification system, based upon the key criteria of “availability”, “security” and “energy-
efficiency” over the planned lifetime of the data centre, for the provision of effective facilities and
infrastructure;
e) details the issues to be addressed in a business risk and operating cost analysis enabling application
of the classification of the data centre;
f) provides reference to operation and management of data centres;
g) introduces the concepts of Key Performance Indicators (KPIs) for resource management of data
centre facilities and infrastructures.
The following topics are outside of the scope of this series of European Standards:
1) the selection of information technology and network telecommunications equipment, software and
associated configuration issues are outside the scope of this European Standard;
2) quantitative analysis of overall service availability resulting from multi-site data centres;
3) safety and electromagnetic compatibility (EMC) requirements (covered by other standards and
regulations. However, information given in this European Standard can be of assistance in meeting
these standards and regulations).
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 50600-2-1, Information technology - Data centre facilities and infrastructures - Part 2-1: Building
construction
EN 50600-2-2, Information technology - Data centre facilities and infrastructures - Part 2-2: Power supply
and distribution
EN 50600-2-3, Information technology - Data centre facilities and infrastructures - Part 2-3: Environmental
control
EN 50600-2-4, Information technology - Data centre facilities and infrastructures - Part 2-4:
Telecommunications cabling infrastructure
EN 50600-2-5, Information technology - Data centre facilities and infrastructures - Part 2-5: Security
systems
6

---------------------- Page: 8 ----------------------

SIST EN 50600-1:2019
EN 50600-1:2019 (E)
EN 50600-3-1, Information technology - Data centre facilities and infrastructures - Part 3-1: Management
and operational information
EN 50600-4-X (all parts), Information technology – Data centre facilities and infrastructures – Part 4-X
3 Terms, definitions and abbreviations
3.1 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
• IEC Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http://www.iso.org/obp
3.1.1
availability
ability of an item to be in a state to perform a required function under given conditions at a given instant of
time or over a given time interval, assuming that the required external resources are provided
[SOURCE: IEC 60050-191:1990, 191-02-05]
3.1.2
building entrance facility
facility that provides all necessary mechanical and electrical services and which complies with all relevant
regulations for the entry of specific services or infrastructures into a building
[SOURCE: EN 50173-1:2018, 3.1.18 – modified: replaced “telecommunication cables” with “specific
infrastructures or services” and deleted „and which can enable transmission from outdoor to indoor
cable”]
3.1.3
building security
facilities and systems necessary to provide the required levels of security at the entrance to and within the
building containing the data centre
3.1.4
cabinet
enclosed construction for housing closures and other information technology equipment
[SOURCE: EN 50174-1:2018, 3.1.7]
3.1.5
co-hosting data centre
data centre in which multiple customers are provided with access to network(s), servers and storage
equipment on which they operate their own services/applications
Note 1 to entry: Both the information technology equipment and the support infrastructure of the building are provided
as a service by the data centre operator.
[SOURCE: EN 50174-2:2018, 3.1.2]
7

---------------------- Page: 9 ----------------------

SIST EN 50600-1:2019
EN 50600-1:2019 (E)
3.1.6
co-location data centre
data centre in which multiple customers locate their own network(s), servers and storage equipment
Note 1 to entry: The support infrastructure of the building (such as power distribution and environmental control) is
provided as a service by the data centre operator.
[SOURCE: EN 50174-2:2018, 3.1.3]
3.1.7
computer room space
area within the data centre that accommodates the data processing, data storage and telecommunication
equipment that provides the primary function of the data centre
3.1.8
control room space
area within the data centre used to control the operation of the data centre and to act as a central point
for all control and monitoring functions
3.1.9
data centre
structure, or group of structures, dedicated to the centralised accommodation, interconnection and
operation of information technology and network telecommunications equipment providing data storage,
processing and transport services together with all the facilities and infrastructures for power distribution
and environmental control together with the necessary levels of resilience and security required to provide
the desired service availability
Note 1 to entry: A structure can consist of multiple buildings and/or spaces with specific functions to support the
primary function.
Note 2 to entry: The boundaries of the structure or space considered the data centre which includes the information
and communication technology equipment and supporting environmental controls can be defined within a larger
structure or building.
3.1.10
data centre security
facilities and systems that provide the required levels of security at the entrance to and within the data
centre
3.1.11
demarcation point
point where the operational control or ownership changes
3.1.12
electrical distribution space
area used for housing facilities to distribute electrical power between the transformer space and electrical
spaces within the data centre or elsewhere within the premises or individual buildings within the premises
3.1.13
electrical space
area within the data centre used for housing facilities to deliver and control electrical power to the data
centre spaces (including switchboards, batteries, uninterruptible power systems (UPS) etc.)
3.1.14
enterprise data centre
data centre that is operated by an enterprise which has the sole purpose of the delivery and management
of services to its employees and customers
[SOURCE: EN 50174-2:2018, 3.1.8]
8

---------------------- Page: 10 ----------------------

SIST EN 50600-1:2019
EN 50600-1:2019 (E)
3.1.15
external premises security
facilities and systems that provide the required levels of security for the area between the building and the
boundary of the premises
3.1.16
energy efficiency enablement
ability to measure the energy consumption and to allow calculation and reporting of energy efficiency of
the various facilities and infrastructures
3.1.17
facility
spaces and pathways that accommodate a specific infrastructure
3.1.18
functional capability
ability of the data centre (or system or subsystem) to deliver its intended function
3.1.19
functional element
source of supply, device or path
3.1.20
generator space
area used for housing the installation of electrical power supply generation equipment together with
control systems, storage of associated fuels or energy conversion equipment
3.1.21
holding space
area within the data centre used for the holding of equipment prior to being brought into service or having
been taken out of service
3.1.22
infrastructure
technical systems providing functional capability of the data centre (e.g. power distribution, environmental
control and physical security)
3.1.23
main distributor
distributor used to make connections between the main distribution cabling subsystem, network access
cabling subsystem and active equipment
[SOURCE: EN 50173-5:2018, 3.1.10]
3.1.24
mechanical space
area that is used for housing mechanical equipment and infrastructure that provides environmental
control for the data centre spaces (including chillers and water treatment, air handling and fire
suppression systems)
3.1.25
network operator data centre
data centre that has the primary purpose of the delivery and management of broadband services to the
operators’ customers
[SOURCE: EN 50174-2:2018, 3.1.18]
9

---------------------- Page: 11 ----------------------

SIST EN 50600-1:2019
EN 50600-1:2019 (E)
3.1.26
physical security
active and passive measures (combining physical and technological controls), procedures and
responsibilities to maintain the desired level of availability for the facilities and infrastructures of the data
centres in relation to access control and environmental events
3.1.27
planned downtime
period of time during which a system or subsystem does not provide functional capability whilst it
undergoes maintenance or is switched off to test the response of a related system or subsystem
3.1.28
premises entrance facility
space that provides all necessary mechanical and electrical services for the entry of cables into the
premises
3.1.29
storage space
area where general goods and/or data centre goods to be used in the premises and data centre are
stored
3.1.30
system
set of interrelated functional elements considered in a defined context as a whole and separated from
their environment
3.1.31
telecommunications
technology concerned with the transmission, emission, and reception of signs, signals, writings, images,
and sounds, by cable, radio, optical, or other electromagnetic systems
Note 1 to entry: The term telecommunications has no legal meaning when used in this document
[SOURCE: EN 50173-1:2018, 3.1.49]
3.1.32
telecommunications cabling
telecommunications cabling infrastructure from the telecommunications space(s) to the premises
entrance facility
3.1.33
telecommunication equipment
equipment within the data centre that provides telecommunication services within the data centre
3.1.34
telecommunications space
area which may house demarcation points and telecommunication equipment associated with the building
entrance facility and which may allow service providers restricted access to the data centre
3.1.35
testing space
area within the data centre used for the testing and configuring of equipment prior to being brought into
service
Note 1 to entry: Testing space is sometimes called staging area.
10

---------------------- Page: 12 ----------------------

SIST EN 50600-1:2019
EN 50600-1:2019 (E)
3.1.36
transformer space
area used for housing equipment necessary to convert voltage levels and/or provide necessary isolation
for the connection to the equipment within the premises or individual buildings within the premises
3.1.37
uninterruptible power system
combination of convertors, switches and energy storage devices (such as batteries), constituting a power
system for maintaining continuity of load power in case of input power failure
Note 1 to entry: Continuity of load power occurs when voltage and frequency are within rated steady-state and
transient tolerance bands and with distortion and interruptions within the limits specified for the output port. Input
power failure occurs when voltage and frequency are outside rated steady-state and transient tolerance bands or with
distortion or interruptions outside the limits specified for the UPS.
[SOURCE: EN 62040-1:2017, 3.101]
3.1.38
unplanned downtime
time taken, following a failure of functional capability, to repair the relevant infrastructure together with the
“re-boot” time necessary to recover functional capability following that repair
3.2 Abbreviations
For the purposes of this document the following abbreviations apply:
CRAC Computer Room Air Conditioning (Unit)
CRAH Computer Room Air Handler units
EMI electromagnetic interference
ffs for further study
MTBF Mean Time Between Failures
MTTR Mean Time To Repair
NOC Network Operating Centre
UPS Uninterruptible Power System
4 Conformance
For a data centre design to conform to this European Standard:
a) a business risk analysis according to Clause 5 shall be completed;
b) an appropriate Availability Class in 7.2 shall be selected using a business risk analy
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.